ABB ACH550 User Manual page 24

Table of Contents

Advertisement

22
500...600 Settings
HP
7.5
100
125
150
Switch Code
Switch
Position
Default settings in (parentheses).
Output Contactor Control
In the unlikely event of failure in the bypass control electronics, the user can engage
the drive output contactor without the control electronics by moving jumper J2 to the
Output Contactor position – see "Adjustment Locations" on page 19. When the
jumper is in the Output Contactor position, the Drive contactor is energized and the
Bypass contactor is de-energized. The contactors, and therefore the system, are not
controlled by the bypass electronics when jumper J2 is in the Output Contactor
Installation
500...600 Volt, Codes for Overload Trip Current DIP Switch
Identification
2
ACH550-xx-02A7-6
3
ACH550-xx-03A9-6
5
ACH550-xx-06A1-6
ACH550-xx-09A0-6
10
ACH550-xx-011A-6
15
ACH550-xx-017A-6
20
ACH550-xx-022A-6
25
ACH550-xx-027A-6
30
ACH550-xx-032A-6
40
ACH550-xx-041A-6
50
ACH550-xx-052A-6
60
ACH550-xx-062A-6
75
ACH550-xx-077A-6
ACH550-xx-099A-6
ACH550-xx-125A-6
ACH550-xx-144A-6
A
B
1
(OFF) / ON = Automatic Transfer Bypass Feature (OFF) / ON
2
(OFF) / ON = Mode / Override Relay RO4 (Mode) / Override
3
4
OFF / (ON) = NEMA Class 30 / (NEMA Class 20) overload trip curve
5
6
OFF
OFF
7
OFF
OFF
8
OFF
ON
E-Bypass Configurations for ACH550 Drives
Frame Size
Switch Setting Configurations
Switch Code
C
D
E
RESERVED (OFF)
RESERVED (OFF)
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
Switch Code
R2
A
R2
A
R2
A
R2
A
R2
A
R2
B
R3
B
R3
C
R4
C
R4
D
R4
D
R4
D
R6
E
R6
E
R6
F
R6
F
F
G
ON
ON
OFF
ON
ON
OFF
H
ON
ON
ON