In-row air cooled smart cooling product

Advertisement

5
Installing the Refrigerant Pipe
1. Keep at least 25 mm between pipes.
2. When connecting the indoor and outdoor units, you are advised to connect pipes to the
outdoor unit first. Seal the pipe if the welding break will exceed 15 minutes to prevent dust
and water from entering the pipe.
3. Take appropriate sealing and protection measures when routing welded pipes through holes
to prevent air channel leaks and copper pipe damage. Otherwise, other components may be
damaged by foreign matter.
4. Avoid elbows and ensure that the connection between the indoor and outdoor units is the
shortest.
Pipe support
5.2
Laying Out Pipes Inside the Cabinet
Upward pipe routing
1. When routing pipes upward inside an IT
cabinet, remove the cable ring from the pipe
side in the rear of the cabinet.
3. Route pipes inside the cabinet.
Wall
Pipe
2. Install the binding plate using the
screws removed in the previous step.