Installing Floating Nuts and Guide Rails
Cabinet Requirements
Cabinet size: The height of the NIP6830 is 4 U (1 U = 44.45 mm) for DC cabinet and 5 U for AC cabinet.
Airflow clearance: Maintain a minimum spacing of 2 U between devices installed in the same cabinet, between the top-most
device and the cabinet top, and between the bottom-most device and the cabinet bottom. abinet bottom.
DC cabinet
AC cabinet
M6
M6
4
The second hole in rack unit 8
(for fiber spool)
The second hole in rack unit 7
(for fiber spool)
The first hole in rack unit 6
(for device)
The third hole in rack unit 3
(for device)
Location of floating nuts for guide rails
1U
The second hole in rack unit 9
(for fiber spool)
The second hole in rack unit 8
(for fiber spool)
The first hole in rack unit 7
(for device)
The third hole in rack unit 3
(for device)
Location of floating nuts for guide rails
1U