4.1.4 Termination of the
test
Auto-reclosing - Single- and/or
three-phase
3.4 Lack of verification from synchro-check: Check the function at non-
acceptable voltage conditions. Wait for time out, >5 s. No reclosing.
3.5 Operation Stand by and Off: Check that no reclosing can occur with
the function in Off state.
3.6 Depending on the program selection and the selected fault types that
start and inhibit reclosing, a check of no unwanted reclosing can be
made. For example, if only single-phase reclosing is selected, a test
can verify that there is no reclosing after three-phase tripping.
After the tests, restore the equipment to normal or desired state.
Especially check these items:
4.1 Reclosing operate counters: Check and record the counter contents.
(Reset if it is the user's preference.)
MMI tree:
Service report
AR Counters
AR01-Counters (for AR No. 1)
4.2 Setting parameters, and Operation as required.
4.3 Test switch or disconnected links of connection terminals.
4.4 Normal indications.
(If so preferred, the disturbance report may be cleared.)
MMI tree:
Disturb. Report
Clear DistRep
ABB Network Partner AB
Clear Counters
Version 1.0-00