Cleaning; Maintenance; Description Of Inputs And Outputs - ABB i-bus KNX IPR/S 3.5.1 Product Manual

Ip router secure
Hide thumbs Also See for i-bus KNX IPR/S 3.5.1:
Table of Contents

Advertisement

ABB i-bus
®
KNX
Device technology
The reset to factory settings can also be performed directly on the device. This is not a security risk,
because the device will no longer be part of the system afterward.
Press the Programming button when the KNX bus is not connected
Hold the Programming button down and plug on the bus terminal. The Programming LED flashes (2
Hz)
Press the button, hold it for at least 5 s and then release it. The Programming LED goes out, and the
device reboots with the factory settings
The Router can be reprogrammed if the ETS connects with the device after reset and if the device's FDSK
key is still known to the ETS. The ETS will report that the device was reset in this case.
See chapter 3.5,
.
2.4.6

Cleaning

Disconnect the device from the supply of electrical power before cleaning. If devices become dirty, they
can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive agents or solutions
must never be used.
2.4.7

Maintenance

The device is maintenance-free. In the event of damage, e.g. during transport and/or storage, repairs are
not allowed to be made.
2.5

Description of inputs and outputs

Supply voltage input 12 to 30 V DC
Only a DC voltage in a range of 12 to 30 V may be connected to the power supply input. We recommend
using an NT/S power supply from our range.
It is also possible to power the Router via the voltage output without choke of an ABB KNX power supply
(type SV/S).
Caution
The supply voltage must be 12 to 30 V DC, or the device is powered via PoE (Power over Ethernet) to
IEEE 802.3af class 1.
Connecting the device to 230 V may destroy it!
KNX connection
The supplied bus connection terminal is used to connect to the KNX bus.
Note
The latest ETS 5 version is required for programming.
LAN connection
The device connects to the network via an Ethernet RJ45 interface for LAN networks. The network
interface can be operated with a transmission speed of 10/100 Mbit/s. Network activity is indicated by the
LAN/LINK LED on the front of the device.
KNX
Secure, for more information about the FDSK (Factory Default Setup Key).
IPR/S 3.5.1 | 2CDC502099D0211 Rev. A 17