Airflow Adroit DV50 Instruction Manual

Airflow Adroit DV50 Instruction Manual

Integral co2 sensor
Hide thumbs Also See for Adroit DV50:

Advertisement

Quick Links

DV50 DV80
(Integral CO
Sensor)
2
DV50 DV80 (Integral CO
Sensor)
2
Instruction Manual
© Airflow • We reserve the right to make changes without prior notice

Advertisement

Table of Contents
loading

Summary of Contents for Airflow Adroit DV50

  • Page 1 DV50 DV80 (Integral CO Sensor) DV50 DV80 (Integral CO Sensor) Instruction Manual © Airflow • We reserve the right to make changes without prior notice...
  • Page 2 DV50 DV80 (Integral CO Sensor)
  • Page 3: Table Of Contents

    7. EXPLODED VIEW AND PARTS LIST 8. USER LEVEL DIAGRAMS 9. CERTIFICATE OF CONFORMITY 10. COMMISSIONING THE SYSTEM 11. WARRANTY NOTE: You can sign into your Adroit account at: www.airflowadroitcontrol.com © Airflow • We reserve the right to make changes without prior notice...
  • Page 4: Introduction

    Fine filter for supply air Internal carbon dioxide sensor Coarse filter for supply air Carbon dioxide sensor (optional) Coarse filter for extract air Humidity sensor (optional) Bypass damper of the HR cell VOC sensor (optional) NOTE For more detailed instructions, go to www.airflow.com...
  • Page 5: System Description

    The lastest browser versions on 9. Click on the link given in this e-mail to verify your e-mail address. mobile devices. 10. You are now connected to the Adroit Cloud. © Airflow • We reserve the right to make changes without prior notice...
  • Page 6 DV50 DV80 (Integral CO Sensor) INTRODUCTION GENERAL SAFETY INSTRUCTIONS For safe and proper handling, it is necessary to know the basic safety regulations and the intended usage of the ventilation system. Read this manual before operating the ventilation unit. Keep this manual for later use.
  • Page 7: Adroit Digital Controller

    These icons indicate the hierarchy level of the settings. This icon indicates when the feature is turned off at your user level. The parental controls lock code is 1001. © Airflow • We reserve the right to make changes without prior notice...
  • Page 8 DV50 DV80 (Integral CO Sensor) INTRODUCTION INTRODUCTION WARNING Ventilation has to be constant for the indoor air to stay healthy for the dwellers and the structures of the dwelling. Even for longer The unit is not intended for use by holidays, it is not advisable to stop the ventilation, because the children under 8 or by persons with indoor air will become stuffy and, during the heating season, the...
  • Page 9: Deployment Wizard

    If you want to use the 12 hour clock, proceed as follows: Press the Minus button. The 24 Hour Time setting value is changed to Off. Proceed to the next phase by pressing the Right arrow button. © Airflow • We reserve the right to make changes without prior notice...
  • Page 10: Basic Settings (Setting The Language, Time And Date)

    DV50 DV80 (Integral CO Sensor) BASIC SETTINGS SET THE AUTOMATIC DAYLIGHT SAVING TIME By default, the system automatically switches to the summer time. If you want to use the automatic daylight saving time, proceed to the next step by pressing the right arrow button. If you want to use the manual daylight saving time, proceed as follows: Press the Minus button.
  • Page 11 PARENTAL CONTROLS Set the parental controls on or off by using the Plus and ACCESS CODE: Minus buttons. Press the OK button. The parental controls are now set. © Airflow • We reserve the right to make changes without prior notice...
  • Page 12 If, at the beginning, the air flows differ greatly from the designed rate. Check the air flows by measuring them at the valves, and fine tune the airflow rates, if necessary by first adjusting the units fans, then by adjusting the room valves.
  • Page 13 VOC content, is used or not. 15. The automatic fan speed control, based on the carbon dioxide or VOC content, is now set. 16. Press the OK button. © Airflow • We reserve the right to make changes without prior notice...
  • Page 14 DV50 DV80 (Integral CO Sensor) EXPERT SETTINGS AWAY PROFILE When you want to set the Away profile settings, proceed as follows: 1. The deployment wizard Away profile screen is opened. NOTE Once you have set the fan speed for the At home profile, the fan speed for the Away profile will default to -30% of the At home profile fan speed.
  • Page 15 16. The timer duration setting screen appears. 17. Set the profile timer duration in minutes by using the Plus and Minus buttons. 18. Press the OK button. © Airflow • We reserve the right to make changes without prior notice...
  • Page 16 DV50 DV80 (Integral CO Sensor) EXPERT SETTINGS FIREPLACE PROFILE When you want to set the Fireplace function settings, proceed as follows: 1. The deployment wizard Fireplace function profile screen is opened. 2. Set the profile timer duration in minutes by using the Plus and Minus buttons.
  • Page 17: Ventilation Profiles

    Repeat the selected setup phase or phases, until you are satisfied with the settings. When you are satisfied with the settings, use the arrow buttons to select Start and press the OK button. © Airflow • We reserve the right to make changes without prior notice...
  • Page 18 DV50 DV80 (Integral CO Sensor) VENTILATION PROFILES THE VENTILATION UNIT HAS FOUR VENTILATION PROFILES: AT HOME AWAY BOOST FIREPLACE PROFILE Use this ventilation Use this ventilation profile Use this profile to increase Use this ventilation profile when, for example, profile when the when the dwelling or the ventilation rate, e.g.
  • Page 19 Change filters — Indicates the next recommended filter change date. • Days in use — Indicates how long the unit has been running in days and years. © Airflow • We reserve the right to make changes without prior notice...
  • Page 20: Using The Unit

    DV50 DV80 (Integral CO Sensor) VENTILATION PROFILES VIEWING THE AWAY PROFILE INFORMATION If you want to view the Away profile settings, proceed as follows: Open the Away profile main view. Press the Profile information button. The first information screen for the profile appears. This screen contains the following information: •...
  • Page 21: Temperatures And Sensors

    If you want to view the Fireplace function settings, proceed as follows: Open the Fireplace function main view. The profile main screen contains a summary of the profile data. Also see Table 2, “Profile symbols. © Airflow • We reserve the right to make changes without prior notice...
  • Page 22 DV50 DV80 (Integral CO Sensor) SETTINGS Press the Profile information button. The first information screen for the profile opens. This screen shows the following information: • Duration — Indicates the duration of enhanced ventilation when the Fireplace profile is activated. The value is shown in hours and minutes.
  • Page 23 14. Use the Plus and Minus buttons to select whether the automatic fan speed control, based on the carbon dioxide or VOC level, is used or not. 15. Press the OK button. © Airflow • We reserve the right to make changes without prior notice...
  • Page 24 DV50 DV80 (Integral CO Sensor) VENTILATION PROFILES MODIFYING THE BOOST PROFILE SETTINGS When you want to edit the Boost profile settings, proceed as follows: Open Boost profile main view. Press the Profile information button. Press the Edit button. The fan speed setup opens. Set the Boost profile fan speed as a percentage of the maximum by using the Plus and Minus buttons.
  • Page 25 Off — When the timer is disabled, the Fireplace function is used until manually changed (or the week clock) change the profile. 15. Press the OK button. © Airflow • We reserve the right to make changes without prior notice...
  • Page 26 DV50 DV80 (Integral CO Sensor) TEMPERATURES AND SENSORS VIEWING TEMPERATURE DATA When you want to view the system temperature and sensor data, proceed as follows: Select Settings > Temperatures and sensors. Press the OK button. The temperature and sensors summary screen is opened. This screen contains the following information: •...
  • Page 27 11. A screen displaying the maximum carbon dioxide value from the air carbon dioxide extract air sensor is opened, again 12. To exit the menu, press the Back button. © Airflow • We reserve the right to make changes without prior notice...
  • Page 28 DV50 DV80 (Integral CO Sensor) TEMPERATURES AND SENSORS VIEWING HUMIDITY AND CARBON DIOXIDE STATISTICS When you want to view statistics on the humidity and carbon dioxide values, proceed as follows: Select Settings > Temperatures and sensors. Press the OK button. The temperature and supply and extract air sensors summary screen is opened.
  • Page 29 Press the Edit button. The Filter status 1/2 screen is opened. Press the Plus button. The Filters changed field value changes to Today. Press the OK button. © Airflow • We reserve the right to make changes without prior notice...
  • Page 30 DV50 DV80 (Integral CO Sensor) SETTINGS NOTE The system will automatically set the service reminder to remind you of the filter replacement. The reminder will be displayed when the set reminder interval has elapsed. SETTING THE FILTER REPLACEMENT REMINDER INTERVAL This section describes how to set the filter replacement reminder interval.
  • Page 31 You can select the user interface language as follows: Select Settings > Language. Press the OK button. Select the language you want for example, English. Press the OK button. © Airflow • We reserve the right to make changes without prior notice...
  • Page 32 DV50 DV80 (Integral CO Sensor) SETTINGS TIME AND DATE SETTING THE TIME AND DATE In the following chapters, it shows you how to set: • Time • 24- or 12-hour clock • Automatic daylight-saving time • Date NOTE The system time will stay active for a few hours if the power is cut to the unit.
  • Page 33 A confirmation screen is opened. You can switch the week clock ON or OFF by pressing the OK button in the Week clock screen for a few seconds. © Airflow • We reserve the right to make changes without prior notice...
  • Page 34 DV50 DV80 (Integral CO Sensor) SETTINGS WEEK CLOCK SETTING AND EDITING THE WEEKLY PROGRAM If you want to set the weekly timer program or edit an existing program, proceed as follows: Select Settings > Week clock. Press the OK button. The week view in the week clock is displayed.
  • Page 35 • At 21.00, select the At home profile. Ensure that the week clock is enabled. The figures above depict a week The weekly program is now set clock set in line with this example. © Airflow • We reserve the right to make changes without prior notice...
  • Page 36 DV50 DV80 (Integral CO Sensor) SETTINGS PARTIAL BY-PASS To turn the partial by-pass on: Select Expert settings. Find HR cell bypass settings. Select On from the pop down list menu of the Partial bypass option. The partial bypass has now been turned on and will run automatically based on temperature sensors inputs.
  • Page 37: Maintenance

    Close the door of the unit. Ensure that the safety switch of the door is engaged, allowing the unit to be turned on. Plug the ventilation unit back into the mains. The filters have now been successfully replaced. © Airflow • We reserve the right to make changes without prior notice...
  • Page 38: Heat Recovery Cell

    DV50 DV80 (Integral CO Sensor) MAINTENANCE INSTRUCTIONS HEAT RECOVERY CELL Check that the heat recovery cell (D) is clean every two years, or whenever the filters are being replaced. WARNING Handle the cell carefully! For example, do not lift the cells by the layers.
  • Page 39: Fans

    12. Close the door and plug the unit back into the mains. 13. The fan has now been checked and cleaned. Install the fan beds in a reverse order. © Airflow • We reserve the right to make changes without prior notice...
  • Page 40: Condensing Water

    DV50 DV80 (Integral CO Sensor) MAINTENANCE INSTRUCTIONS REMOVING AND CLEANING THE EXTRACT AIR FAN This section describes how to remove the extract air fan of the right handed unit. The steps are mirrored for the left handed unit. To remove and clean the extract air fan: Disconnect the ventilation unit from the mains electricity supply.
  • Page 41: Troubleshooting

    Check the cables from the unit to the control panel. but the control panel is not power is lost, or the control panel Contact the service centre if necessary. working. is damaged. © Airflow • We reserve the right to make changes without prior notice...
  • Page 42 DV50 DV80 (Integral CO Sensor) MAINTENANCE INSTRUCTIONS DV50 Adroit Product descriptions Product numbers: DV50 (R) Adroit (Integral CO Sensor) 90001273 DV50 (L) Adroit (Integral CO Sensor) 90001274 Air volumes Fans Extract air 47 l/s, 100 Pa 0.043 kW 0.32 Supply air 56 l/s, 100 Pa 0.043 kW 0.32 Electrical connection...
  • Page 43: Technical Specifications

    Adjustment position / air flows (supply/extract) dm³/s Adjustment position (%) Air flow (dm³/s) 12/14 19/22 22/25 27/30 31/34 35/40 41/45 44/48 LpA, dB (A) 23.8 28.8 34.6 38.4 40.4 44.6 46.7 48.9 50.2 © Airflow • We reserve the right to make changes without prior notice...
  • Page 44 DV50 DV80 (Integral CO Sensor) DV80 ADROIT TECHNICAL SPECIFICATIONS MEASUREMENT POINTS FAN INPUT POWER Measurement points after the connection 100% outlet. The fan curves indicate the total pressure accounted for by duct losses. Supply air Extract air VIEW FROM ABOVE (l/s) Volume flow rate AIR VOLUMES DV ADROIT, SUPPLY AIR ISO COARSE >...
  • Page 45: Internal Electrical Connection

    11.1 V operating voltage Optional additional heater radiator AN/I Analog input 0-10 VDC with 90°C and 130°C overheating RM/I 24 V relay input protection RM/O 24 V relay output © Airflow • We reserve the right to make changes without prior notice...
  • Page 46: External Electrical Connection

    DV50 DV80 (Integral CO Sensor) EXTERNAL ELECTRICAL CONNECTION 7028350 POWER SUPPLY Adroit 2014-08-29 JS REMOTE Adroit MONITORING Digital Maximum ≤6W Controller transmitter Modbus RTU Adroit digital Controller Adroit RH% 0.3W 2x2x0,5+0,5 transmitter 2x2x0,5+0,5 Adroit CO 1.2W transmitter Adroit Voltage 24 VDC transmitter Adroit 2x2x0,5+0,5...
  • Page 47: Installation

    MEASURING TUBES The accessories delivered with the unit include four ADROIT measuring tubes. These can be inserted in the ducts to allow for easier ventilation adjustment. © Airflow • We reserve the right to make changes without prior notice...
  • Page 48: Dimensions And Duct Outlets

    DV50 DV80 (Integral CO Sensor) INSTALLATION DIMENSIONS AND DUCT OUTLETS UNIT DIMENSIONS view from above Dimension DV50 Adroit DV80 Adroit view from view from left (Integral CO (Integral CO right Sensor) Sensor) 1026 100 (female) 125 (female) Seen from behind NOTE Model R: Outdoor air to the unit...
  • Page 49: Condensing Water Outlet

    If you use the alternative condensing water outlet, move the gasket ring and the locking part to the tube joint part that will be mounted on the wall. © Airflow • We reserve the right to make changes without prior notice...
  • Page 50: Exploded View And Parts List

    DV50 DV80 (Integral CO Sensor) EXPLODED VIEW AND PARTS LIST NO. PART CODE NO. PART CODE Door assembly for DV50 Adroit Side sealing strip of the heat recovery for 60000201 60000276 (door plate, insulation, door switch button) DV50 Adroit Door assembly for DV80 Adroit Side sealing strip of the heat recovery for 60000202 60000277...
  • Page 51 External sensor settings Display settings Heating settings Panel address Professional settings Basic fan settings Modbus settings I/O and bus settings Lock code and access rights Defrost settings © Airflow • We reserve the right to make changes without prior notice...
  • Page 52: User Level Diagrams

    DV50 DV80 (Integral CO Sensor) USER LEVEL DIAGRAM Limited Away Away information Edit Unit information Turn unit on At home At home information Edit Error log Boost Boost information Fan test Edit Setup Fireplace mode Fireplace information Edit Heater test HR cell bypass test Service menu Self-test...
  • Page 53: Certificate Of Conformity

    Date 14th May 2019 Managing Director Airflow Developments Limited Aidelle House, Lancaster Road, Cressex Business Park High Wycombe, Buckinghamshire. HP12 3QP, U.K. T: +44 (0)1494 425252 E: info@airflow.com W: airflow.com © Airflow • We reserve the right to make changes without prior notice...
  • Page 54: Commissioning The System

    • Has been installed in accordance with latest Building Regulations and IEEE wiring regulations by a recognised competent installer. Airflow Developments Ltd shall not be liable for any loss, injury or other consequential damage, in the event of a failure of the...