(b) Abnormal completion
(3) Setting items
The following explains the setting items on the Device Read/Write screen.
(a) Connection target (character string)
Specify the IP address or host name of the connection target Ethernet module.
Ex.
To specify using the IP address, enter 10. 97. 85. 200.
(b) Start device
Specify the device code and start device of the device for reading/writing data.
• Device code (selection): Select the device memory.
• Start device (character string): Specify the start number of the device memory for which data is to be
read/written. Specify the start device number in decimal/hexadecimal from the target device memory.
Ex.
To specify the data register D100, select the device code "D" and specify "100" for the start device.
Ex.
To specify the link register W1FF, select the device code "W" and specify "1FF" for the start device.
(c) Number of device (character string)
Specify the number of points (hexadecimal) of the device for which reading/writing are to be performed.
Ex.
To specify 20 points as the number of device points, specify "14".
(d) Read data/write data (character string) (Refer to Page 31, Section 4.4.1 (4).)
• Read data (execution result screen): Displays the content of data for the number of device points read
from the specified device memory.
• Write data: Specify the data to be written to the device for the number of device points.