11.03
Note:
3.)
MD 36955 $MA_SAFE_STOP_SWITCH_TIME_F[AX1] = 3.5;
3.5 s because ESR was parameterized to 3.1 s
MD 36955 $MA_SAFE_STOP_SWITCH_TIME_F[AX2] = 3.5;
3.5 s because ESR was parameterized to 3.1 s
An ESR can be initiated in this time. This is the reason that here it makes sense
to use the same time as in $MA_ SAFE_STOP_SWITCH_TIME_E.
4.)
MD 10089 $MN_SAFE_PULSE_DIS_TIME_BUS_FAIL[AX1] = 0.5;
0.5 s because ESR was parameterized to 0.2 s
An ESR can be autonomously executed in the drive (drive-based function) in
this time. This time should therefore be adapted to the parameterization of the
drive MD $MD_RETRACT_TIME (in this particular example, 200 ms).
In this example, the system does not wait for this time in the following specific
cases
-
-
-
5.)
MD 36977 $MA_SAFE_EXT_STOP_INPUT[3,AX1]=04010109
Assignment to the SPL: OUTSI[09]
MD 36977 $MA_SAFE_EXT_STOP_INPUT[3,AX2]=04010109
Assignment to the SPL: OUTSI[09]
DB axis DBX32.5
DB axis DBX111.7 includes the checkback signal "Stop E active"
6.)
MD 36951 $MA_SAFE_VELO_SWITCH_DELAY[AX1]=4.1s
MD 36951 $MA_SAFE_VELO_SWITCH_DELAY[AX2]=4.1s
A value (1 s + retraction time) must be entered, for all axes, in the MD 36951
(delay time SG and SBH). After 1 s, the defective door switch is detected with
Alarm 27090, crosswise data comparison and Stop E is initiated. Depending on
the selected SG stage, retraction motion is executed. If this time is significantly
© Siemens AG 2003 All Rights Reserved
SINUMERIK 840D/SIMODRIVE 611 digital SINUMERIK Safety Integrated (FBSI) - Edition 11.03
The safe operating stop is activated after this time has expired.
This is the reason that this transition time for the Stop E must
correspond to the ESR times
($MC_ESR_DELAY_TIME1 + $MC_ESR_DELAY_TIME2). If this
time is selected to be too short, then the retraction motion will not
be correctly executed and depending on the safe functions, hard
stops will be initiated (Alarm 27024 Stop A/B).
Delaying stops following a stop F
Delaying pulse cancellation when the drive bus fails:
active SBH
when an external Stop A is selected
active SG1: For SG1, $MA_SAFE_VELO_STOP_REACTION is
parameterized so that when the bus fails, the pulses should be
immediately cancelled.
Input assignment of the SGE "de-select external Stop E"
U DB18.DBX63.0
=
DB31.DBX32.5
=
DB32.DBX32.5
e SG/
Delay time for th
SBH changeover:
8 Application examples
8.8 Example for combining SI with ESR
De-select the external Stop E from the PLC:
(corresponds to OUTSIP[09])
(ext. Stop E, axis X)
(ext. Stop E, axis Y)