Huawei FusionPower6000 Product Description page 29

Hide thumbs Also See for FusionPower6000:
Table of Contents

Advertisement

FusionPower6000
Product Description
Item
Inverter overload
capability
Issue 02 (2021-06-30)
1000 kVA/1200 kVA
Inverter overload capability
for front-to-back airflow:
● 105% < load ≤ 110%:
transfers to bypass mode
after 60 min or longer
(ambient temperature ≤
30°C)
● 100% < load ≤ 110%:
transfers to bypass mode
after 60 min or longer
(ambient temperature >
30°C)
● 110% < load ≤ 125%:
transfers to bypass mode
after 10 minutes or longer
● 125% < load ≤ 150%:
transfers to bypass mode
after 1 minute or longer
● Load > 150%: transfers to
bypass mode after 200 ms
or more; withstands at
least 50 shocks
Inverter overload capability
for top airflow:
● 100% < load ≤ 110%:
transfers to bypass mode
after 60 minutes or longer
● 110% < load ≤ 125%:
transfers to bypass mode
after 10 minutes or longer
(ambient temperature ≤
30°C)
● 110% < load ≤ 125%:
transfers to bypass mode
after 1 minute or longer
(ambient temperature >
30°C)
● 125% < load ≤ 150%:
transfers to bypass mode
after 1 minute or longer
(ambient temperature ≤
30°C)
● 125% < load ≤ 150%:
transfers to bypass mode
after 20 seconds or more
(ambient temperature >
30°C)
Copyright © Huawei Technologies Co., Ltd.
4 Product Overview
1600 kVA
Inverter overload capability
for front-to-back airflow:
● 105% < load ≤ 110%:
transfers to bypass mode
after 60 min or longer
(ambient temperature ≤
30°C)
● 100% < load ≤ 110%:
transfers to bypass mode
after 60 min or longer
(ambient temperature >
30°C)
● 110% < load ≤ 125%:
transfers to bypass mode
after 10 minutes or
longer
● 125% < load ≤ 150%:
transfers to bypass mode
after 1 minute or longer
● Load > 150%: transfers
to bypass mode after 200
ms or more; withstands
at least 50 shocks
23

Advertisement

Table of Contents
loading

Table of Contents