SPECIFICATIONS

TABLE 1 CONTACTOR TYPE HCV-5HA/5HAM/7HA/7HAM (Magnetically Held)
Maximum Voltage
Rated Operational Current
Rated Thermal Current
Interrupting Capacity (NEMA Class E1)-5HA
Interrupting Capacity (NEMA Class E1)-7HA
Permissible Switching Frequency
Mechanical Life
Electrical Life
Closing Time
Opening Time
Arcing Time
Pick-Up Voltage AC or DC
Drop-Out Voltage AC or DC
Rated Control Voltage *
Coil Circuit Inrush
Coil Circuit Holding
Auxiliary Contact Arrangement
Auxiliary Contact Rating
* Coil drive board setting required (standard 120 Vac). Refer to contactor manuals for further details.
CONTACTOR TYPE HCV-5HAL/5HAML/7HAL/7HAML (Latched Type)
Permissible Switching Frequency
Mechanical Life
Tripping Voltage
Tripping Current
A latched contactor is the same as magnetically-held type, except number of auxiliary contacts is reduced to 2
N.O. – 2 N.C. Standard operating voltage is 120VAC Close/125VDC Trip.
CONTACTOR RATINGS
7200 Volts
400 Amps
450 Amps
7000 Amps RMS Sym. @ 5 kV Max
4500 Amps RMS Sym. @ 7.2 kV Max
7200 Amps RMS Sym. @ 7.2 kV Max
1200/Hour
2,500,000 Operations
250,000 Operations
75-100 ms
20-30 ms
10 ms or less
85% (Hot) – 70% (Cold)
60% or Less of Coil Rating DC (Cold)
120Vac 50/60Hz or Opt. 240Vac/125Vdc/250Vdc
5.4A Peak @ 120Vac (670VA AC (700W DC)
0.12A Average @ 120Vac (85VA AC - 85W DC)
3 N.O. – 3 N.C. (Max-STD)
10 A, 48-600Vac Max. (NEMA Class A600)
300/Hour
250,000 Operations
60% or less of Coil Rating DC (Cold)
4.8A Peak @ 125Vdc