34
Basic Control Connections for Damper Actuator Control
Auto Start
Damper End Switch
Firestat, Freezestat, High
Static Switch
To Damper Actuator
Parameter Number
Start-up
X1
Terminals on ACH550 Control Board
1
Terminal for signal cable shield
2
Analog Input Channel 1
3
Analog Input Common
4
10 V / 10 mA Reference voltage for potentiometer
15 Digital Input 3
16 Digital Input 4
17 Digital Input 5
18 Digital Input 6
X2
Terminals on E-Bypass Control Board
1
Start/Stop
2
Run Enable
3
Safety Interlocks
4
Override 1 – Fireman's Override
5
Override 2 – Bypass Override
6
I/O Power Supply – Not used
7
ACH550 24V voltage supply
8
Start/Stop 2
Internally
9
Run Enable 2
Supplied
10 Safety Output
24 VDC
11 Drive RO3 – N.O.
12 Drive RO3 – Com
13 Drive RO1 – N.C.
14 Drive RO1 – Com
15 Common – Use only with Internal 24 VDC Supply.
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
1001
EXTERNAL 1 COMMANDS
1002
EXTERNAL 2 COMMANDS
1601
1401
1403
E-Bypass Configurations for ACH550 Drives
Pre-wired to
ACH550
terminal block
X1.
Do NOT
disturb.
RO1 – Bypass Fault – N. C.
RO1 – Bypass Fault – N. O.
RO1 – Bypass Fault – Com
RO2 – System Run – N. C.
RO2 – System Run – N. O.
RO2 – System Run – Com
RO3 – System Started – N. C.
RO3 – System Started – N. O.
RO3 – System Started – Com
RO4 – Mode/Override – N. C.
RO4 – Mode/Override – N. O.
RO4 – Mode/Override – Com
RO5 – Drive Fault – N. C.
RO5 – Drive Fault – N. O.
RO5 – Drive Fault – Com
RO6 – Hand/Off/Auto – N. C.
RO6 – Hand/Off/Auto – N. O.
RO6 – Hand/Off/Auto – Com
Description
RUN ENABLE
RELAY OUTPUT 1
RELAY OUTPUT 3
ACH550 Drive
E-Bypass
Jumper J3
External
Internal
115 VAC
24 VDC
Powered
Powered
I/O
I/O
Setting
1 (DI1)
1 (DI1)
2 (DI2)
7 (STARTED)
3 (FAULT (-1))