Section 6
IED operation
6.2.3

Disturbance reports

PCM600 can be used for creating reports of disturbance recorder data.
6.2.4

IED self-supervision

The IED self-supervision handles internal run-time fault situations. If the IED has a problem, the
internal fail relay is activated and the green Ready LED is flashing.
Internal faults can be divided to hardware errors, run-time errors in the application or operating
system and communication errors. Further actions always depend on the cause of the error.
The IED records IED status data and events.
6.2.5

Non-operative functions

Control functions can be non-operative if:
function is not turned on, that is, Operation = Off.
function is set to a non-operative state by IEC 61850.
Non-operative functions set to a non-operative state by IEC 61850 are listed on the LHMI under Main
menu/Test/Function overview.
IEC16000253 V1 EN-US
6.3

IED parameterization

IED parameters are set via the LHMI or PCM600.
The IED's settings need to be verified before the IED is connected to a system.
38
For more information, see PCM600 documentation.
Only authorized and skilled personnel should analyze the errors and decide on
further actions.
Document all the recorded data from the IED before resetting the tripping and IED
lockout functions.
IEC16000253-1-en.vsdx
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 500 131-UEN Rev. C
GUID-4191AAA0-EA7E-4C74-9B8E-EC44FC390919 v3
GUID-FFF9F2C4-B04B-40BD-A636-8D430DBA69CF v10
GUID-752CDABC-4F21-4A02-AF77-F8AD0165F1DD v2
GUID-F3F7C6D0-1A2B-487B-8291-C5C346F56C3E v9
Switchgear control unit SAM600-IO
Operation manual