1. T/H sensors in the aisle should be installed at the door frame inside the server cabinet and 1.5 m
above the ground (33 U).
2. T/H sensor and its cable should be purchased from Huawei by BOM number.
3. Connect the T/H sensor outside the cabinet to T/H_2 port. If there are more than one T/H sensors,
connect them in series and then connect them to the T/H_2 port.
4. Set the sensor positions based on their location and the table.
Name
Cold aisle 1 temp/humid
Cold aisle 2 temp/humid
Cold aisle 3 temp/humid
Cold aisle 4 temp/humid
Cold aisle 5 temp/humid
Hot aisle 1 temp/humid
Hot aisle 2 temp/humid
Hot aisle 3 temp/humid
Hot aisle 4 temp/humid
Hot aisle 5 temp/humid
(Optional) Connecting the Teamwork Network Cable
5.5
The smart cooling product supports both FE teamwork networking and CAN teamwork
networking (hand-in-hand).
All smart cooling products in a
teamwork group must be of the same
model.
Do not directly connect the first and
the last smart cooling products to
form a ring network.
A maximum of 32 smart cooling
products can be networked in one
group. The teamwork cable between
two adjacent smart cooling products
must not exceed 10 m.
If CAN networking is required onsite,
set Enable teamwork CAN resistor
for the first and last smart cooling
products to Yes on the screen.
CAN teamwork network cable
DIP Switch ID
Address
1
11
ON
12
OFF
13
ON
14
OFF
15
ON
21
ON
22
OFF
23
ON
OFF
24
ON
25
Connecting an FE teamwork network cable
11
2
3
4
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
5
6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF

Advertisement

loading

This manual is also suitable for:

Netcol5000-c032