Refer to [Chapter 3 OPERATION] in the instruction manual for the SJ300 inverter be-
fore operating with this board. When the operation command is given from the terminal
side of the inverter main body, operate with the following procedure.
<Procedure>
1. Turn ON the POWER switch of the inverter.
2. Set the control method (A044) in [05].
3. Set the necessary items according to the instruction manual "Chapter 4
FUNCTION EXPLANATION" of the inverter main body.
4. For speed control, operation is started when operation command of the inverter
main body is turned on.
5. For position control, turn on the STAT terminal of SJ-FB and operation com-
mand of the inverter main body first of all. Next input the pulse train position
command to SAP-SAN and SBP-SBN. Then the motor turns only the pulse that
you input.
Confirm the following while trial operation.
ü The motor accelerates normally.
ü The motor rotates in the correct direction.
ü Neither abnormal vibration nor noise is recognized in the motor.
If the motor doesn't accelerate normally or the inverter trips with overload, check the
encoder for phase order.
Phase order : The normal phase order is that the waveform of phase A advances by 90°
than that of phase B when the motor rotates forward.
(Note 1) : The monitor signal may not be output from FM terminal of inverter main body
under vector control with sensor (A044=05). Please confirm the monitor out-
put in this case.
(Note 2) : Please do not do the free run action by "RS terminal" of inverter main body.
When you do this action, over current trip, or power element destruction may
occur. Please use "FRS" the terminal when performing free run action.
(Note 3) : If the torque limit setting (b041-b044) is enlarged, over current trip would oc-
cur at the time of the motor added burden. In this case, please adjust the
torque limit setting value.
(Note 4) : The motor constant data of the SJ300 series is the data at the time of base
frequency 50Hz in the J1 motor made in Hitachi. . Please put in the value
that did it to motor constant I0 (H023) 0.7 times, in the case that you use it
with base frequency 60Hz in the J1 motor.
(Note 5) : Please do the auto tuning, in the case that you do not understand the motor
constant.