Huawei UPS5000-S-600 kVA User Manual

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

Quick Links

UPS5000-S-600 kVA
User Manual (Singapore, Three-
phase, Three-wire)
Issue
01
Date
2021-04-14
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei UPS5000-S-600 kVA

  • Page 1 UPS5000-S-600 kVA User Manual (Singapore, Three- phase, Three-wire) Issue Date 2021-04-14 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    User Manual (Singapore, Three-phase, Three-wire) About This Document About This Document Purpose This document describes the UPS5000-S-600 kVA in terms of its features, performance, working principles, appearance as well as instructions for installation, and operation and maintenance (O&M). Intended Audience This document is intended for: ●...
  • Page 4 Change History Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues. Issue 01 (2021-04-14) This issue is the first official release. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    2.3.4 Bypass Module................................... 25 2.3.5 Control Module.................................. 26 2.3.5.1 Overview................................... 26 2.3.5.2 ECM..................................... 27 2.3.5.3 Dry contact card................................29 2.3.5.4 Monitoring interface card............................31 2.3.6 MDU....................................... 36 2.4 Typical configurations................................. 38 Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 6 4.1.4 Common Functions Screen............................98 4.2 WebUI....................................... 99 4.2.1 Login...................................... 99 4.2.2 Monitoring Page................................100 4.2.2.1 Param. Settings Page..............................101 4.2.2.2 Comm. Config. Page..............................106 4.2.2.3 Control Page.................................. 106 4.2.3 Query....................................107 Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 7 6 UPS Routine Maintenance....................139 6.1 Monthly Maintenance...............................139 6.2 Quarterly Maintenance..............................140 6.3 Annual Maintenance................................. 141 7 Troubleshooting........................142 8 Technical Specifications..................... 145 A Alarm List..........................149 B Acronyms and Abbreviations................... 162 Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 8 UPS5000-S-600 kVA User Manual (Singapore, Three-phase, Three-wire) Contents C FCC Supplier's Declaration of Conformity (SDoC)............165 Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 9: Safety Information

    The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
  • Page 10 ● Keep irrelevant people away from the equipment. Only operators are allowed to access the equipment. ● Use insulated tools or tools with insulated handles, as shown in the following figure. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 11 Do not change the structure or installation sequence of equipment without permission. ● Do not touch a running fan with your fingers, components, screws, tools, or boards before the fan is powered off or stops running. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 12: Personnel Requirements

    Do not power on the equipment before it is installed or confirmed by professionals. 1.2 Personnel Requirements ● Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations. ●...
  • Page 13 0°C. Handle cables with caution, especially at a low temperature. – Cables stored at subzero temperatures must be stored at room temperature for at least 24 hours before they are laid out. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 14: Installation Environment Requirements

    Install the equipment in an area far away from liquids. Do not install it under areas prone to condensation, such as under water pipes and air exhaust vents, or areas prone to water leakage, such as air conditioner vents, ventilation Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 15 Any violations must be promptly pointed out by the site manager or safety supervisor and the involved personnel should be prompted for correction. Personnel who fail to stop violations will be forbidden from working. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 16: Mechanical Safety

    Ensure that the wider end of the ladder is at the bottom, or protective measures have been taken at the bottom to prevent the ladder from sliding. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 17 D ANGER When removing a heavy or unstable component from a cabinet, be aware of unstable or heavy objects on the cabinet. ● Be cautious to avoid injury when moving heavy objects. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 18: Device Running Safety

    The UPS operating environment must meet the requirements for the climate indicator, mechanically active substance indicator, and chemically active substance indicator in ETSI EN 300 019-1 class 3.6. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 19 UPS is connected to a backfeed protection card. Disconnect the backfeed protection card from the UPS before operating the UPS. Do not use the UPS in the following places: Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Battery Safety

    ● Dispose of waste batteries in accordance with local laws and regulations. Do not dispose of batteries as household waste. If a battery is disposed of improperly, it may explode. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 21 NO TICE To ensure battery safety and battery management accuracy, use batteries provided with the UPS by Huawei. Huawei is not responsible for any battery faults caused by batteries not provided by Huawei. Battery Installation Before installing batteries, observe the following safety precautions: ●...
  • Page 22 Use batteries within the allowed temperature range; otherwise, the battery performance and safety will be compromised. ● Do not throw a lithium battery in fire. ● When maintenance is complete, return the waste lithium battery to the maintenance office. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 23: Others

    UPS output voltage level or frequency. Doing so may affect the power supply to equipment. ● Exercise caution when setting battery parameters. Incorrect settings will affect the power supply and battery lifespan. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 24: Overview

    NO TE The UPS5000-S-600K-NN uses 50 kVA power modules. It can expand up to 600 kVA and is compatible downwards to 50 kVA. This document describes the 600 kVA UPS. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 25: Working Principle

    In normal mode, the rectifier converts AC power into DC power, then the inverter converts DC power into high-precision AC outputs. The conversions protect loads from interference such as input harmonics, glitches, and voltage transients. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 26: Bypass Mode

    UPS transfers to joint power mode. In this case, the power module obtains energy from both the mains and batteries, and the energy is converted into AC outputs over the inverter. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 27: Battery Mode

    UPS transfers from bypass mode to normal mode. In bypass mode or normal mode, the rectifier keeps working and charges batteries using a charger. The ECO mode delivers a high efficiency. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 28: Product Introduction

    Figure 2-7 UPS conceptual diagram in ECO mode NO TE Manual startup is required to ensure that the inverter is in standby state and the power flow has reached the inverter. 2.3 Product Introduction 2.3.1 Appearance Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 29: Product Structure

    UPS5000-S-600 kVA User Manual (Singapore, Three-phase, Three-wire) 2 Overview Figure 2-8 UPS appearance (1) Power cabinet (2) Anchor baffle (3) Monitoring display (4) Bypass cabinet plates unit (MDU) 2.3.2 Product Structure Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 30 User Manual (Singapore, Three-phase, Three-wire) 2 Overview Figure 2-9 Product Structure (1) Power modules (2) Control module (3) Mains input switch (4) Output switch (5) Bypass module (6) Fan power module (7) Bypass input switch Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 31: Power Module

    The module is not configured, the short inverter or rectifier software is being intervals upgraded, or the inverter software is being upgraded (blinking at 4 Hz, on for 0.125s and off for 0.125s). Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 32 Dimensions (H x W x D): 130 mm x 442 mm x 620 mm ● Weight: ≤ 35 kg ● Rated output capacity: 50 kVA/50 kW ● Power density: 50 kVA/3 U Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 33: Bypass Module

    (blinking intervals at 4 Hz, on for 0.125s and off for 0.125s). The bypass software is being upgraded. Alarm Yellow Steady on A minor alarm is generated for the indicator bypass. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 34: Control Module

    (from left to right). The four cards are hot swappable. One subrack is reserved above the dry contact card. A backfeed protection card or dry contact extended card can be inserted into this subrack. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 35: Ecm

    The control module consists of two energy control modules (ECMs) in active/ standby mode. Figure 2-13 ECM Table 2-4 Ports on the ECM Silk Screen Description PARALLEL The PARALLEL port transmits parallel signals between racks. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 36 Controls the running of a single UPS5000 and a parallel system, and reports the UPS5000 status information to other monitoring modules. ● The system provides three types of CAN communication: monitoring CAN communication, intra-rack parallel CAN communication, and inter-rack parallel CAN communication. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 37: Dry Contact Card

    Port for signal ground ● Disconnected: no battery grounding fault Port for detecting diesel ● Connected: D.G. Disconnecte generator (D.G.) mode mode ● Disconnected: Port for signal ground non-D.G. mode Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 38 STATUS_MT maintenance circuit circuit breaker breaker ● Connected: SWITCH Port for signal ground circuit breaker STATUS_0V SWITCH Port for monitoring the ● Connected: Connected STATUS_BP bypass input circuit circuit breaker breaker Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 39: Monitoring Interface Card

    ● In a parallel system, ensure that used dry contacts properly connect to each UPS. The monitoring interface card provides external ports as well as monitoring and control functions for the MDU. The ports include the ambient temperature and Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 40 No power supplied, Mains supplies power, ECO mode, Battery test,, Batt. Volt. Below Thres. and Firefighting action. ● Configure power segment settings based on backup time. DB26 Provides FE, RS485, I2C, and CAN signals. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 41 0.5–1.5 mm ● RS485 cables and FE cables must be shielded cables. Figure 2-17 Figure 2-18 are recommended wiring methods for DO ports. Figure 2-17 Wiring method 1 Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 42 UPS5000-S-600 kVA User Manual (Singapore, Three-phase, Three-wire) 2 Overview Figure 2-18 Wiring method 2 Figure 2-19 COM1 pins Table 2-8 COM1 pin definition Description RS485– RS485+ 12V_PORT Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 43 User Manual (Singapore, Three-phase, Three-wire) 2 Overview Figure 2-20 COM2 pins Table 2-9 COM2 pin definition Description RS485+ RS485– RS485+ RS485– CANH0 CANL0 Figure 2-21 RS485 pins Table 2-10 RS485 pin definition Description RS485_T+ Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 44: Mdu

    RS485–. 2.3.6 MDU Appearance Figure 2-22 MDU (1) Status indicator (2) LCD touchscreen Table 2-11 Status indicator Status Color Meaning A critical alarm has been generated, and the buzzer sounds continuously. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 45 The indicator on the MDU panel is yellow when the bypass supplies power in non-ECO mode. Figure 2-23 MDU ports Table 2-12 Description of MDU ports Port Name Description MUS05A Connects to the MDU and monitoring interface card (DB26) Network port Reserved RS485_1 Reserved Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 46: Typical Configurations

    View or obtain UPS running information during preventive maintenance. NOTE Only Huawei service engineers or authorized service engineers are allowed to use the WiFi module. To ensure security, remove the WiFi module immediately after use.
  • Page 47: Single Ups

    UPS are connected over parallel cables. The parallel connections synchronize the UPS outputs to supply power to loads. If one UPS fails, the other UPSs continue supplying power to loads. Figure 2-24 Conceptual diagram of an N+X parallel system Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 48: Dual-Bus System

    An optional static transfer switch (STS) can be installed to start the bus synchronization controller (BSC). The UPS systems work in normal mode or bypass mode. Figure 2-25 Conceptual diagram of a dual-bus system Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 49: Installation

    Installation 3.1 Installation Preparations 3.1.1 Site 3.1.1.1 UPS Dimensions Figure 3-1 Dimensions (unit: mm) 3.1.1.2 Installation Environment ● Do not install the UPS in high temperature, low temperature, or damp environments. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 50: Installation Clearances

    500 mm space should be reserved at the rear for ventilation. If the UPS will be operated from the rear, at least 800 mm space should be reserved for operations. Figure 3-2 Reserved clearances (unit: mm) Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 51: Tools And Instruments

    Φ16 electric drill Diagonal pliers Crimping tools Wire stripper Electric hydraulic pliers Clamp meter Multimeter Cable tie Level instrument Polyvinyl chloride Cotton cloth Label Electrician's knife (PVC) insulation tape Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 52: Power Cables

    Table 3-1 lists only the common tools for installation and cable connection. For more dedicated tools required, see the corresponding component manuals. Prepare tools based on site requirements. 3.1.3 Power Cables Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 53 Nominal battery discharge current (A) 1316 connector Maximum battery discharge current 1576 Recommended cross- 3 x (2 x 240) sectional area (mm ● When selecting, connecting, and routing power cables, follow local safety regulations and rules. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 54: Unpacking

    ● If multiple loads are connected, specifications for branch circuit breakers must not exceed the recommended specifications. ● The circuit breaker selection principle is to protect loads and cables, and the cascading principle is to realize specific protection. 3.1.4 Unpacking Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 55 Step 2 Remove the UPS outer packing. Step 3 Remove the bolts that secure the UPS to the pallet and remove the UPS from the pallet. Figure 3-3 Removing the pallet from the UPS ----End Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 56: Single Ups Installation

    ● B: mounting holes on the floor Figure 3-4 Mounting hole dimensions (unit: mm) Step 2 Use a hammer drill to drill holes for installing expansion bolts, and install expansion sleeves in the holes. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 57 Partially tighten the expansion bolt and vertically insert it into the hole. Knock the expansion bolt using a rubber mallet until the expansion sleeve is fully inserted into the hole. Partially tighten the expansion bolt. Remove the bolt, spring washer, and flat washer. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 58: Installing The Ups On Channel Steel

    Step 5 Install the front, rear, left, and right anchor baffle plates. Figure 3-8 Installing the front, rear, left, and right anchor baffle plates ----End 3.2.1.2 Installing the UPS on Channel Steel Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 59 Step 4 Use common M12x60 bolts to secure the cabinets into the mounting holes in the channel steel and tighten the bolts. Step 5 Install the front, rear, left, and right anchor baffle plates. ----End Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 60: Ups Cable Connection Reference

    Choose an appropriate cabling route based on the actual situation. The figure is for reference only. Step 4 Connect the cable with a crimped terminal to the corresponding copper bar. Step 5 Clean foreign matter inside the cabinet. ----End Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 61: Routing Cables

    ● (Optional) If copper bar protective covers are installed for the bypass cabinet, remove the protective covers and then the connecting copper bars. The protective covers need to be reinstalled after the connecting copper bars are removed. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 62 ● Before cable connections, ensure that all external input switches are OFF. Paste warning labels to prevent operation on the switches. ● Connect input power cables to the UPS and then to customer equipment. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 63 UPS5000-S-600 kVA User Manual (Singapore, Three-phase, Three-wire) 3 Installation Figure 3-13 Ground cable Step 6 Connect the mains input power cables. Figure 3-14 Connecting the mains input power cables Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 64 Figure 3-15 Connecting AC output power cables Step 8 Connect the bypass input power cables. (Perform this step only when the mains input and bypass input use different power sources.) Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 65 ● The battery voltage may result in serious injury. Observe safety precautions when connecting cables. ● Ensure that cables are correctly connected between battery strings and the battery switch, and between the battery switch and the UPS. Avoid inverse connections. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 66 ● Bind signal cables and power cables separately. ● The number and colors of signal cables are for reference only. ● The figure uses the cable connection between the UPS and the SmartLi as an example. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 67: Remote Epo

    3.2.4 Remote EPO NO TICE ● Huawei does not provide the EPO switch or cable. If the cable is required, the recommended cable is 22 AWG. ● Equip the EPO switch with a protective cover to prevent misoperations, and cover the cable with protective tubing.
  • Page 68: Parallel System Installation

    Step 1 Ground each UPS in a parallel system separately, and connect power cables and battery cables. Step 2 Choose a parallel mode and connect cables to the parallel system based on site requirements. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 69 The length and specifications of power cables on each UPS must be the same to achieve current equalization in bypass mode. The power cables include bypass input power cables and UPS output power cables. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 70: Connecting Signal Cables

    Figure 3-23 Figure 3-24 show the wiring principle for an N+X parallel system. Figure 3-23 N+X parallel system topology NO TICE Figure 3-24 shows only the CM, which stands for the UPS. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 71 Figure 3-24 Signal cable connections of N+X parallel system ● BSC master and slave cables are required in a dual-bus parallel system. Figure 3-25 shows the cable connections for a dual-bus system containing two master systems. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 72: Installation Verification

    Connect signal cables for each UPS. 3.4 Installation Verification NO TICE If the check results of listed items 8 and 9 in Table 3-4 do not meet the acceptance criteria, the UPS may be damaged. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 73 3. There is no foreign matter around switch terminals. 4. There is no foreign matter on the bottom plate of the cabinet. 5. There is no foreign matter on the rear module subrack. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 74 3. Do not remove the dustproof cover before power-on to prevent dust inside the UPS. Figure 3-26 Fill the holes with sealing putty (1) Paper protective film (2) Sealing putty Figure 3-27 Dustproof cover Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 75: User Interface

    User interfaces provided in this document correspond to the monitor display module (MDU) version V300R001C95SPC501 and are for reference only. The LCD screen is divided into three parts: status bar, alarm bar and information area. Figure 4-1 Main Menu screen Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 76: System Info Screen

    Scrolls the page down. Scrolls the page up. Returns to the upper-level menu. Logs a user out. 4.1.2 System Info Screen On the main screen, tap System Info to access the System Info screen. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 77: Module Data Screen

    4.1.2.2 Runn Info Screen On the System Info screen, tap to access the Runn Info screen. On this screen, AC Output, UPS Load, Mains Input, and Bypass Input can be queried. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 78 Load ratio of each phase on the UPS, that is, proportion of actual power to rated power. Crest factor Proportion of the peak value of load current to the valid value. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 79 Line voltage (V) Bypass input line voltage Current (A) Bypass input current Power factor Proportion of the bypass input active power to the bypass input apparent power. Frequency (Hz) Bypass input frequency Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 80 ● If the value is less than 1, the value takes 0. ● If the value is greater than or equal to 1 and less than 2, the value takes 1. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 81: Alarms Screen

    System Info screen to enter the Alarms screen. Figure 4-6 Alarms Screen Active alarms This screen displays alarm information including the severity, name, ID, location, and generation time. Figure 4-7 Active alarms Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 82: Settings Screen

    Settings screen. NO TE If a user is not currently logged in, a dialog box will display for entering a user name and password. Figure 4-9 Settings screen 1 Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 83 Manual: Check that their IP addresses are two different values on the same network segment. Set the UPS IP address to be in the same subnet as the PC IP address. Perform the bitwise AND operation for the UPS IP Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 84 NAT means network address Disable Disable, Enable mapping translation. If it is set to Disable, Internet cannot access IP addresses in the local area network (LAN). Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 85 1, 2 frame format. When the UPS is connected over the serial port Modbus, set this parameter based on the frame format that the upstream device Modbus supports. Figure 4-14 ModbusTCP Settings Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 86 Figure 4-15 Amb T/H Sensor Item Description Default Value Value Range Start – 32–44 address Quantity Number of cascaded ambient temperature 0–4 and humidity sensors. Figure 4-16 WiFi Settings Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 87 HTTPS Refers to a secure Enable Disable, transmission protocol used to Enable access the UPS through a browser. Disable: The HTTPS services are unavailable. Enable: All functions are available. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 88 Default Value Value Range SmartLi start SmartLi communication address address when the UPS queries SmartLi data. Start address Address for the NMS to obtain 0–124 for SmartLi- lithium battery data. communication Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 89 Figure 4-20 System Settings 2 Figure 4-21 System Settings 3 Item Description Default Value Value Range Single/ Specifies whether the UPS works in Single Single, Parallel single mode or parallel mode. Parallel Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 90 ECO voltage is abnormal and transfers to normal mode. BSC mode ● If the system is a dual-bus system Non-BSC Non-BSC, that consists of Huawei UPSs, set Standard this parameter to Standard BSC BSC mode, mode. Opt. BSC card mode ●...
  • Page 91 Indicates whether the BCB trips when Enable Disable, UPS stops the system stops supplying power and Enable power the output power is off. supply Enable Disable, remotely Enable option auth Input Settings Figure 4-22 Input Settings Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 92 Disable Disable, limiting or disable input current Enable limiting to protect generators. Input cur. Limits the input current to 50–200 limiting ratio protect the D.G. Output Settings Figure 4-23 Output Settings Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 93 (less than 20 ms) occurs when the UPS transfers from normal mode to bypass mode. If Output freq. track rate (Hz/s) is fast, the inverter frequency is unstable. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 94 415 V, the default value is +10%. ● When the voltage level is 420 V, the default value is +10%. ● When the voltage level is 480 V, the default value is +10%. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 95 ● Retain default settings for Chg. cur. limiting coef. . Only professional maintenance personnel are allowed to change the settings. Figure 4-25 Battery settings (lithium battery) Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 96 Sched. Time for scheduled shallow 00:00 - 06:00 00:00 - 06:00, shallow dis. discharge test. 06:00 - 12:00, test time 12:00 - 18:00, 18:00 - 24:00 Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 97 Dry contact extended card (MUE07A): provides five routes of input signals and five routes of output signals. On the Settings screen, tap Dry Contact Set. The Dry Contact Set screen is displayed. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 98 Enable, the mains and bypass backfeed protection is enabled. MUS05A DO_1 Action, Controls the status of DO ports on the MUS05A MUS05A DO_2 Action, dry contact card. MUS05A DO_3 Action, MUS05A DO_4 Action Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 99 User Settings NO TICE Set the date and time correctly. Incorrect time display in running and alarm information would lead to analysis errors during maintenance or repair. Figure 4-26 User Settings 1 Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 100: Maintenance Screen

    Set the date and time as required. 4.1.2.5 Maintenance Screen On the System Info screen, tap to display the Maintenance screen. The Maintenance screen provides buttons such as Battery Maint., USB Operations, Inv. ON, and Inv. OFF. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 101 Perform battery maintenance periodically to increase the battery lifespan and improve the UPS reliability. Battery maintenance includes Shallow Dis. Test and Capacity Test. The next maintenance time displayed on the screen indicates the upcoming time in which to check batteries. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 102 Capacity Test Fully discharge batteries. A deep discharge test is conducted to obtain the battery discharge performance data. USB Operations Figure 4-31 USB Operations screen 1 Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 103 (a dialog box is displayed for you to confirm this operation). After performing active/standby switchover, ensure that this ECM is in standby state (that is, the green indicator is blinking) and then maintain the ECM. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 104 ● The UPS generates no battery overtemperature, overvoltage, or overcurrent alarm. No generator is connected to the UPS. ● The mains, batteries, charger, and discharger are normal. No overload alarm is generated. ● SOC > 30% Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 105: About Screen

    Fan Life Estimate ● If the service life of a fan is about to end, that is, Module X fan life (y) is less than Pre-warn. time for fan life(mon), contact Huawei technical support to replace the power module. ●...
  • Page 106: Common Functions Screen

    On the Common Functions to query the AC output, UPS load, and mains input information, start or shut down the inverter, control the buzzer, and query the historical alarms. Figure 4-36 Common Functions 1 Figure 4-37 Common Functions 2 Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 107: Webui

    (startup, shutdown, troubleshooting, runtime clearing, and battery management), system configuration (network parameters, user management, time and date, and site information), and system maintenance (upgrade, calibration, and variables commissioning). Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 108: Monitoring Page

    ● It is advised to change the password after the first login using User Mgmt. on the Config. page to prevent unauthorized access. ----End 4.2.2 Monitoring Page After a user logs in to the WebUI, the Monitoring page is displayed by default. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 109: Param. Settings Page

    Displays system monitoring information. 4.2.2.1 Param. Settings Page Set system parameters, input parameters, output parameters, bypass parameters, battery parameters, and dry contacts on the Param. Settings page. Figure 4-39 Param. Settings Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 110 Module cycle Indicates the rotation interval of modules 1–100 hiber. period in hibernation mode. The default value is 30, which means that the hibernating module is rotated every 30 days. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 111 Enable waveform BCB trips in If this parameter is set to Enable, the Enable Disable, case of EOD BCB will trip in case of EOD. Enable Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 112 Monitors the current differences between Disable Disable, equal. racks or modules. If this parameter is set Enable detection to Enable, the Mod. Cur. Eql. Data can be viewed on the running information screen. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 113 Table 4-16 Bypass Setting Item Description Default Value Value Range BPM mode Specifies whether to start bypass mode Enable Disable, upon BPM when overtemperature occurs. Enable overtemp. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 114: Comm. Config. Page

    4.2.2.2 Comm. Config. Page Open the Comm. Config. page to set communications information. Figure 4-40 Comm. Config. 4.2.2.3 Control Page Open the Control page to control the system running. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 115: Query

    On the Logs page, you can set Log to Historical logs, Cap. test logs, or Common test logs, and query or export logs. NO TE Historical logs can be exported but not queried. Figure 4-43 Logs 4.2.4 Config. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 116: User Management

    4.2.4.2 Site Config. Page On the home page, choose Config. > Site Config.. Figure 4-45 Site Config. ● The NTP parameters are used to set the NTP server address, port number, and synchronization interval. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 117: Rccmd

    RCCMD RCCMD function is set to Disable by default, as shown in Figure 4-46. If required, set it to Enable upon first login. After you submit the setting, the page refreshes. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 118 If it is set to Disable, the RCCMD certificate controls will not be displayed on the page, as shown in Figure 4-49. If SSL Encrypted Transmission is set to Disable, a message indicating there is a risk will be displayed. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 119 The MDU supports 17 alarm events, and a maximum of 50 jobs can be added for each event, as shown in Figure 4-50. Figure 4-50 shows the buttons on the Event Configuration page, and Table 4-18 describes these buttons. Figure 4-50 Event configuration page Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 120 You can delete all jobs of the event by clicking this button. Figure 4-51 shows the buttons after one event is expanded and Table 4-19 describes these buttons. Figure 4-51 Buttons after one event is expanded Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 121 Figure 4-52 RCCMD shutdown ● RCCMD Message: Specify the RCCMD client IP address, port, and message to be conveyed. The RCCMD client will receive the message. For example, enter "This is a test message". Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 122 RCCMD client will receive the UPS input voltage value (for example, single-phase: 220 V; three-phase A: 220 V, B: 220 V, C: 220 V). Table 4-20 lists the signal names that can be entered. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 123 #TEMPDEG Temperature inside the Celsius #AUTONOMTIME Battery backup time minutes #STATUS UPS status #RUNTIME UPS operating time minutes #BATTVOLT Battery voltage #INFREQ Input frequency #BYPASSINFREQ Bypass input frequency #OUTFREQ Output frequency Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 124 After the certificate is uploaded successfully, click Submit. The WebUI of the MDU will restart, and the uploaded certificate will be used for communication. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 125: Managing The Ups By Using The Nms Complying With Rfc1628 Standard

    MIB file which allows the third-party NMS to manage the UPS remotely. Figure 4-57 Download the MIB NO TE The UPS-RFC1628-MIB has more alarms than RFC1628. Download the UPS-RFC1628-MIB before using. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 126: Maint. Page

    Non-professional engineers should exercise caution when operating the maintenance page. On the homepage, click the Maint. tab to open the Maint. page. Maintenance functions include calibration, commissioning variables, upgrade, and downloading data. Figure 4-59 Calib. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 127: Protecting The Server By Using The Rccmd Software

    4.2.6.1 Introduction to the Software The RCCMD shutdown software is part of the centralized monitoring system of the Generex network. The UPS5000 MDU integrates the functions of the Generex RCCMD server: Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 128: Rccmd Event Shutdown And Message Sending

    Figure 4-64 Setting the MDU IP address and SSL encrypted transmission mode on the RCCMD client Step 2 On the MDU WebUI, choose Config. > RCCMD, and set RCCMD function to Enable. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 129: Ups Alive Check Function

    The default interval is 1800s and detection is performed 100 times, as shown in Figure 4-65. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 130 UPS5000-S-600 kVA User Manual (Singapore, Three-phase, Three-wire) 4 User Interface Figure 4-65 Heartbeat detecting mode on the RCCMD client You can also manually detect heartbeat by clicking Run alive check now..Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 131 UPS5000-S-600 kVA User Manual (Singapore, Three-phase, Three-wire) 4 User Interface Figure 4-66 Detecting heartbeat manually Figure 4-67 Detecting heartbeat manually and successfully ----End Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 132: Operations

    Step 1 Close the upstream bypass and mains input switches. Step 2 Close the UPS bypass input switch, mains input switch, and output switch. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar.
  • Page 133: Initial Startup

    Enter the generated password in the password text box on the LCD to start the inverter. ----End 5.1.2.2 Settings Wizard Procedure Step 1 Set the language, time, network parameters, system parameters, and battery parameters on the Settings Wizard screen. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 134 Step 3 After you set parameters on the Settings Wizard screen, the system displays the Bypass mode and No battery alarms, which do not need to be handled. If there is any other alarm, you need to rectify the fault. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 135: Starting The Inverter

    UPS IP address . Step 3 In the address box of the browser, enter https:// Step 4 Enter the correct user name and password and click Login. Figure 5-2 Logging in to the WebUI Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 136: Powering On Loads

    On the LCD On the main screen, tap Common Functions. Tap Inv. OFF. If no user is logged in, enter a user name and password, and tap on the login screen displayed. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 137 After the inverter shuts down, the UPS works in bypass mode if the bypass is normal; the UPS supplies no power and the loads power off if the bypass is abnormal. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 138: Starting The Ups In Battery Mode

    UPS and then open the circuit breaker for each battery string. Step 4 Open the external mains and bypass input switches. ----End 5.3 Starting the UPS in Battery Mode Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 139: Transferring To Bypass Mode

    1 Hz or is steady on. Then, press and hold down the BATT START button on the bypass module for at least 2 seconds. The system automatically enters the battery cold start status. The LCD displays the Huawei logo and an initialization progress bar.
  • Page 140: Testing Batteries

    If the bypass is not normal, the inverter supplies power immediately. If the inverter is not started, the UPS may be disconnected. ----End 5.6 Testing Batteries 5.6.1 Shallow Discharge Test Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 141 ● The battery discharge capacity reaches the specified value (10%–50%, 20% by default). ● The discharge voltage reaches the warning threshold (calculated in real time). ● The load ratio fluctuation exceeds 10%. ● An alarm is generated. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 142: Capacity Test

    ● An alarm is generated. The test is complete when the minimum cell voltage reaches 2.6 V. Data about the most amount of energy discharged is stored once a month for 36 months. ----End Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 143: Test Data Download

    4-pin terminal on the EPO port of the dry contact card. Figure 5-11 EPO ports After you press the EPO button, the EPO and No power supplied alarms are displayed on the LCD. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 144: Clearing The Epo State

    UPS transfers to bypass mode. ● Viewing active alarms on the LCD Choose System Info > Alarms and tap Active Alarms to check that the EPO alarm is cleared. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 145: Exporting Data

    You do not need to query logs. Choose Query > Logs, click Export, and save the file. Step 2 Click Query, and you can see the corresponding historical alarms. Step 3 Click Export and save the displayed webpage. ----End 5.10 Setting Hibernation Mode Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 146 Step 3 Set the Module cycle hibernation period to an integer ranging from 1 to 100. The default value is 30. Figure 5-15 System settings NO TE Click Submit after setting parameters on the WebUI. ----End Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 147: Ups Routine Maintenance

    Customers are not allowed to maintain components behind protective covers that can be removed only using tools. If the components are to be maintained, contact Huawei technical support. ● Only maintenance engineers can maintain power modules and bypass modules.
  • Page 148: Quarterly Maintenance

    Conduct a shallow discharge If an alarm is generated, refer discharge test test when the UPS is backed to the alarm list. (recommended) up to verify that the batteries can discharge normally. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 149: Annual Maintenance

    The circuit breakers and ● Replace the circuit breaker through-current cables meet load breaker. capacity requirements. ● Replace the cable. The actual cable through-current capacity is greater than the circuit breaker specifications. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 150: Troubleshooting

    EOD voltage and 11.3 V/cell. For details about how to rectify common faults, see Table 7-1. If any unmentioned faults occur, see the alarm list chapter, or contact Huawei technical support. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 151 The UPS When the mains Set the UPS working mode Set the working works in is normal, the to ECO mode. mode correctly. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 152 Reduce the load, or normal. indicator is on. experiences improve overtemperature. ventilation. NO TE For details about component replacement and maintenance involved in Troubleshooting and Alarm List, consult Huawei maintenance engineers. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 153: Technical Specifications

    Relative humidity 0%–95% RH (non-condensing) Altitude 0–1000 m When the altitude is greater than 1000 m and less than 4000 m, the rated power should be derated. For details, see the IEC62040-3. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 154 384–528 V AC, derated at 192–384 V AC Rated frequency 50 Hz or 60 Hz Input frequency 40–70 Hz Input PF ● > 0.99 (full load) ● > 0.98 (half load) Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 155 Under rated conditions, the maximum charge power of power a module is 15 kW. Batteries with no Supported neutral wire Table 8-7 Output electrical specifications Item Specifications Output system Three-phase, three-wire, and PE Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 156 ● Load > 150% or a short circuit occurs: run for 200 ms Table 8-8 System electrical specifications Item Specifications Redundancy design The auxiliary power supplies, centralized controllers, and parallel signals use redundancy design. Supported Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 157: A Alarm List

    528 V, the mains input is not normal; if the input voltage is less than 514 V, the sampling circuit of the power module is not normal. Replace the faulty module. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 158 Replace the faulty module. 0001-3 The mains is not Check the mains. normal. 0004-1 Mains ph. Minor Cable connections Verify the cable connections. Reversed are incorrect. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 159 Check whether the cable reversed sequence of the phase sequence is correct three-phase using a multimeter. If no bypass input is multimeter is available, reversed. exchange the positions of any two cables. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 160 2. If they are correctly set, number. certain batteries may be ● The battery faulty. neutral wire is 3. Check whether the battery not installed neutral wire is correctly properly. connected. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 161 If yes, disable it and check whether the alarm is cleared. If the alarm persists, the dry contact board may be faulty. Replace the board. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 162 2. Check whether the fans properly. are functioning properly. ● The air channel Replace the power module for the power if the fans are faulty. module is obstructed. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 163 ● The I2C bus is 1. Rectify the fault and check not normal. whether the alarm is cleared. ● The E2PROM is faulty. 2. If the alarm is generated again, replace the power module. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 164 2. Check that the module reduces the power is not derated due rated system to a fan fault. power. 3. If the alarm persists, ● The module is replace the power module. damaged. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 165 ● The intra-rack INVBYP cable is broken. ● The parallel CAN bus is broken. 0584-2 Inter-rack par. Minor The inter-rack Replace the inter-rack parallel cable alarm parallel cable is cable. faulty. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 166 Replace the dry contact board board fault communication MUE05A. with the dry contact board MUE05A fails. 0090-2 Replace the dry contact board communication MUE06A. with the dry contact board MUE06A fails. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 167 The running status is closed circuit breaker is displayed. No further measures are required. 0335 Generator Warning The generator is The running status is connected connected. displayed. No further measures are required. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 168 2. Check that bypass input the bypass and output power cables input or output on each rack meet the cables is length requirements. incorrect. 3. Rectify any bypass SCR ● The bypass SCR open-circuit. open-circuits. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 169 2. After maintenance, open the maintenance circuit breaker and then start the inverter. 0380 In self-check Warning The inverter is in Wait until the inverter self- self-check. check is complete. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 170: B Acronyms And Abbreviations

    Acronyms and Abbreviations AC transfer switch American Wire Gauge bus synchronization controller BCB box battery circuit breaker box BBB box battery bus bar box Conformite Europeenne digital signal processing economic control operation Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 171 International Electrotechnical Commission liquid crystal display monitor display unit personal computer protective earthing power distribution unit RS485 Recommended Standard static transfer switch SNMP Simple Network Management Protocol Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 172 User Manual (Singapore, Three-phase, Three-wire) B Acronyms and Abbreviations THDi total distortion of the input current waveform THDv total harmonic distortion of output voltage uninterruptible power system Universal Serial Bus VRLA valve-regulated lead acid Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.
  • Page 173 This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Issue 01 (2021-04-14) Copyright © Huawei Technologies Co., Ltd.