ABB i-bus
®
KNX
Commissioning
In case of errors repeat telegrams
Options:
Yes: If an error is detected when a telegram is transmitted, the telegram is repeated up to three times.
No: The telegram is not repeated.
User-defined: The reaction can be set individually for different types of telegram.
The following dependent parameters appear when the User-defined option is selected:
If free group address structure is used:
Main group 0...13 => 1...28,671
Main group 14...31 => 28,672...65,535
Note
In the ETS 5 it is possible to not just assign two- or three-stage group addresses; it is possible to assign
them freely. If the free group address view is selected, main group 0...13 corresponds to subgroup
range 1...28,671 and main group 14...31 corresponds to subgroup range 28,672...65,535. Relevant
details can be found in the help for the ETS.
Yes
No
User-defined
Repeat group addressed telegrams
Options:
Yes
No
Yes: If an error is detected when a group addressed telegram is transmitted, the telegram is
repeated up to three times.
No: The telegram is not repeated.
Repeat physically addressed telegrams
Options:
Yes
No
Yes: If an error is detected when a physically addressed telegram is transmitted, the telegram
is repeated up to three times.
No: The telegram is not repeated.
Repeat broadcast telegrams
Options:
Yes
No
Yes: If an error is detected when a broadcast telegram is transmitted, the telegram is repeated
up to three times.
No: The telegram is not repeated.