ABB ATS-16 A Operating Manual

ABB ATS-16 A Operating Manual

Automatic transfer switch 230 vac

Advertisement

Quick Links

O P ER AT I N G M AN UA L
ATS-16 A
Automatic Transfer Switch
230 VAC
PREPARED
2019-04-16
Product Marketing
APPROVED
2019-05-22
Gabriele Poccia
OWNING ORGANIZATION
ABB, Electrification – Smart Power business line
© Copyright 2019 ABB. All rights reserved.
STATUS
Approved
DOCUMENT KIND
Operating manual
DOCUMENT ID.
4NWD003885
SECURITY LEVEL
Public
REV.
LANG.
PAGE
A
EN
1/18

Advertisement

Table of Contents
loading

Summary of Contents for ABB ATS-16 A

  • Page 1 PREPARED STATUS SECURITY LEVEL 2019-04-16 Product Marketing Approved Public APPROVED DOCUMENT KIND 2019-05-22 Gabriele Poccia Operating manual OWNING ORGANIZATION DOCUMENT ID. REV. LANG. PAGE ABB, Electrification – Smart Power business line 4NWD003885 1/18 © Copyright 2019 ABB. All rights reserved.
  • Page 2 This symbol and wording does not indicate a dangerous situation. This symbol indicates that reading the instruction manual/booklet before starting work or before operating equipment or machinery is compulsory. STATUS SECURITY LEVEL DOCUMENT ID. REV. LANG. PAGE Approved Public 4NWD003885 2/18 © Copyright 2019 ABB. All rights reserved.
  • Page 3: Table Of Contents

    2.6. Rack Mounting ..............................8 2.7. Dimensions of area .............................. 8 3. Installation ............................... 9 3.1. Configuration of the ATS-16 A system ......................9 3.2. Technical Data ............................... 9 3.2.1. Block Diagram ............................9 3.2.2. ATS-16 A Technical Data ........................10 3.3.
  • Page 4: Important Safety Instructions

    • RISK OF ELECTRIC SHOCK - DISCONNECTION OF AC SOURCE(S) (AND THE DC SOURCE) IS REQUIRED TO DE-ENERGIZE THIS UNIT BEFORE SERVICING • THERE IS DANGER OF AN ELECTRICAL IMPACT. DANGER STATUS SECURITY LEVEL DOCUMENT ID. REV. LANG. PAGE Approved Public 4NWD003885 4/18 © Copyright 2019 ABB. All rights reserved.
  • Page 5 DANGER HIGH FAULT CURRENTS (LEAKAGE CURRENTS): BEFORE CONNECTING THE MAINS YOU MUST ENSURE THAT THERE IS A PROPER EARTH CONNECTION! DANGER STATUS SECURITY LEVEL DOCUMENT ID. REV. LANG. PAGE Approved Public 4NWD003885 5/18 © Copyright 2019 ABB. All rights reserved.
  • Page 6: Installation

    UNDAMAGED. ANY DAMAGED OR MISSING PARTS MUST BE REPORTED TO THE SUPPLIER AS SOON AS POSSIBLE. NOTE 2.2. Unpacking list The ATS-16 A is available voltage level 220/230/240VAC. Nominal current: 16 A. • ATS-16 A module • 2 pluggable input power cables (p/n: 108-00140-xx) •...
  • Page 7: Environmental Conditions

    ATS -16 A 2.5. Environmental conditions THE ATS-16 A MUST BE EITHER RACK MOUNTED OR INSTALLED ON A LEVEL AND EVEN SURFACE IN AN AREA PROTECTED FROM EXTREMES OF TEMPERATURE, WATER, AND HUMIDITY, AND FROM THE PRESENCE OF CONDUCTIVE POWDER OR DUST NOTE DO NOT STACK UNITS AND DO NOT PLACE ANY OBJECTS ON TOP OF THE UNIT.
  • Page 8: Rack Mounting

    The ATS-16 A scope of supply contains two brackets for fixing the ATS-16 A into a 19-inch rack or into a cabinet with 19-inch inner design. Vertical mounting is also possible with the ATS-16 A.
  • Page 9: Installation

    3.1. Configuration of the ATS-16 A system The ATS-16 A provides high reliability supply by switching the load to one of two possible power supplies. Primarily, these two supplies are UPS devices with sinusoidal output only. These UPS devices must operate on the double conversion principle.
  • Page 10: Ats-16 A Technical Data

    IEC 320-C20x 2 Power Cord: p/n 108- 00140-xx Outlet IEC 320-C19 x 1 IEC 320-C13-3 x2 EPO active Output NOT supplied. STATUS SECURITY LEVEL DOCUMENT ID. REV. LANG. PAGE Approved Public 4NWD003885 10/18 © Copyright 2019 ABB. All rights reserved.
  • Page 11 D = 425 mm H = 184 mm Color Silver RAL 9006 Material Metallic Case Structure Rack Mount Unit (1U) Vertical mount (0U) STATUS SECURITY LEVEL DOCUMENT ID. REV. LANG. PAGE Approved Public 4NWD003885 11/18 © Copyright 2019 ABB. All rights reserved.
  • Page 12 IEC61000-4-3 level 2 (Lab.) IEC61000-4-4 level 2 IEC61000-4-5 level 3 IEC 61000-2-2 LF Immunity IEC61000-4-6 level 2 (Lab.) IEC61000-3-2 Harmonic (Lab.) IEC61000-3-3 Flickers STATUS SECURITY LEVEL DOCUMENT ID. REV. LANG. PAGE Approved Public 4NWD003885 12/18 © Copyright 2019 ABB. All rights reserved.
  • Page 13: External Protection And Isolation Devices

    All protection devices (circuit breakers and fuses) placed upstream of the ATS-16 A input and downstream to ATS-16 A output line have to be installed for the protection of both the cables and the equipment and in coordination with both ATS-16 A input protection (fuses) and ATS-16 A overload capacities.
  • Page 14: Front Panel

    3.6. Operating Panel In the following figure you can see the front panel of the ATS-16 A. Most of the functions of the ATS-16 A are driven by an internal control. From the operating panel, mains electricity can be set as the preferred source of power.
  • Page 15 Each 3-second push on BP1 and BP2 together will release a fault (Fault release) (you must clear the fault conditions first). STATUS SECURITY LEVEL DOCUMENT ID. REV. LANG. PAGE Approved Public 4NWD003885 15/18 © Copyright 2019 ABB. All rights reserved.
  • Page 16: Description Of The System

    The 2-pole ATS-16 A is a two-way, single phase automatic switch powered by two independent synchro- nous or asynchronous AC power supply sources. The ATS-16 A makes a rapid switch from one source to the other in the event of a fault to the power supply used to power the load.
  • Page 17: Manual Switch On Procedures

    LED SW1 or SW2 according to the primary source 4.3. Switch OFF WHEN THIS PROCEDURE IS CARRIED OUT THE LOAD IS NO LONGER SUPPLIED BY THE ATS-16 A. WARNING STATUS SECURITY LEVEL DOCUMENT ID. REV. LANG. PAGE Approved Public 4NWD003885 17/18 © Copyright 2019 ABB. All rights reserved.
  • Page 18: Troubleshooting

    Is the mains voltage present at the ATS-16 A input? • Has one of the two input fuses tripped or open? When contacting the ABB customer service representative, please have the following information ready: • Device information (model name and serial number) •...

Table of Contents