110
Frame sizes R5 and R6
Choose between gG and aR fuses according to the table under
selecting between gG and aR fuses
checking that the short-circuit current of the installation is at least the value
given in the fuse table. The short-circuit current can be calculated as follows:
where
Calculation example
Drive:
• ACS800-01-0075-3
• supply voltage
Transformer:
• rated power S
• rated voltage (drive supply voltage) U
• transformer impedance z
Supply cable:
• length = 170 m
• resistance/length = 0.398 ohm/km
• reactance/length = 0.082 ohm/km.
Technical data
U
I
=
k2-ph
2
R
+ (Z
2 ·
c
I
= short-circuit current in symmetrical two-phase short-circuit
k2-ph
U = network line-to-line voltage (U)
R
= cable resistance (ohm)
c
2
Z
= z
· U
/S
= transformer impedance (ohm)
k
k
N
N
z
= transformer impedance (%)
k
U
= transformer rated voltage (V)
N
S
= nominal apparent power of the transformer (kVA)
N
X
= cable reactance (ohm).
c
= 600 kVA
N
2
U
N
·
Z
= z
·
= 0.072
k
k
S
N
ohm
m · 0.398
R
= 170
c
km
ohm
m · 0.082
X
= 170
c
km
on page 114, or verify the operating time by
2
+ X
)
k
c
= 430 V
N
= 7.2%.
k
2
(430 V)
= 22.19 mohm
600 kVA
= 67.66 mohm
= 13.94 mohm
Quick guide for