Settings: MENU – Commissioning/Service – AOP Settings – Control Settings
Acknowledge error from the AOP (factory setting: yes)
● Yes: Errors can be acknowledged via the AOP.
● No: Errors cannot be acknowledged via the AOP.
Settings: MENU – Commissioning/Service – AOP settings – Control settings
CDS changeover via AOP (factory setting: No)
● Yes: In the LOCAL mode, in the operating screen form the active CDS can the changed
● No: In the LOCAL mode, in the operating screen form the active CDS cannot be changed
5.7.7

Timeout monitoring

In "LOCAL" mode or if "OFF in REMOTE" is active, the drive is shut down in an adjustable
time if the data cable between the AOP and drive is disconnected (factory setting 3000 ms).
The AOP30 operator panel
Operating Instructions, 03/2012, A5E00331451A
by one. This is helpful, if operation via an AOP would not be possible due to the fact that
a standard telegram is active.
When CDS0 or 2 is active, "CDS+1" switches to CDS1 or CDS3.
When CDS1 or 3 is active, "CDS-1" switches to CDS0 or CDS2.
by one.
Control via the operator panel
5.7 Operation via the operator panel (LOCAL mode)