Huawei iBAT 2.0-CIM01C2 Quick Manual page 13

Hide thumbs Also See for iBAT 2.0-CIM01C2:
Table of Contents

Advertisement

2. Open Internet Explorer, choose Tools > Internet Options > Advanced, and select Use TLS
1.1 and Use TLS 1.2.
3. Enter https://CIM IP address in the address box of Internet Explorer to log in to the iBOX
WebUI home page.
In this document, the CIM WebUI parameters are obtained from CIM V296B017.
On the CIM WebUI, the CIM is named iBOX and the BIM is named iBAT.
The preset user name is admin. The preset password is Changeme. To ensure access security,
change the password upon first use.
If you forget the IP address, hold down the Default button on the CIM for more than 10 seconds.
Then the ALM indicator blinks at short intervals, and the CIM IP address is restored to the
factory default setting (192.168.0.10).
4. Access the System Settings > Batt. String Config page, and set Batt. String Config parameters
according to the following table.
Batt. String Config
Current acquisition
source
Battery N line
Single batt. group
number of HALL
Single batt. capacity
Batt. installation time
iBAT number of iBOX
Number of battery strings
Batt. string No.
5. Access the System Settings > Running parameter page, and set Running parameter
parameters according to the following table.
Running parameter
Parallel Communication
Configuration
Basic Information
HALL Rerverse Config
Description
The actual specifications of the Hall effect sensor prevail.
Set whether there is a battery N wire according to the actual situation.
Indicates the number of Hall effect sensors connected to a single
battery string.
Specifies the capacity of each battery that is connected in the battery
string in series.
Time when the battery is installed for the first time.
Indicates the total number of iBATs managed by the iBOX.
Indicates the total number of battery strings managed by the iBOX.
Sets the battery string numbers of the iBOXs connected in parallel to
unique ones when multiple iBOXs are connected in parallel.
Description
This parameter needs to be set when multiple iBOXs are connected in
parallel and does not need to be set when there is only one iBOX. Set
Whether the iBOX communicates directly with the NetEco to Yes,
and set Number of iBOX configured under each UPS. Configure IP
addresses for multiple iBOXs.
If a BCB box is configured, set BCB configuration to Done and Batt.
abnormal BCB trip to Enable.
If the Hall effect sensor is reversely installed, you can set reverse
connection to correct it.
13