Item
Harmonic current
Table 4-10 Bypass input electrical specifications
Item
Power system
Rated voltage
Rated frequency
Frequency range
Input mode
Issue 02 (2021-06-30)
Specifications
● THDi < 9% (30% linear load), THDi < 6% (50%
linear load), THDi < 3% (100% linear load)
● THDi < 11% (30% non-linear load), THDi < 8%
(50% non-linear load), THDi < 5% (100% non-
linear load)
Remarks:
1. The preceding specifications are met when the
mains input and bypass input share a power
source.
2. The input THDu is less than 2%.
Specifications
Three-phase four-wire + PE
380 V AC/400 V AC/415 V AC (line voltage)
50 Hz/60 Hz
50 Hz/60 Hz±6 Hz (adjustable with a tolerance of 0.5–
6 Hz, ±2 Hz by default)
The mains input and bypass input share a power
source (by default) or use different power sources.