In Service Operation

6.10 Settings Group Selection

6.10

Settings Group Selection

For different applications you can save the respective function settings in so-called Settings groups, and if
necessary enable them quickly.
The relay provides 2 groups of settings – Group number (Gn) 1 to 2. At any time, only one group of settings
can be active - SYSTEM CONFIG > Active Group setting. During operation, you can switch between
settings groups. The source of the switchover can be selected via a parameter.
You can switchover the settings groups via the following alternatives:
Via the relay fascia directly on the device
Via an online Reydisp Evolution connection to the device
Via binary inputs
Via a communication connection to the substation automation technology
The communication protocols IEC 60870-5-103, Modbus TCP can be used for switching the settings groups.
A settings group includes all switchable settings of the device. Except for a few exceptions (for example,
general device settings such as rated frequency), all device settings can be switched.
NOTE
i
i
When the settings group or any setting parameters is changed, the relay restarts to apply the new settings
and the protection is not active for the moment.
NOTE
i
i
Only one setting group is available for the MLFB 7SR450[1/3]-xGA10-1AA0 variant.
3
Only in 7SR45 dual powered relays
82
3
Reyrolle, Operating, Manual
C53000-B7040-C101-1, Edition 08.2020