7.2.7 COMCON
Apparatus control
Table 13: Input signals for COMCON
IN:
COxx-SEL_RES
COxx-SELECT
COxx-R_SEL_O
COxx-R_SEL_C
COxx-R_OPEN
COxx-R_CLOSE
COxx-R_CANCEL
COxx-REMOTE
COxx-S_SEL_O
COxx-S_SEL_C
COxx-S_OPEN
COxx-S_CLOSE
COxx-S_CANCEL
COxx-S_BLK_OP
COxx-S_DBL_OP
COxx-S_IR_OVR
COxx-S_BL_UPD
COxx-S_PR_UPD
COxx-S_MA_U_O
COxx-S_MA_U_C
COxx-STATION
COxx-L_SEL_O
1MRK 580 150-XEN
DESCRIPTION:
Input for reset of selection after operation
Input stating that a correct selection and
reservation is made in the bay
Selection for opening the apparatus from
Remote (pulse input)
Selection for closing the apparatus from
Remote (pulse input)
Execute command for opening the appara-
tus from Remote (pulse input)
Execute command for closing the apparatus
from Remote (pulse input)
Input for cancelling an operation from
Remote (pulse input)
Input for indicating Remote as valid operator
place
Selection for opening the apparatus from
Station (pulse input)
Selection for closing the apparatus from
Station (pulse input)
Execute command for opening the appara-
tus from Station (pulse input)
Execute command for closing the apparatus
from Station (pulse input)
Input for cancelling an operation from Sta-
tion (pulse input)
Input for blocking operation from Station
(pulse input)
Input for deblocking operation from Station
(pulse input)
Input for overriding selection and reserva-
tion from Station (pulse input)
Input for blocking process updating from
Station (pulse input)
Input for resuming process updating from
Station (pulse input)
Input for manual entry of open position from
Station (pulse input)
Input for manual entry of close position from
Station (pulse input)
Input for indicating Station as valid operator
place
Selection for opening the apparatus from
Local
Page
6 - 85