Initial Configuration
2.2
1. Add the NetCol5000-A0031.
2. Set the running parameters and control parameters for the NetCol5000-A0031 on the
ECC800 WebUI.
On the Running Parameters tab page, you are advised to set Temperature setpoint to
23 ° C, Humidity setpoint to 50% RH, Control mode to Cold aisle average value control,
and Cold aisle T/H sensor fault enable and Hot aisle T/H sensor fault enable to Enable.
Commissioning Procedure
2.3
Before commissioning, ensure that the smart cooling product is properly powered on.
Ensure that the electric heating belt of the crankcase has been preheated for more than 12
hours.
1. Log in to the ECC800 WebUI as admin and choose Monitoring > Cooling > NetCol5000-
A0031 to enter the smart cooling product commissioning page.
2. Choose Controls > Control Information, set Startup/Shutdown to ON, and click Submit.
3
Power-On Commissioning for the Management System
Preparations and WebUI Login
3.1
1. Connect a network cable between the PC network port and
the WAN_1 port on the ECC800.
2. Set the IP address of the PC to the same network segment as
the IP address of WAN_1.
3. Set LAN parameters.
4. Set Internet Explorer parameters.
5. Log in to the ECC800 WebUI.
3.2
Preparations and App Login
1. Download and install the FusionModule app from Huawei AppGallery.
If Huawei AppGallery has been installed on the PAD: Log in to the Huawei AppGallery client,
search for FusionModule, and tap Install.
If Huawei AppGallery is not installed on the PAD:
Method 1: Log in to Huawei AppGallery ( https://appgallery.huawei.com/), search for
FusionModule, and tap Install.
Method 2: Log in to the ECC800 WebUI on a PC and scan the QR code to install the app.
2.
Hold down the SW button on the ECC800 for less than 3s to enable the WiFi function.
3.
(Optional) Enable the WiFi function on the ECC800 WebUI.
4.
Log in to the app.
Initial Startup Password Authentication
3.3
1. Authenticate the startup password on the WebUI.
a)
Log in to the ECC800 WebUI as an administrator.
b)
Record the values of Barcode and Verify Code in the displayed Startup Password dialog
box.
c)
Within 24 hours, inform Huawei technical support of Barcode and Verify Code to obtain
the password. After obtaining the password, enter the password in the Password text box
and click Submit to complete the authentication of the startup password.
d)
Choose System Settings > System Parameters > Site Configuration and set System type
to FusionModule500/800.
20
Change the password upon
the first login.