Room temperature controller for four-pipe fan coil units

Advertisement

Use

Functions

CE1N3023en
2017-11-14
Room Temperature Controller
for four-pipe fan coil units
Outputs for on / off valve actuators
Outputs for three-speed fan
Control depending on room or return air temperature
Operating Modes: normal, energy saving and frost protection or OFF
Operating mode changeover input for remote control
Selectable control parameters
Operating voltage AC 230 V

Typical use:

Control of the room temperature in individual rooms that are heated or cooled with
four-pipe fan coil units.
For opening or closing a valve
for switching a three-speed fan.
The controller acquires the room temperature with its integrated sensor or external
room temperature sensor (QAA32) or external return air temperature sensor (QAH11.1)
- if used - and maintains the setpoint by delivering control commands to the 2-point-
valve.
The switching differential is adjustable. It can be 1 or 4 K in heating mode and
0.5 or 2 K in cooling mode.
3
RCC30
Building Technologies
023

Advertisement

Table of Contents
loading

Summary of Contents for Siemens RCC30

  • Page 1 RCC30 Room Temperature Controller for four-pipe fan coil units Outputs for on / off valve actuators Outputs for three-speed fan Control depending on room or return air temperature Operating modes: normal, energy saving and frost protection or OFF Operating mode changeover input for remote control...
  • Page 2 Manipulated variable "Heating valve" Manipulated variable "Cooling valve" ? SDC ? SDC The RCC30 provides control either depending on the measured room temperature or Return air tempera- depending on the fan coil unit’s return air temperature. Changeover is automatic if a ture QAH11.1 cable temperature sensor is connected to the device.
  • Page 3 Room sensor 1747 QAA32 Motoric on/off actuator 4863 SFA21... Thermal actuator (for radiator valve) 4893 STA21... Thermal actuator (for small valve 2,5 mm) 4878 STP21... *) The documents can be downloaded from http://siemens.com/bt/download. Siemens Room temperature controller CE1N3023en Building Technologies 2017-11-14...
  • Page 4 Frost protection function enabled enabled Switching differential 1 K in heating mode 4 K in heating mode 0.5 K in cooling mode 2 K in cooling mode Dead zone in normal operation Factory setting Siemens Room temperature controller CE1N3023en Building Technologies 2017-11-14...
  • Page 5 Directive 2012/19/EU and may not be disposed of as domestic garbage. ∂ Dispose of the device through channels provided for this purpose. ∂ Comply with all local and currently applicable laws and regulations. Siemens Room temperature controller CE1N3023en Building Technologies 2017-11-14...
  • Page 6 The product environmental declaration CE1E3020 contains data on envi- Environmental ronmentally compatible product design and assessments (RoHS compli- compatibility ance, materials composition, packaging, environmental benefit, disposal). *) The documents can be downloaded from http://siemens.com/bt/download. Siemens Room temperature controller CE1N3023en Building Technologies 2017-11-14...
  • Page 7 Connection diagram Return air temperature sensor (QAH11.1) T h r e e - s p e e d f a n RCC30 room temperature controller External operating mode changeover switch Zone valve MVE.../ MXE... for heating mode Zone valve MVE.../ MXE... for cooling mode...
  • Page 8 Dimensions unit 42,8 96,6 baseplate Issued by © Siemens Switzerland Ltd, 2002 - 2017 Siemens Switzerland Ltd. Technical specifications and availability subject to change without notice. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6300 Zug Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies...

Table of Contents