Huawei NetCol5000-A User Manual page 83

Acc precision air conditioner controller
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

ACC Precision Air Conditioner Controller
User Manual
Menu
Home
Screen >
Settings >
System
Settings >
Drain
Device
Home
Screen >
Settings >
Quick
Settings
Issue 02 (2016-11-30)
Parameter
Description
Water supply
After the humidification, the
rate
water supply time is calculated
as follows: Water supply time
= Water supply time x Water
supply rate.
Low float fall
When the low float rises, the
pump off delay
water pump begins to drain
water. When the low float
drops, the water pump will be
shut down after the time delay.
High float fall
When the high float drops, the
pump off delay
water pump will be shut down
after the time delay.
Low float rise
Sets the time delay for
delay
reporting an alarm and
shutting down the water pump
after the low float rises (if the
low float rises and does not
drop for a certain period, the
float is faulty or the water is
not properly drained).
High float rise
Sets the time delay for
delay
reporting an alarm and
shutting down the water pump
after the high float rises (if the
high float rises and does not
drop for a certain period, the
float is faulty or the water is
not properly drained).
Full water signal
Indicates the time delay for
delay
reporting a full water alarm
after the high float rises (the
system is shut down but the
water pump keeps running).
L-flt rise stdby
Indicates the time delay for
pump on delay
starting the standby pump after
the low float rises.
Language
Sets the interface language to
Settings
Chinese or English.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A Parameter Description
Default Value
humidifier: 62s
150%
NetCol5000-A035
(025): 8s
NetCol5000-A020,
NetCol5000-C:
240s
NetCol5000-A035
(025): 25s
NetCol5000-A020,
NetCol5000-C:
300s
NetCol5000-A035
(025): 300s
NetCol5000-A020,
NetCol5000-C:
600s
NetCol5000-A035
(025): 300s
NetCol5000-A020,
NetCol5000-C:
600s
NetCol5000-A035
(025),
NetCol5000-A020
: 60s
NetCol5000-C:
180s
120s
Consistent with the
current interface
language
77

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-aNetcol5000-cNetcol8000-c

Table of Contents