ABB REC 561 User Manual page 351

Bay level control terminal
Table of Contents

Advertisement

1MRK 580 150-XEN
Page
6 - 66
Apparatus control
Table 3: Input signals for BAYCONB
IN:
BBxx-ACK_F_B
BBxx-ANY_ACK
BBxx-V_TX
BBxx-EX_DA_UP
BBxx-RE_RQ_B
BBxx-V_RE_RQ
Table 4: Output signals for BAYCONB
OUT:
BBxx-REMOTE
BBxx-STATION
BBxx-LOCAL
BBxx-EXCH_OUT
BBxx-SEL1
BBxx-SEL2
BBxx-SEL3
BBxx-SEL4
BBxx-SEL5
BBxx-SEL6
BBxx-SEL7
BBxx-SEL8
BBxx-RE
BBxx-RE_BAYS
BBxx-ACK_T_B
ABB Network Partner AB
DESCRIPTION:
Input for acknowledging the reservation of
other bays
Input indicating that at least one acknowl-
edge is still active
Indication for valid transmission of the reser-
vation signals
Input is 1 if the program that acknowledged
the reservation is running
Request for reservation from other bays
Input is 1 for valid request of reservation
from any bay
DESCRIPTION:
Indication of Remote operator place
Indication of Station operator place
Indication of Local operator place
Output for information exchange with other
BAYCON:s in bays with more than 8 appa-
ratuses
Apparatus 1 is selected after reservation
acknowledgement from other bays
Apparatus 2 is selected after reservation
acknowledgement from other bays
Apparatus 3 is selected after reservation
acknowledgement from other bays
Apparatus 4 is selected after reservation
acknowledgement from other bays
Apparatus 5 is selected after reservation
acknowledgement from other bays
Apparatus 6 is selected after reservation
acknowledgement from other bays
Apparatus 7 is selected after reservation
acknowledgement from other bays
Apparatus 8 is selected after reservation
acknowledgement from other bays
A reservation has been made in this bay
Request for reservation of other bays
Acknowledgement to other bays that this
bay is reserved
Version 1.0-00