13.4.8. "Variable primary fl ow" option
The "Variable Primary Flow" option is used to modulate the power of the hydraulic pump This modulation is obtained by
powering the pump through a frequency inverter.
The minimum frequency of the pump must not be less than the manufacturer's recommendations (e.g.
CAUTION
30Hz) and must ensure a suffi cient fl ow rate for the unit (Refer to the § "Physical characteristics", page
11).
13.4.8.1. Constant speed mode
The pump operates at a fi xed speed whatever the unit capacity. This speed is determined during commissioning to adjust the
power of the pump to the load drops of the installation.
Speed set-point
100%
Mod. pump
max speed
Mod. pump
min speed
0%
Step 1
Setting
Mod. pump max speed
Mod. pump standby speed
Main Menu
Main Menu
1/4
1/4
Status
Status
Commissioning
Commissioning
✔
Services
Services
Service
Service
Configuration
Configuration
Access
Manual control
Deice
Operation hours
Lock out
Inputs-Outputs
Parameters
Archives
100%
Capacity
Default
Min.
Max.
100%
0%
100%
60%
0%
100%
1/8
1/8
✔
Configuration
Configuration
Fan
Fan
Pump
Pump
Circuit control
Contacts D1 D2
dT ret./sup. temp
Control on
Commissioning
Pump configuration
Pump
Continuous pump
Modulation
Acceleration delay
--------------------------
---------------
Anti seizing act.
Anti-seizing frequency
Anti-seizing duration
--------------------------
---------------
Mod. pump max speed
Mod. pump min speed
Mod. pump standby speed
Capacity for max speed
33
1/7
1/7
✔
Pump configuration
Pump
Continuous pump
Modulation
20K
Acceleration delay
Return t
--------------------------
Anti seizing act.
Anti-seizing frequency
Anti-seizing duration
--------------------------
Mod. pump max speed
Mod. pump min speed
Mod. pump standby speed
Capacity for max speed
1/13
Single
Off
2 stages
10 s
Active
72h
120s
80,0%
40,0%
20,0%
100,0%
1/13
Single
Off
2 stages
10 s
---------------
Active
72h
120s
---------------
80,0%
40,0%
20,0%
100,0%