Installing The Wiring (Supplement To Ach550-Uh User's Manual) - ABB ACH550 User Manual

Table of Contents

Advertisement

8
Ratings and Frame Size
The chart in the "Ratings" section of the ACH550-UH User's Manual lists technical
specifications, and identifies the drive's frame size – significant, since some
instructions in this document vary, depending on the drive's frame size. To read the
Ratings table, you need the "Output current rating" entry from the type code (see
above). Also, when using the Ratings tables, note that there are two tables based on
the drive's "Voltage rating".
Suitable Mounting Location (Supplement to ACH550-UH User's Manual)
In selecting a suitable mounting location for E-Bypass configurations, refer to the
Technical Data in this manual for the appropriate information on:
• Branch circuit protection
• Dimensions and weights

Installing the Wiring (Supplement to ACH550-UH User's Manual)

WARNING!
• Do not connect or disconnect input or output power wiring, or control
wires, when power is applied.
• Never connect line voltage to drive output Terminals T1, T2, and T3.
• Do not make any voltage tolerance tests (Hi Pot or Megger) on any part of
the unit. Disconnect motor wires before taking any measurements in the
motor or motor wires.
• Make sure that power factor correction capacitors are not connected
between the drive and the motor.
Wiring Requirements
Refer to the "Wiring Requirements" Section in the ACH550 User's Manual. The
requirements apply to all ACH550 drives. In particular:
• Use separate, metal conduit runs to keep these three classes of wiring apart:
– Input power wiring.
– Motor wiring.
– Control/communications wiring.
• Properly and individually ground the drive, the motor and cable shields.
Installation
E-Bypass Configurations for ACH550 Drives

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs55001/u1

Table of Contents