Section 7
Operating procedures
GUID-6FC25881-990D-4288-8206-7F807044F572 V2 EN-US
Figure 27:
7.1.2

Recorded data

The IED is provided with intelligent and flexible functionality that collects different kinds of data. The
recorded data gives substantial information for post fault analysis.
Disturbance records
Events
7.1.2.1

Creating disturbance recordings

Normally disturbance recordings are triggered by the IED applications but the recording can also be
triggered manually.
1.
Select Main menu /Disturbance records .
2.
Select Manual Trig with
3.
Press
42
Fault indication
The internal event list is not updated dynamically. To update the list, leave the
Internal events menu and then select it again.
Set the DRPRDRE Operation to On via LHMI or PCM600 and at least one channel
has to be connected. To make the setting, select Main menu /Settings /IED
Settings and then Monitoring /Disturbance report /DisturbanceReport /
DRPRDRE:1 .
or
to execute manual triggering.
© 2017 - 2021 Hitachi Power Grids. All rights reserved
IEC13000247-1-en.vsd
.
1MRK 500 131-UEN Rev. C
GUID-1E9CFEC1-6245-4612-B637-821951B95D60 v7
GUID-B0CE46C1-1219-4BA2-9627-E53FC0413409 v5
Switchgear control unit SAM600-IO
Operation manual