EN
5.1. Function test
BEKOMAT
8/9
®
Testing normal function
To test the solenoid valve, press the test button briefly (for approx. 2 seconds).
Red "ALARM" LED flashes, yellow "VALVE" led is lit
Valve to condensate discharge is opened
Testing alarm function
To test the solenoid valve alarm function, close the condensate inlet and press and
hold the test button for approx. 1 minute.
Alarm relay switches over
Release TEST button
BEKOMAT
returns to normal mode operation
®
•
Condensate inlet is again open!
•
Min. operating pressure 0.5 bar!
Installation and operating manual
19