ABB REC 561 User Manual page 484

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00
6.2.6 BB_ES
Interlocking
Table 10: Output signals for A1A2_DC
OUT:
IIxx-Q11CLREL
IIxx-Q11CLITL
IIxx-DCOPTR
IIxx-DCCLTR
IIxx-VPDCTR
Table 11: Input signals for BB_ES
IN:
IJxx-Q15_OP
IJxx-Q15_CL
IJxx-ABCDC_OP
IJxx-VP_ABCDC
IJxx-EXDUP_BB
IJxx-EXVVA_BB
Table 12: Output signals for BB_ES
OUT:
IJxx-Q15REL
IJxx-Q15ITL
IJxx-BBESOPTR
IJxx-BBESCLTR
1MRK 580 151-XEN
DESCRIPTION:
For GIS closing of Q11 is allowed
For GIS closing of Q11 is forbidden
Signal is 1 if the bus section disconnector is
open
Signal is 1 if the bus section disconnector is
closed
Switch status of Q11 is valid (open or
closed)
DESCRIPTION:
Signal is 1 if Q15 on this busbar part is open
Signal is 1 if Q15 on this busbar part is
closed
Signal is 1 if all disconnectors on this busbar
part are open
The switch status of all disconnectors on
this busbar part are valid.
Signal is 1 if no transmission error from any
bay containing all disconnectors on this bus-
bar part
Signal is 1 if the interlocking programs in all
bays containing all disconnectors on this
busbar part are running
DESCRIPTION:
Switching of Q15 is allowed
Switching of Q15 is forbidden
Signal is 1 if Q15 on this busbar part is open
Signal is 1 if Q15 on this busbar part is
closed
Page