2.11 Model LWO450 Output Module (100 to 200 VAC Contact Output,
16 Points)
Item
Output points
Insulation method
Rated output
Maximum output voltages
Minimum output current
Maximum rush current
OFF→ON
Response time
ON→OFF
Maximum switching frequency 1,800 times per hour
Service life (electrical) of relay
Internal
12 VDC
consumption
5 VDC
current
Points per common
Insulation withstand voltage
Connection
Applicable
cable size
External wiring
Tightening
torque
Maximum
wiring
length
Operation indication
Mass
Load
L
L
Fuse
100-220
VAC
L
L
2 SPECIFICATIONS OF INDIVIDUAL MODULES
16
Relay
100 to 220 VAC: 2 A per point, 5 A per common
12 to 24 VDC: 2 A per point, 5 A per common
48 VDC: 0.5 A per point
100 to 110 VDC: 0.2 A per point
250 VAC, 125 VDC
20 mA
5 A, 100 ms or less
15 ms or less
15 ms or less
Approx. 100,000 cycles of make-and-break operation (2 A at
220 VAC [COS φ = 0.4], 2 A at 24 VDC [L/R = 7 ms], make-
and-break operation frequency of 1,800 cycles per hour,
normal temperature and normal humidity)
22 mA × n, where n is the number of points in ON state.
25 mA
8
1,500 VAC, 1 minute (between external terminal and ground)
20-point terminal block connector (Connector screw type:
M3)
2
0.5 to 1.25 mm
0.6 to 0.8 N·m
200m
LED (lit when the module is powered on)
410 g
1
C0
2
0
RY
9
7
10
C1
11
C2
12
8
RY
19
F
20 C3
Specification
2-15
LWO450
DO
0
8
1
9
2
A
3
B
4
C
5
D
6
E
7
F
D.OUTPUT
AC100-200V
C0
1
0
2
1
3
2
4
3
5
4
6
5
7
6
8
7
9
C1
10
C2
11
8
12
9
13
A
14
B
15
C
16
D
17
E
18
F
19
C3
20
HITACHI