Huawei NetCol5000-C030 Quick Manual
Huawei NetCol5000-C030 Quick Manual

Huawei NetCol5000-C030 Quick Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:

Advertisement

Quick Links

NetCol5000-C(030, 032) In-row Chilled
Water Smart Cooling Product
Quick Guide
Issue: 04
Date: 2019-06-24
1
Overview
Model
Cooling Capacity (kW)
Net Weight (kg) (full configuration)
Dimension (mm) (H x W x D)
Optional components
Electric control box
Water outlet pipe
Water inlet pipe
Chilled water valve
2
Preparing Materials
Materials
Fuse, combined hexagon head bolts M12x90, OT ground terminal of the power cable to the
Configured with
indoor unit, and single cord end terminal of the power cable to the indoor unit, cable ties
the Equipment
Automatic drainpipe
Humidifier water
Engineering
inlet pipe
Procurement
Chilled water inlet
and outlet pipes
NetCol5000-C030
30
166
2000 x 300 x 1200
Humidification, differential pressure sensor, and Wifi module
Air filter
Water pan
Drainpipe
Humidifier pump
BSPT 1/2-inch rigid pipe connector with external threads, and rigid
pipe (PP-R or C-PVC)
G 3/4-inch rigid pipe connector with internal threads (plastic materials
such as PA66, or metal materials are recommended), and rigid pipe
(withstand pressure ≥ 0.7 MPa)
Seamless steel pipe with a G 1 in. external threaded connector or
Aluminum plastic pipe (withstand pressure ≥ 1.6 MPa)
1
Copyright © Huawei Technologies Co., Ltd. 2019 All rights reserved.
NetCol5000-C032
32
176
2200 x 300 x 1200
Display screen
Fan

Advertisement

loading

Summary of Contents for Huawei NetCol5000-C030

  • Page 1 NetCol5000-C(030, 032) In-row Chilled Water Smart Cooling Product Quick Guide Issue: 04 Date: 2019-06-24 Copyright © Huawei Technologies Co., Ltd. 2019 All rights reserved. Overview NetCol5000-C030 NetCol5000-C032 Model Cooling Capacity (kW) Net Weight (kg) (full configuration) Dimension (mm) (H x W x D)
  • Page 2: Installing The Equipment

    Power cable (3x2.5 mm² ), teamwork networking and monitoring Cables cables, and equipotential cable (≥ 16 mm²) Engineering Procurement Indoor unit base, thermal insulation foam, and thermal insulation Others foam glue Preparing an Indoor Unit Base 1. Shock absorption bars (EPDM rubber, 5 mm (Side view) thick) need to be installed between the ground and the base.
  • Page 3 0.3–0.5 MPa of nitrogen before delivery. Take dual-cabinet packaging as an example. If no nitrogen is discharged, contact Huawei technical support. 2. You can open or close the exhaust valve using a flat-head screwdriver. Slowly open the...
  • Page 4 Removing the side plates Moving the cabinet Four to six persons are required to move the cabinet to the installation position. After that, install the side plates. Force-bearing beam Force-bearing beam Leveling the Cabinet Installing Cabinets Side by Side...
  • Page 5 (Only for 30 kW) Remove two Securing the Equipment rodent-proof kits (Only for 30 kW) Install the Air Baffle 3.10 Installing Pipes Pipe Layout 1. A 1:100 tilt should be reserved for the main drainpipe. 2. Keep a clearance of at least 25 mm between pipes. Secure the pipes to supports every a certain distance.
  • Page 6 Unit: mm Pipe support Connecting the Drainpipe Recommended: BSPP 1/2inch reserved connector with inner screw thread BSPT 1/2inch adapter with outer screw thread Rigid pipe (PP-R or C-PVC) Connecting the Humidifier Water Inlet Pipe G 3/4 inch reserved connector with outer screw thread Cable ties G 3/4 inch adapter with...
  • Page 7 Connecting the Chilled Water Inlet and Outlet Pipes Aluminum plastic pipe (1) Reserved device port (2) Direct connection of external teeth (3) Sealing ring (4) Nut (5) Aluminum plastic pipe Connecting the Seamless steel pipe (1) Reserved device port (2) Seamless steel pipe ( Optional) Leakage Test with Nitrogen •...
  • Page 8 Injecting Water to Expel Nitrogen Clean the main pipe beforehand to avoid blockage of the heat exchanger due to foreign construction matter. Close the isolation valve on the water inlet and outlet pipes before the cleaning. 1. Open the general water supply valve. 2.
  • Page 9: Installing Cables

    Installing Cables Connecting the Equipotential Ground Cable and Power Cable 1. When routing the cables, wrap the section of all signal cables inside the smart cooling product with the corrugated pipes and route them out of the corresponding cable holes so that the strong- and weak-current cables are separated.
  • Page 10 (Optional) Installing a Differential Pressure Sensor Cold aisle Connect a pressure inlet tube to the + mark and route it to the aisle through the hole on the top of the cabinet. Ensure that the pressure inlet faces downwards. Connect another pressure inlet tube to the –...
  • Page 11 1. T/H sensors in the aisle should be installed at the door frame inside the server cabinet and 1.5 m above the ground (33 U). 2. T/H sensor and its cable should be purchased from Huawei by BOM number. 3. Connect the T/H sensor outside the cabinet to T/H_2 port. If there are more than one T/H sensors, connect them in series and then connect them to the T/H_2 port.
  • Page 12 (Optional) Connecting the Monitoring Network Cable The smart cooling product supports both RS485 monitoring and FE monitoring. Connecting the FE monitoring cable (SNMP/Modbus-TCP protocol) The FE monitoring and FE teamwork use the same network cable. Connect the FE monitoring cable in the same process of connecting the FE teamwork network cable. Connecting the RS485 monitoring network cable (Modbus-RTU protocol) •...
  • Page 13: Verifying The Installation

    Verifying the Installation Check No. Check Item Result □ Passed All water pipes are properly and securely installed, and free from leakage, □ Failed blockage, and sharp turns. The liquid level detector is level. The water pan is free from foreign matter such as □...
  • Page 14 (Optional) Setting the Indoor Fan Control Type If a micro differential pressure sensor is installed and the pressure difference control is required, set Air-side difference pressure sensor type to 0–50 Pa, and set the Indoor fan control type to Pressure diff ctrl. It is recommended that the Indoor fan pressure difference setpoint retain the default value.
  • Page 15 After tapping Yes, the bar code and the • Download the Service Expert app from verification code are shown on the screen. Huawei app store and runs on Android. Apply for permission after downloading Open the Service Expert app. the app.
  • Page 16 If a water leakage alarm is generated, the smart cooling product will shut down by default. If you do not need to stop the smart cooling product, Contact Huawei technical support engineers to evaluate risks. After the risk is accepted, choose Settings > System Settings > System Control, and set the Overflow alarm action to No action or Only the indoor fan running.

This manual is also suitable for:

Netcol5000-c032