Setting Table - ABB REC 561 User Manual

Bay level control terminal
Table of Contents

Advertisement

ABB Network Partner AB
Version 1.0-00

5.3 Setting table

PARAMETER:
Operation
InputPhase
UMeasure
(For two bay version)
AutoEnerg
ManEnerg
UHigh
ULow
FreqDiff
PhaseDiff
Udiff
tAutoEnerg
tManEnerg
For the second breaker in
the bay, inputs and outputs
are named SYN2.
The version for two bays
also includes inputs and
outputs for SYN3 and SYN4
Synchronism and energizing
check for double circuit breakers
and voltage selection
SETTING RANGE:
Off, Release, On
L1, L2, L3,
L1 - L2, L2 - L3, L3 - L1
Ph/N, Ph/Ph
Off, DLLB, DBLL,
Off DLLB, DBLL,
Both
(70 - 100)% of Ur/sqr3
(10 - 80)% of Ur/sqr3
(0.05 - 0.30)Hz
(5 - 75)degrees
(5 - 50)% of Ur/sqr3
(0.00 - 1.00)seconds
(0.00 - 1.00)seconds
DESCRIPTION:
Function execution
Voltage reference selection. L1, L2, L3 are
phase-neutral. L1-L2, L2-L3, L3-L1 are
phase-phase
Voltage reference selection, phase-neutral
or phase-phase
Both
Auto energizing check:
• Off=Not in use
• DLLB=Dead line live bus
• DBLL=Dead bus live line
• Both=DLLB or DBLL
Manual energizing check:
• Off=Not in use
• DLLB=Dead line live bus
• DBLL=Dead bus live line
• Both=DLLB or DBLL
High-voltage limit
Low-voltage limit
Frequency-difference limit
Phase-difference limit
Voltage-difference limit
Auto-energizing time delay
Manual-energizing time delay
1MRK 580 167-XEN
Page
5 - 47