5.2
(Optional) Installing a Differential Pressure Sensor
(Optional) Installing Water
5.3
Censor
Cold aisle
Connect a pressure inlet tube to the + mark and
route it to the aisle through the hole on the top of
the cabinet. Ensure that the pressure inlet faces
downwards. Connect another pressure inlet tube
to the – mark and route it to the cabinet top
through the hole atop.
Hot aisle
Connect a pressure inlet tube to the + mark and
route it to the cabinet top through the hole atop.
Connect another pressure inlet tube to the – mark
and route it to the aisle through the hole on the top
of the cabinet. Ensure that the pressure inlet faces
downwards.
Connect the cable terminal of the micro differential
pressure sensor to the DPT terminal.
(Optional) Installing T/H Sensors
5.4
Outside Cabinet
10