ABB CM Instruction Leaflet
ABB CM Instruction Leaflet

ABB CM Instruction Leaflet

Phase balance current relay

Advertisement

Quick Links

Effective:
June 1980
Supersedes I.L. 41-181.2J, dated March 1978
( | ) Denotes Change Since Previous Issue
!
CAUTION
Before putting relays into service, remove all
blocking which may have been inserted for the
purpose of securing the parts during shipment,
make sure that all moving parts operate freely,
inspect the contacts to see that they are clean
and close properly, and operate the relay to
check the settings and electrical connections.
1.0 APPLICATION
The type CM relay is an induction type relay designed
to protect polyphase electrical machinery against
phase unbalance or phase failure.
As shown in figure 6 the relay may be used with
either three or two-current transformers. With three
ct's the accuracy class must be at least C50; with two
ct's the accuracy class must be at least C70. Other-
wise ct errors during motor starting may cause
undesired CM tripping.
2.0 CONSTRUCTION & OPERATION
The type CM relay consists of two main current units
and their associated resistor and an indicating con-
tactor switch (ICS), or an ac indicating contactor
switch (ACS). The principal component parts of the
relay and their location are shown in figures 1 and 2.
2.1. MAIN UNIT
Each main unit has a pair of electromagnets operat-
All possible contingencies which may arise during installation, operation or maintenance, and all
details and variations of this equipment do not purport to be covered by these instructions. If further
information is desired by purchaser regarding this particular installation, operation or maintenance
of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.
Printed in U.S.A .
ABB Automation Inc.
Substation Automation and Protection Division
Coral Springs, FL 33065
Type CM Phase
Balance Current Relay
ing on a single disc. The disc is damped by a perma-
nent magnet. Each disc carries its own set of
contacts with the two sets being connected in paral-
lel, in order that either disc may close the trip circuit.
The electromagnet pair are mounted face to face on
opposite sides of the disc, and so connected that the
electrical torque of one electromagnet opposes that
of the other, thus producing balanced operating
torque on the disc when the magnitudes of the cur-
rents through each of the two electromagnets are
equal. One of the electromagnets on the lower disc is
connected in series with one of the electromagnets
on the upper disc. Thus phase A current may balance
phase B current on the upper disc, and phase B cur-
rent balance C current on the lower disc. Conse-
quently
operating torque is produced on the two discs, but
with unbalanced conditions or an open phase the bal-
ance on the disc is upset and one or two sets of con-
tacts close.
Each electromagnet has a main coil located on the
center leg of an "E" type laminated structure that pro-
duces a flux which divides and returns through the
outer legs. A shading coil located on one of the outer
legs of the "E" structure causes the flux through that
leg to lag the main pole flux. The out-of-phase fluxes
thus produced in the air gap will cause disc rotation.
A resistor located to the rear of each main unit is
used as an aid in balancing the opposing torques by
controlling the current flow through the shading coils.
For some CM relays, the front electromagnet may
have adjustable plugs which are used to aid in cali-
bration.
with
balanced
system
Instruction Leaflet
41-181.2K
conditions,
no

Advertisement

Table of Contents
loading

Summary of Contents for ABB CM

  • Page 1 If further information is desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB Power T&D Company Inc. representative should be contacted. Printed in U.S.A .
  • Page 2 41-181.2K Figure 1a. Non-Tapped Type CM Relay without case Figure 1b. Non-Tapped Type CM Relay without case (Front View (Rear Vies)
  • Page 3 41-181.2K Figure 2a. Type CM Tapped Relay without case Figure 2b. Type CM Tapped Relay without case (Front View) (Rear View)
  • Page 4: Energy Requirements

    The front spring, in addition to holding the target, pro- 188A145 vides restraint for the armature and thus controls the pickup value of the switch. Figure 3. Typical Operating Curve of the Type CM Relay 2.3. AC INDICATING CONTACTOR SWITCH 3.1. TRIP CIRCUIT (ASC)
  • Page 5: Installation

    For all electrical checks refer to test diagram figure 4 of the connecting screw. for tapped CM, put tap screw in one amp setting.
  • Page 6 41-181.2K Sub 2 188A146 Figure 4. Typical Time Curve with Zero Restraint of the Type CM Relay 1. Contacts Electromagnets are to be energized alone (zero restraint). Apply ten amperes and note that con- Stationary contacts assembly should be aligned tacts make at one second ±...
  • Page 7: Routine Maintenance

    Apply six amperes to front electromagnet and 8.1. MAIN UNITS vary current flowing through rear electromagnet. For all electrical checks refer to test diagram figure 5. For tapped CM, put tap screw in one amp tap setting. a) The moving contact should make with the...
  • Page 8: Renewal Parts

    When ordering parts, always give the the ICS. This value of current should not be greater complete nameplate data. 876A588 Figure 6. Relay Type CM Phase Balance Current With Taps And Acs Unit In Type FT-31 Case.
  • Page 9 41-181.2K 187A232 Figure 7. Internal Schematic of the Non-Tapped Type CM Relay in the Type FT-31 Case 762A812 Figure 8. Internal Schematic of the Tapped Type CM Relay in the Type FT-31 Case...
  • Page 10 41-181.2K Figure 9. Element Assembly for CM Relay (Front View)
  • Page 11 41-181.2K Sub 4 188A144 Figure 10. External Schematic Diagram of the Type CM Relay in the Type FT-31 Case Figure 10. External Schematic Diagram of the Type CM Relay in the Type FT-31 Case...
  • Page 12 41-181.2K 57S902 Figure 11. External Schematic Diagram of the Type CM Relay in the Type FT-31 Case ABB Automation Inc. 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL: 954-752-6700 FAX: 954-345-5329 Printed in U.S.A . visit our website at www.abbus.com/papd...

Table of Contents