Panasonic 140 Installation And Maintenance Manual page 35

Heat pump chiller
Table of Contents

Advertisement

1. Set all units in demand to open all the valves (load = 100%).
2. Set the water pressure setting to a high value (example: 8,0 bar)
3. Check that the output is in line with ECOi-W requirements.
4. Read the pressure value in the system (example: 3,5 bar).
5. Set the water pressure setting to the read value.
When the pressure setting is set, check that the system is operational in the following
conditions:
• when in partial load, the pressure is constant.
• when at zero load (all units off), check that the pump switches to stand-by and that no
water pressure alarm is triggered
13.4.9. Reduced mode
Reduced mode can have the following confi gurations:
• Decreased cool. setp
This function is only available if the unit is in cool mode. It can cool the building at night when electricity is less expensive.
• Eco
Heat and cool setpoints are respectively lowered and raised to reduce the unit's electrical consumption.
• Low noise
In cool mode, the condensation pressure setpoint is increased to reduce the noise generated by the ventilators.
• Eco + Low noise
The "reduced mode" mode activation can be triggered in the following ways:
• directly on the ECOi-W via the user interface
• communication network (Modbus/Bacnet/Cloud)
• external dry contact D2 if entry confi gured.
13.4.10. Limited capacity
Limited capacity is occasionally used to limit the electricity consumption of the ECOi-W to prevent exceeding the electric
power capacity of the installation site.
The "Limited capacity" mode activation can be triggered in the following ways:
• directly on the ECOi-W via the user interface
• communication network (Modbus/Bacnet/Cloud)
• external dry contact D2 if entry confi gured.
Main Menu
Main Menu
1/4
1/4
Status
Status
Commissioning
Commissioning
Commissioning
Commissioning
03.02.2016
03.02.2016
Services
Language selection
Language selection
Communications
Communications
Access
Glycol protection
Glycol protection
Auto change over
Auto change over
Water Law
Water Law
Reduced mode
Reduced mode
Limited capacity
Cold OAT protection
Small volume protection
Calendar
Versions
Main Menu
Main Menu
1/4
1/4
Status
Status
Commissioning
Commissioning
Commissioning
Commissioning
03.02.2016
03.02.2016
Services
Language selection
Language selection
Communications
Communications
Access
Glycol protection
Glycol protection
Auto change over
Auto change over
Water Law
Water Law
Reduced mode
Reduced mode
Limited capacity
Limited capacity
Cold OAT protection
Small volume protection
Calendar
Versions
1/12
1/12
10:40:05
10:40:05
Reduced mode
Reduced mode type
Decreased cool. setp
Decreased cool. setp
-Wat.t.night sh.C
Eco mode
-Wat.t.eco sh.C
-Wat.t.eco sh.H
Low noise
-Circuit 1
-P. evp. delta
-P. cond. delta
-Circuit 2
-P. evp. delta
-P. cond. delta
1/12
1/12
10:40:05
10:40:05
Limited capacity
Low load lim.
35
Pump configuration
1/15
Pump
Single
Continuous pump
Modulation
2 stages
Acceleration delay
--------------------------
---------------
Anti seizing act.
Active
Anti-seizing frequency
Anti-seizing duration
120s
--------------------------
---------------
Mod. pump max speed
80,0%
Mod. pump min speed
40,0%
Mod. pump standby speed
20,0%
Capacity for max speed
100,0%
Wat. pres. setp.
Wat. pres. setp.
8,0bar
8,0bar
Wat. press. val.
Wat. press. val.
3,5bar
3,5bar
1/17
Decreased cool. setp
Eco
2,0K
Low noise
3,0K
Eco+low noise
3,0K
2,0 bar
2,0 bar
2,0 bar
2,0 bar
1/1
50
50 %
0
Off
10 s
72h
1/4
100

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents