3.2 Installation Environment

The programmable controller and I/O modules mounted in it must be used within the installation
environment specified in Table 3-1. To ensure a long-term stable performance of these
hardware products, the user is recommended to use them at normal temperature and normal
humidity (15 to 35°C, 45 to 85%RH). If they are used in a high-temperature and high-humidity
environment or an environment where the temperature fluctuates widely between day and night,
their useful service life will be shortened.
Power supply
voltage
Power supply
voltage range
Ambient
temperature
Ambient
humidity
Vibration
resistance
Shock
resistance
Ambient air
(cleanliness)
It may happen that the input voltage of the power supply module is within the
above specifications but it is close to the upper or lower limit. In these cases,
the user is advised to consider the input voltage as being abnormal and ask a
power supply management specialist for inspection of the module.

Table 3-1 Installation Environment Specifications

100 to 120 VAC, single phase, 50/60 ±5 Hz for model LWV450;
100 to 120 VAC, single phase, 50/60 ±5 Hz, 100 to 110 VDC for
model LWV460;
100 to 110 VDC for model LWV550
85 to 132 VAC for model LWV450;
85 to 132 VAC, 80 to 143 VDC for model LWV460;
80 to 143 VDC for model LWV550
During operation, 0 to 55°C; During storage, -20 to 70°C
(Temperature ramp rate: 10°C/hour or less)
During operation, 30 to 90%RH; During storage, 10 to 90%RH
(non-condensing)
Conforming to JIS C0040 standard;
Frequency, 10 to 150 Hz;
Acceleration, 10 m/s
Directions, X, Y, and Z;
Sweep time, 8 minutes;
Sweep cycles, 20
Conforming to JIS C0041 standard;
Peak acceleration, 147 m/s
Half-sine pulses;
Directions, X, Y, and Z; 3 times in each direction
Class 1 million, with no corrosive gases