Huawei FusionModule 1000A20 Initial Configuration Parameter Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule 1000A20:

Advertisement

Quick Links

FusionModule1000A20 Prefabricated All-in-One Data
Center
Initial Configuration Parameter Manual
(2019, Nicaragua)
Issue
01
Date
2019-05-06
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

loading

Summary of Contents for Huawei FusionModule 1000A20

  • Page 1 FusionModule1000A20 Prefabricated All-in-One Data Center Initial Configuration Parameter Manual (2019, Nicaragua) Issue Date 2019-05-06 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2: Trademarks And Permissions

    Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: Intended Audience

    Indicates a potentially hazardous situation which, if not avoided, could result in equipment damage, data loss, performance deterioration, or unanticipated results. NOTICE is used to address practices not related to personal injury. Issue 01 (2019-05-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 4: Change History

    Change History Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues. Issue 01 (2019-05-06) This issue is the first official release. Issue 01 (2019-05-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 5 FusionModule1000A20 Prefabricated All-in-One Data Center Initial Configuration Parameter Manual (2019, Nicaragua) Contents Contents Initial Configuration Parameter Manual ..................ii 1 Initial Configuration Parameter Manual Usage..............1 2 Initial Configuration Parameters ....................2 Issue 01 (2019-05-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 6 Improper modifications of parameters may easily cause abnormal running status, or even damage to the system. You are not allowed to modify configuration parameters without permission when using a data center. If a modification is necessary, contact Huawei technical support. Huawei shall not be responsible for any loss caused by unauthorized configuration modification.
  • Page 7 FusionModule1000A20 Prefabricated All-in-One Data Center Initial Configuration Parameter Manual (2019, Nicaragua) 2 Initial Configuration Parameters Initial Configuration Parameters This chapter describes the initial configuration parameters for the systems of a Data Center solution. Issue 01 (2019-05-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 8 List of Initial Configuration Parameters Category Diagram ID Diagram Name Detailed Initial Configuration Parameters NO.P001 Power Supply and Distribution Device Layout Diagram NO.P002 Power Supply and Distribution System Diagram Initial Configurations for the Power Supply and Distribution System Initial Configuration Parameters for 3D ATS Table 1 Initial Configuration Parameters for Power Supply and Distribution Devices Initial Configuration Parameters for 8D ATS...
  • Page 9 NO.P001 Power Supply and Distribution Device Layout Diagram Lighting-24 Lighting-25 Lighting-26 Lighting-27 Lighting-28 Lighting-29 Lighting-30 Lighting-31 Lighting-32 Lighting-15 Lighting-16 Lighting-17 Lighting-18 Lighting-19 Lighting-20 Lighting-21 Lighting-22 Lighting-23 UPS-2 UPS-1 Fan-2 Fan-1 Power PDB-1 Signal window Power window...
  • Page 10 NO.P002 Power Supply and Distribution System Diagram Air Conditioner distribution Module IT Load 1 distribution Module IT Load 2 distribution Module IT Load 2 distribution Module IT Load 1 distribution Module Air Conditioner distribution Module Fuse1 Fuse2 Fuse3 Fuse4 Fuse5 Fuse6 BAT+ BAT N...
  • Page 11 Table 1 Initial Configuration Parameters for Power Supply and Distribution Devices Device Name Project Configuration Quantity Power Distribution Device Name Remarks ■Involved □Not involved Integrated UPS UPS-1/2 Note: The following device parameters are not all parameters of the devices. Only the parameters that need to be set for the project are listed. Default values will be used for the other parameters so they do not need to be set. To view other device parameters, see the user manual for the corresponding device.
  • Page 12 Component UPS-1/2 Integrated UPS (20kVA-80kVA) Initial Configuration Parameters Category Parameter Default Value Value Range Setting 12 languages, including English, Chinese, Language English English Italian, and so on Basic Password 000001 Default value Single/Parallel Single Single, Parallel Single Output voltage level 208 V 208 V 208 V、220 V、230 V...
  • Page 13 voltage level is 208 V +15% +10%, +15%, +20%, +25% Default value Bypass Param. Maximum bypass voltage voltage level is 220 V +15% +10%, +15%, +20% Default value voltage level is 230 V +10% +10%, +15% Default value BCB connection Disable Disable/Enable Disable...
  • Page 14 NO.C001 Cooling Device Layout Diagram Opening direction Slide 200mm Slide 200mm Opening direction Opening direction Slide 200mm RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT UPS-2 UPS-1 Air Conditioner-B1 Air Conditioner-D1 Fan-2 Air Conditioner-A1 Air Conditioner-C1 (With Electric Heating &...
  • Page 15 NO.C003 Indoor and Outdoor Unit Signal Cable Wiring Diagram Opening direction Slide 200mm Slide 200mm Opening direction Opening direction Slide 200mm RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT RS485_IN RS485_OUT UPS-2 UPS-1 Air Conditioner-B1 Air Conditioner-D1 Fan-2 Air Conditioner-A1...
  • Page 16 Table 2 Initial Configuration Parameters for Cooling Devices Initial Configuration Parameters of Remote Temperature and Humidity Sensor DIP Switches for Air Cooled Precision Air Conditioners DIP Switch Sequence No. Sensor Name and No. Address Remote humidity and temperature sensor 1 Remote humidity and temperature sensor 2...
  • Page 17 Initial Teamwork Configuration Parameters for Air Cooled Precision Air Conditioners Coolin L1/L2 Large L1/L2 Large Large L1/L2 linkage L1/L2 L1/L2 L1/L2 Cold Teamwo Team Enable Total Force ring capacit linkag Hot aisle Team Rotatio Rota Require ring ring linkage dehumi linkage linkag linkag...
  • Page 18 Initial Temperature and Humidity Configuration Parameters for Air Cooled Precision Air Conditioners Temp control Cold-aisle temp Cold-aisle humid Air Conditioner Cold aisle sensor 1 Cold aisle sensor 2 T/H control type mode set point set point Cold aisle All air conditioners Enable Enable Average valve...
  • Page 19 NO.M001 Monitoring Device Layout Diagram DOOR DOOR DOOR Opening direction Slide 200mm Slide 200mm Opening direction Opening direction Slide 200mm UPS-2 UPS-1 DOOR EXIT BREAK GLASS Air Conditioner-B1 Air Conditioner-D1 Fan-2 Air Conditioner-A1 Air Conditioner-C1 (With Electric Heating & (With Electric Heating & (21KW) (21KW) Fan-1...
  • Page 20 NO.M002 Monitoring System Network Diagram AI/DI Module-1 Reserved Reserved Reserved Reserved Reserved Reserved DDF-1 Reserved HUAWEI WAN_1 LAN_1 COM1/12V COM3/12V AI/DI_1 AI/DI_3 AI/DI_5 DO_1 MMU02B ECC800 53.5VDC_OUT1 53.5VDC_OUT2 BACK WAN_2 LAN_2 COM2/12V COM4/12V AI/DI_2 AI/DI_4 AI/DI_6 DO_2 Collector_ECC800 Reserved Reserved...
  • Page 21 Table 3 Initial Configuration Parameters for the Management System Port to Monitori WebUI User LCD User Upper- Data Device Device Alarm Upper- Upper-Level Device Name Device IP Address Name and Name and Transf Level Remarks Type Model Address Threshold Level Device Port Device Password...
  • Page 22 Settings > Comm User name: Settings > IP Settings NetCol5000- Admin Collector_ Air Conditioner- Smart ETH Set IP assigning mode A021HN12D20 Initial POE_1 ECC800 Gateway-2 to Automatic (DHCP). 020E1 password: 000001 Settings > Comm User name: Settings > IP Settings NetCol5000- Admin Set IP assigning mode...
  • Page 23 Normal: open Collector_ SIGMA Crimped Collector_EC Extinguishant Control FAULT RELAY Alarm: AI/DI_2 ECC800 contact XT/K11031M2 terminal C800 Panel closed POLYMR Normal: Collector_ Door Status M520/ Crimped Collector_EC closed AI/DI_3 ECC800 contact Sensor-3 GREYSTONE terminal C800 Alarm: open GS-06 Normal: open Collector_ SIGMA Crimped...
  • Page 24 The AC actuator connects to the ECC800 controller in wireless mode. Camera commissioning: Obtain the IP address automatically allocated by the ECC800 to the camera through Huawei IPC TOOL. Then access the camera on the WebUI over the IP address to configure the Remarks: internal IP address.
  • Page 25 NO.F001 Fire Extinguishing Device Layout Diagram EXIT EXIT-1 Opening direction Slide 200mm Slide 200mm Opening direction Opening direction Slide 200mm UPS-2 UPS-1 Warning Signs-1 Abort Air Conditioner-B1 Air Conditioner-D1 Fan-2 Air Conditioner-A1 Air Conditioner-C1 (With Electric Heating & (With Electric Heating & (21KW) (21KW) Fan-1...
  • Page 26 NO.F002 Fire Extinguishing System Conceptual Diagram-1 Horn Strobes -2 Horn Strobes -1 Terminal Resistor - + + - + + Warning Signs-1 Terminal Resistor Terminal Resistor 6.8K 6.8K 2WIRE SILENCE SILENCE COMM+ LEV1 LEV2 COMM+ LEV1 LEV2 2WIRE Terminal Resistor pneumatic switch-1 Fire Alarm Bell-1 Extinguishant Abort Button -1...
  • Page 27 NO.F002 Fire Extinguishing System Conceptual Diagram-2 L1 IN L1 IN L1 IN L1 IN L1 IN L1 OUT L1 OUT L1 OUT L1 OUT L1 OUT L1 OUT black black L1 IN L1 IN L1 IN L1 IN L1 IN L1 OUT L1 OUT L1 OUT...
  • Page 28 NO.L001 Lighting Device Layout Diagram Lighting-24 Lighting-25 Lighting-26 Lighting-27 Lighting-28 Lighting-29 Lighting-30 Lighting-31 Lighting-32 Lighting-15 Lighting-16 Lighting-17 Lighting-18 Lighting-19 Lighting-20 Lighting-21 Lighting-22 Lighting-23 UPS-2 UPS-1 Signal window Power window Power PDB-1...
  • Page 29 NO.F003 Emergency Exit Diagram Exit Opening direction Slide 200mm Slide 200mm Opening direction Opening direction Slide 200mm UPS-2 UPS-1 Air Conditioner-B1 Air Conditioner-D1 Fan-2 Air Conditioner-A1 Air Conditioner-C1 (With Electric Heating & (With Electric Heating & (21KW) (21KW) Fan-1 Humidifier 21KW) Humidifier 21KW) Signal window Power window...