Torque Specifications - Huawei PDU8000 Quick Manual

Ups modular input power distribution cabinet (single cabinet)
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

No.
Symptom
The insulation
resistances of
the power
distribution
1
devices and
feed circuit are
less than 0.5
megohm.
The PD510 does
not display
2
parameters
correctly.
The indicators
3
are off.
The ATS is
4
faulty.
Appendix
A

Torque Specifications

Possible Cause
The insulation layer is
damaged.
The transformation
ratio is incorrectly set
for the current or
voltage.
Cables to the
corresponding current
transformer and
voltage collector are
not properly
connected.
The current
transformer is faulty.
The PD510 is faulty.
Cables to the
indicators are not
properly connected.
The indicators are
faulty.
See the ATS manual.
Solution
2. Isolate the customer's cable.
If the insulation resistance of the PDC is
less than 20 megohms, the insulation of the
PDC does not meet the requirement. Check
the circuits one by one to locate and rectify
the circuits with insulation faults.
If the insulation resistance of the PDC is
greater than 20 megohms, the insulation of
the customer cables does not meet the
requirement. Check the circuits one by one to
locate and rectify the circuits with insulation
faults.
1. Set transformation ratio based on the actual
rated current.
2. Check that cables to the corresponding
current transformer and voltage collector are
properly connected.
3. If cables are correctly connected, check the
current transformer. If the current
transformer is faulty, replace it.
4. If the circuits and current transformer are
normal, check whether the PD510 is faulty. If
the PD510 is faulty, replace the PD510.
1. Check that cables to the indicators are
properly connected.
2. If the cables are properly connected, check
the indicators. If the indicators are faulty,
replace them.
23