E-Bypass Configurations for ACH550 Drives
Fuses, 500...600 Volt, Fuses
HP
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
Line Reactor
The ACH550 E-Bypass may contain optional input line reactors to provide additional
input impedance on the VAC line. This impedance is in addition to the approximate
5% input impedance provided by internal reactors that are standard in the drive.
Drive's Power Connection Terminals
The following tables list power and motor cable terminal sizes for connections to an
input circuit breaker or disconnect switch, a motor terminal block and ground lugs.
The tables also list torque that should be applied when tightening the terminals.
500...600 Volt
Identification
ACH550-xx-02A7-6
ACH550-xx-03A9-6
ACH550-xx-06A1-6
ACH550-xx-09A0-6
ACH550-xx-011A-6
ACH550-xx-017A-6
ACH550-xx-022A-6
ACH550-xx-027A-6
ACH550-xx-032A-6
ACH550-xx-041A-6
ACH550-xx-052A-6
ACH550-xx-062A-6
ACH550-xx-077A-6
ACH550-xx-099A-6
ACH550-xx-125A-6
ACH550-xx-144A-6
Drive Input Fuse Ratings
Frame
Amps
Size
(600V)
R2
15
R2
15
R2
15
R2
15
R2
30
R2
30
R3
40
R3
40
R4
100
R4
100
R4
100
R4
100
R6
125
R6
125
R6
160
R6
200
39
Bussmann
Type
KTK-R-15
KTK-R-15
KTK-R-15
KTK-R-15
KTK-R-30
KTK-R-30
JJS-40
JJS-40
JJS-100
JJS-100
JJS-100
JJS-100
170M1368
170M1368
170M1369
170M1370
Technical Data