Haier AB12CS1ERA Service Manual
Hide thumbs Also See for AB12CS1ERA:

Advertisement

SUPER MATCH
Service Manual
SYJS-06-2018 REVB
Edition: 2018-06

Advertisement

Table of Contents
loading

Summary of Contents for Haier AB12CS1ERA

  • Page 1 SUPER MATCH Service Manual SYJS-06-2018 REVB Edition: 2018-06...
  • Page 2: Table Of Contents

    Super Match CONTENTS Part 1 General Information ............................1 1. Indoor/outdoor unit models ............................2 2. Feature ..................................4 3. Maxi split and function ............................6 Part 2 Indoor Units ..............................8 1. 4-Way Cassette type .............................9 2. Convertible type ..............................52 3. Duct indoor type ..............................99 4.
  • Page 3: Part 1 General Information

    Super Match Part 1 General Information 1. Indoor/outdoor unit models ............................2 2. Feature ..................................4 3. Maxi split and function ............................6...
  • Page 4: Indoor/Outdoor Unit Models

    Super Match Indoor/outdoor unit models Indoor unit models 4-way Cassette Type (PB-700IB) Low ESP duct (25Pa) AB09CS1ERA AD12LS1ERA AB09CS2ERA AD18LS1ERA AB12CS1ERA(S) AD24LS1ERA AB12CS2ERA(S) AB18CS1ERA(S) AB18CS2ERA(S) 4-way Cassette Type (PB-950JB) Medium ESP duct (70Pa) AB24ES1ERA(S) AD12MS1ERA AB28ES1ERA(S) AD12MS1ERA(D) AD18MS1ERA AD18MS1ERA(D) AD24MS2ERA...
  • Page 5 Super Match Outdoor unit models 1U24GS1ERA 3U19FS1ERA 3U19FS1ERA(N) 1U28HS1ERA(S) 3U24GS1ERA 1U28GS2ERA(S) 3U24GS1ERA(N) 1U36HS1ERA(S) 1U48LS1ERA(S) 4U26HS1ERA 1U48LS1ERB(S) 4U30HS1ERA 1U48LS1EAB(S) 5U34HS1ERA 1U48IS1ERB(S) 5U45LS1ERA 1U48IS1EAB(S) 1U60IS1ERB(S) 1U60IS2ERB(S) 1U60IS1EAB(S) 1U48IS1EAB(S) 1U60IS2EAB(S)
  • Page 6: Feature

    Super Match 2. Feature 2.1 Easy Instalaltion, More User Friendly • Easy vacuum & charging Vacuum and charging every indoor unit just one time from general stop valve(1:4 to 1:5 outdoor unit) General stop valve • Easy start up& maintenance §...
  • Page 7 Super Match 2.2 Wider Installation • Wider installation O.U. 15m I.U. above O.U. 10m I.U. below O.U. Total pipe length≤100m I.U. I.U. 7.5m I.U. I.U. Individual pipe length≤25m • Wider range operation: Wider range operation of outside temperature 46°CDB Cooling: from -10 C to 46 24°CDB Heating: from -15...
  • Page 8: Maxi Split And Function

    Flared connection outdoor indoor outdoor 2Y200A unit unit unit side AB28ES1ERA (S) side 125±1 unit side 450±5 side 1U60IS1ERB(S) AC28ES1ERA(S) AB12CS1ERA (S) 3-Ø6.35 Flared connection AB12CS2ERA (S) FQG- Ø9.52 Flared connection 1U36HS1ERA(S) outdoor indoor unit 3Y100A unit side side AC12CS1ERA(S) 410±5...
  • Page 9 1U60IS1ERB(S) +0.15 IDФ12.9 side Ø19.05 AC18CS1ERA(S) Flared connection outdoor 1U60IS2ERB(S) 410±5 unit side (342.5) *400±2.5 indoor unit side 1U48LS1ERA(S) AB12CS1ERA(S) 4-Ø6.35 80±3 80±3 80±3 Flared connection 4-Ø9.52 1U48LS1ERB(S) +0.15 AB12CS2ERA (S) Flared connection IDФ9.7 +0.15 IDФ12.9 Ø9.52 FQG- Flared connection...
  • Page 10: Part 2 Indoor Units

    Super Match Part 2 Indoor Units 1. 4-Way Cassette type ..............................9 1.1 Features ................................10 1.2 Specification ..............................11 1.3 Dimension .................................30 1.4 Piping diagram ..............................32 1.5 Wiring diagram ..............................33 1.6 Air velocity and temperature distribution ......................35 1.7 Sound Pressure Level ............................39 1.8 Installation .................................44 2.
  • Page 11: Way Cassette Type

    Super Match 1. 4-Way Cassette type 1.1 Features ................................10 1.2 Specification ..............................11 1.3 Dimension .................................30 1.4 Piping diagram ..............................32 1.5 Wiring diagram ..............................33 1.6 Air velocity and temperature distribution ......................35 1.7 Sound Pressure Level ............................39 1.8 Installation .................................44...
  • Page 12: Features

    Super Match 1.1 Features AB09CS1ERA AB09CS2ERA AB12CS1ERA(S) AB12CS2ERA(S) AB18CS1ERA(S) AB18CS2ERA(S) AB24ES1ERA(S) AB36ES1ERA(S) AB60CS1ERA(S) AB48ES1ERA(S) AB60ES2ERA(S) Compact Design (Only for units AB12-AB18) The panel dimension is 700mm*700mm, smaller and universal. Harmony with the environment. The unit diamnesion is 570mm*570mm*260mm for easy installation.
  • Page 13: Specification

    Super Match 1.2 Specification Item Model AB09CS1ERA (S) Function —— Cooling Heating Capacity 2600 2900 Censible heat ratio 0.71 Dehumidifying capacity 10-³xm³/h power supply 1PH, 220-230V~, 50/60Hz Type × Number —— centrifugal*1 Speed(H-M-L) r/min 690/620/560 Fan motor output/input 10/33 power Air-flows (H/M/L) m³/h 620/520/450...
  • Page 14 Super Match Item Model AB09CS2ERA (S) Function —— Cooling Heating Capacity 2600 2900 Censible heat ratio 0.71 Dehumidifying capacity 10-³xm³/h power supply 1PH, 220-230V~, 50/60Hz Type × Number —— centrifugal*1 Speed(H-M-L) r/min 690/620/560 Fan motor output/input 10/33 power Air-flows (H/M/L) m³/h 620/520/450 Speed (Hi/Me/Lo)
  • Page 15 Super Match Item Model AB12CS1ERA(S) Function cooling heating 3.50(0.9 ~ 4.5) 3.7(1 ~ 4.8) Capacity Sensible heat ratio 0.71 Total power input 1.06(0.28~1.8) 0.99(0.28~1.8) Max. power input 1800 1800 EER or COP 3.31 3.71 Dehumidifying capacity 10‐³×m³/h Power cable H05RN-F 4G 4.0mm2...
  • Page 16 H05RN-F 4G 4.0mm2 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current A / A 5.0(1.2-8.0)/8.0 4.7(1.2-8.0)/8.0 Start Current Unit model (color) AB12CS1ERA(S) Type × Number CENTRIFUGALX1 Speed(H-M-L) r/min 690/560/520 Fan motor output/ input power 11/30 Air-flow(H-M-L) m³/h 620/520/450 inner grooved pipe/φ7.0...
  • Page 17 Super Match Item Model AB18CS1ERA(S) Function cooling heating Capacity 5(1.8~5.8) 5.2(2~6.5) Sensible heat ratio 0.71 Total power input 1.53(0.55~2) 1.52(0.6~2) Max. power input 2000 2000 EER or COP 3.26 3.42 Dehumidifying capacity 10‐³×m³/h Power cable H05RN-F 4G 4.0mm2 Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current...
  • Page 18 H05RN-F 4G 4.0mm2 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current A / A 5.0(1.2-8.0)/8.0 4.7(1.2-8.0)/8.0 Start Current Unit model (color) AB12CS1ERA(S) Type × Number CENTRIFUGALX1 Speed(H-M-L) r/min 690/560/520 Fan motor output/ input power 11/30 Air-flow(H-M-L) m³/h 620/520/450 inner grooved pipe/φ7.0...
  • Page 19 Super Match Item Model AB24ES1ERA(S)/1U24GS1ERA Function cooling heating Capacity 7.1(2~7.3) 7.1(2.5~8) Sensible heat ratio 0.72 Total power input 2.20(0.5~2.6) 1.91(0.5~2.6) Max. power input 2600 2600 EER or COP 3.23 3.72 Dehumidifying capacity 10‐³×m³/h Power cable H05RN-F 4G 4.0mm2 Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current...
  • Page 20 Super Match Item Model AB28ES1ERA(S)/1U28HS1ERA(S) Function cooling heating Capacity 8(2.2-9.5) 9.1(2.5-10.0) Sensible heat ratio Total power input 2.492(0.5-4.2) 2.668(0.5-4.2) Max. power input 4600 4600 EER or COP 3.21 3.41 Dehumidifying capacity 10-³×m³/h Power cable 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current A / A 10.8(2.2-18.5)/20...
  • Page 21 Super Match Item Model AB28ES1ERA(S)/1U28GS2ERA(S) Function cooling heating Capacity 7.8(2.2-9.5) 8.5(2.5-10.0) Sensible heat ratio 0.74 Total power input 2.43(0.5-4.2) 2.49(0.5-4.2) Max. power input 4200 4200 EER or COP 3.21 3.41 Dehumidifying capacity 10‐³×m³/h Power cable 1PH, 220-230V~, 50/60Hz Power source(indoor unit) N, V, Hz Running /Max.Running current A / A...
  • Page 22 Super Match Item Model AB36ES1ERA(S)/1U36HS1ERA(S) Function cooling heating Capacity 9.5(2.2-11.2) 10.1(2.5-11.8) Sensible heat ratio Total power input 2.96(0.5-4.3) 2.798(0.5-4.3) Max. power input 4300 4300 EER or COP 3.21 3.61 Dehumidifying capacity 10-³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A 12.87(2.2-19.3)/19.3...
  • Page 23 Super Match Item Model AB48ES1ERA(S)/1U48IS1EAB(S) Function cooling heating Capacity 14.1 15.5 Sensible heat ratio 0.74 Total power input 4.66 4.82 Max. power input 6500 6500 EER or COP 3.03(B) 3.22(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50/60 Running /Max.Running current A / A...
  • Page 24 Super Match Item Model AB48ES1ERA(S)/1U48IS1ERB(S) Function cooling heating Capacity 13.6(6.0-15) 14.5(6.0~16.5) Sensible heat ratio 0.74 Total power input 4.5(2.0---6.0) 4.25(2.0---6.0) Max. power input 6000 6000 EER or COP 3.02(B) 3.41(B) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A...
  • Page 25 Super Match Item Model AB48ES1ERA(S)/1U48LS1EAB(S) Function cooling heating Capacity 13.0 14.1 Sensible heat ratio Total power input 4.62 4.85 Max. power input 6500 6500 EER or COP 2.81(C) 2.91(E) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1N~,220~230, 50/60 Running /Max.Running current A / A 8.0/10.5...
  • Page 26 Super Match Item Model AB48ES1ERA(S)/1U48LS1ERA(S) Function cooling heating Capacity 12.1(6.0-14.1) 13.0(6.0~16.0) Sensible heat ratio 0.74 Total power input 4.02(2.0---6.0) 4.0(2.0---6.0) Max. power input 5600 5600 EER or COP 3.01(B) 3.25(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A...
  • Page 27 Super Match Item Model AB48ES1ERA(S)/1U48LS1ERB(S) Function cooling heating Capacity 12.1(6.0-14.1) 13.0(6.0~16.0) Sensible heat ratio 0.74 Total power input 4.02(2.0---6.0) 4.0(2.0---6.0) Max. power input 6000 6000 EER or COP 3.01(B) 3.25(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 3, 380~400, 50 Running /Max.Running current A / A...
  • Page 28 Super Match Item Model AB60CS1ERA(S)/1U60IS1EAB(S) Function cooling heating Capacity 15.1 16.3 Sensible heat ratio 0.73 Total power input 5.01 5.07 Max. power input 6500 6500 EER or COP 3.01(B) 3.21(C) Dehumidifying capacity 10‐³×m³/h Power cable 1, 220 ~ 230, 50 Power source N, V, Hz Running /Max.Running current...
  • Page 29 Super Match Item Model AB60CS1ERA(S)/1U60IS1ERB(S) Function cooling heating Capacity 15.3(4.0~16.5) 16.3(4.0~17.5) Sensible heat ratio 0.73 Total power input 5.06(2.0---6.5) 5.07(2.0----6.5) Max. power input 6500 6500 EER or COP 3.02(B) 3.21(C) Dehumidifying capacity 10‐³×m³/h Power cable 1, 220 ~ 230, 50 Power source N, V, Hz Running /Max.Running current...
  • Page 30 Super Match Item Model AB60ES2ERA(S)/1U60IS2EAB(S) Function cooling heating Capacity 14.1 15.5 Sensible heat ratio 0.74 Total power input 4.66 4.82 Max. power input 6500 6500 EER or COP 3.03(B) 3.22(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220~230V, 50/60Hz Running /Max.Running current A / A...
  • Page 31 Super Match Item Model AB60ES2ERA(S)/1U60IS2EAB(S) Function cooling heating Capacity 13.6(6.0-15) 14.5(6.0~16.5) Sensible heat ratio 0.74 Total power input 4.24(2.0---6.0) 4.02(2.0---6.0) Max. power input 6000 6000 EER or COP 3.21(A) 3.61(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220~230V, 50/60Hz Running /Max.Running current A / A...
  • Page 32: Dimension

    Super Match 1.3 Dimension AB09CS1ERA AB12CS1ERA(S) AB18CS1ERA(S) AB09CS2ERA AB12CS2ERA(S) AB18CS2ERA(S) AB24ES1ERA(S) AB28ES1ERA(S)
  • Page 33 Super Match AB36ES1ERA(S) AB48ES1ERA(S) AB60ES2ERA(S) Indoor unit Panel AB09CS1ERA AB12CS1ERA(S) PB-700IB AB18CS1ERA(S) AB24CS1ERA(S) AB28CS1ERA(S) AB36CS1ERA(S) PB950JB AB48CS1ERA(S) AB60CS2ERA(S) AB60CS1ERA(S) PB-1340IB...
  • Page 34: Piping Diagram

    Super Match 1.4 Piping diagram Liquid pipe Gas pipe Filter Filter Indoor heat exchanger...
  • Page 35: Wiring Diagram

    Super Match 1.5 Wiring diagram AB09CS1ERA AB12CS1ERA(S) AB18CS1ERA(S AB24ES1ERA(S)
  • Page 36 Super Match AB28ES1ERA (S) AB36ES1ERA(S) AB48ES1ERA(S) AB60CS1ERA(S) AB60ES2ERA(S)
  • Page 37: Air Velocity And Temperature Distribution

    Super Match 1.6 Air velocity and temperature distribution AB09/12CS1ERA: a. Cooling / Air Velocity Distribution Cooling Blowy angle:40 Air Velocity Distribution 2.7m 1.5m/s 1.5m/s 1.0m/s 1.0m/s 0.5m/s 0.5m/s b. Cooling / Temperature Distribution Cooling Blowy angle:40 Temperature Distribution 2.7m...
  • Page 38 Super Match c. Heating / Air Velocity Distribution Heating Blowy angle:70 Air velocity Distribution 2.7m 1.5m/s 1.5m/s 1.0m/s 1.0m/s 0.5m/s 0.5m/s d. Heating / Temperature Distribution Heating Blowy angle:70 Temperature Distribution 2.7m...
  • Page 39 Super Match AB18-48 a. Cooling / Air Velocity Distribution Cooling Blowy angle:40 Air Velocity Distribution 2.7m 1.5m/s 1.5m/s 1.0m/s 1.0m/s 0.5m/s 0.5m/s b. Cooling / Temperature Distribution Cooling Blowy angle:40 Temperature Distribution 2.7m...
  • Page 40 Super Match c. Heating / Air Velocity Distribution Heating Blowy angle:70 Air velocity Distribution 2.7m 1.5m/s 1.5m/s 1.0m/s 1.0m/s 0.5m/s 0.5m/s d. Heating / Temperature Distribution Heating Blowy angle:70 Temper ature Distribution 2.7m...
  • Page 41: Sound Pressure Level

    Super Match 1.7 Sound Pressure Level 1) Testing illustrate: 2) Testing condition: a: Unit running in the normal condition b: Test in the semi-anechoic chamber c: Noise level varies from the actual factors such as room structure, etc.
  • Page 42 Super Match...
  • Page 43 Super Match...
  • Page 44 Super Match...
  • Page 45 Super Match...
  • Page 46: Installation

    Check if the installation place is strong enough to hold weight. Take necessary measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern for place need be reinforced) Model AB09CS1ERA AB12CS1ERA(S) AB18CS1ERA(S) AB24ES1ERA(S) AB28ES1ERA(S)
  • Page 47 Super Match 3. PREPARATION FOR THE INSTALLATION (1) Position of ceiling opening between unit and suspending bolt. AB36ES1ERA(S) AB48ES1ERA(S) AB60ES2ERA(S) 860-890 (ceiling hole) (Hanging position) Wall or barrier Barrier Ground...
  • Page 48 Super Match Indoor unit Panel AB60CS1ERA(S) AB09CS1ERA 1280(Ceiling opening) AB12CS1ERA(S) PB-700IB 1070 (Distance between AB18CS1ERA(S) suspending bolts) AB24ES1ERA(S) AB28ES1ERA(S) PB-950JB AB36ES1ERA(S) AB48ES1ERA(S) AB60ES2ERA(S) AB60CS1ERA(S) PB-1340IB 20 Over (2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.) ■...
  • Page 49 Super Match 4. INSTALLATION OF INDOOR UNIT In the case of new ceiling (1) Install unit temporally Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket. (2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details.
  • Page 50 Super Match Pipe size Tighten torque A(mm) Flare shape 1420~1720N.cm 6.35 8.3~8.7 (144~176kgf.cm) 3270~3990N.cm 9.52 12.0~12.4 R0.4 ~ 0.8 (333~407kgf.cm) 4950~6030N.cm 12.7 12.4~16.6 (490~500kgf.cm) 6180~7540N.cm 15.88 18.6~19.0 (630~770kgf.cm) 9720~11860 N.cm 19.05 22.9~23.3 (990~1210 kgf.cm) 6. INSTALLATION OF WATER DRAINAGE PIPE (1) Install water drainage pipe ■...
  • Page 51 Super Match <Cautions for the drain water lifting pipe > Installation height shall be less than 280mm. There should be a right angle with unit, 300mm from unit. Note: The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it. If several water hoses join together, do as per following procedures.
  • Page 52 Super Match AB09CS1ERA AB12CS1ERA(S) AB18CS1ERA(S) AB24ES1ERA(S) AB28ES1ERA(S) AB36ES1ERA(S) AB48ES1ERA(S) AB60CS1ERA(S) AB60ES2ERA(S) Indoor unit Indoor unit terminal block terminal block Outdoor unit Outdoor unit terminal block terminal block Power supply:380-400V, 3N~,50Hz Power supply:1PH,220-230V~,50Hz 7. WIRING ■ All supplied parts. materials and wiring operation must in appliance with local code and regulations.
  • Page 53 Super Match Pay special care to the following and check after installation Item to the checked Improper installation may cause Is indoor unit firmly installed? Unit might fall down, make vibration or noise. Is gas leakage check performed? This may lead to gas shortage. Is unit properly insulated? Dew or water drop may occur.
  • Page 54: Convertible Type

    Super Match 2. Convertible type 2.1 Features ................................53 2.2 Specification ..............................55 2.3 Piping diagram ..............................70 2.4 Wiring diagram ..............................71 2.5 Air velocity and temperature distribution ......................73 2.6 Sound Pressure Level ............................81 2.7 Installation .................................85...
  • Page 55: Features

    Super Match 2.1 Features AC12CS1ERA(S) AC48FS1ERA(S) AC28ES1ERA(S) AC18CS1ERA(S) AC60FS1ERA(S) AC36ES1ERA(S) AC24CS1ERA(S) Ultra thin unit, only thick 199mm (Only for AC12~24CS1ERA(S)) The convertible unit adopts a double drain pan design. The unit body is only thin, only 199mm. It is beautiful, elegant and and space saving.
  • Page 56 Super Match Easy taken out filter The filter can be easily taken out, you need not take down the unit or open the air inlet grill, and realize convenient cleaning working Only for units AC28-AC60 Automatic Control of Airflow Direction The airflow direction can be controlled in 5 steps from up to down and from left to right automactically, more selectable, more flexible.
  • Page 57: Specification

    Super Match 2.2 Specification Item Model AC12CS1ERA(S)/1U12BS3ERA Function cooling heating Capacity 3.5(0.9~4.5) 3.9(1~4.8) Sensible heat ratio 0.71 Total power input 1.03(0.28~1.8) 1.02(0.28~1.8) Max. power input 1800 1800 EER or COP 3.39 3.81 Dehumidifying capacity 10‐³×m³/h Power cable H05RN-F 4G 4.0mm2 1PH, 220-230V~, 50/60Hz Power source N, V, Hz...
  • Page 58 Super Match Item Model AC18CS1ERA(S) Function cooling heating Capacity 5(1.8~5.8) 5.5(2~6.5) Sensible heat ratio 0.71 Total power input 1.53(0.55~2) 1.48(0.6~2) Max. power input 2000 2000 EER or COP 3.26 3.72 Dehumidifying capacity 10‐³×m³/h Power cable H05RN-F 4G 4.0mm2 Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current...
  • Page 59 Super Match Item Model AC24CS1ERA(S)/1U24GS1ERA Function cooling heating Capacity 6.5(2~7.3) 7.1(2.5~8.0) Sensible heat ratio 0.72 Total power input 2.16(0.5~2.6) 2.08(0.5~2.6) Max. power input 2600 2600 EER or COP 3.01 3.41 Dehumidifying capacity 10‐³×m³/h Power cable H05RN-F 4G 6.0mm2 Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current...
  • Page 60 Super Match Item Model AC28ES1ERA(S)/1U28HS1ERA(S) Function cooling heating Capacity 8.5(2.1-10.0) 9.5(2.2-10.5) Sensible heat ratio Total power input 2.355(0.5-4.2) 2.632(0.5-4.2) Max. power input 4200 4200 EER or COP 3.61 3.61 Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A 10.2(2.2-18.5)/18.5...
  • Page 61 Super Match Item Model AC28ES1ERA(S)/1U28GS2ERA(S) Function cooling heating Capacity 8.3(2.1-10.0) 9.0(2.2-10.5) Sensible heat ratio 0.74 Total power input 2.57(0.5~4.2) 2.43(0.5~4.2) Max. power input 4200 4200 EER or COP 3.23 3.71 Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A...
  • Page 62 Super Match Item Model AC36ES1ERA(S)/1U36HS1ERA(S) Function cooling heating Capacity 10(2.2-11) 10.6(2.2-11.8) Sensible heat ratio Total power input 2.77(0.5-4.3) 2.94(0.5-4.3) Max. power input 4300 4300 EER or COP 3.61 3.61 Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A 10.9(2.2-19.3)/19.3...
  • Page 63 Super Match Item Model AC48FS1ERA(S)/1U48IS1EAB(S) Function cooling heating Capacity 14.5 15.5 Sensible heat ratio 0.74 Total power input 4.51 4.28 Max. power input 6500 6500 EER or COP 3.22(A) 3.62(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50/60 Running /Max.Running current A / A...
  • Page 64 Super Match Item Model AC48FS1ERA(S)/1U48IS1ERB(S) Function cooling heating Capacity 14(6.0-15) 15(6.0~17) Sensible heat ratio 0.74 Total power input 4.34(2.0---6.0) 4.14(2.0---6.0) Max. power input 6000 6000 EER or COP 3.23(A) 3.62(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A...
  • Page 65 Super Match Item Model AC48FS1ERA(S)/1U48LS1EAB(S) Function cooling heating Capacity 14.1 15.2 Sensible heat ratio 0.74 Total power input 4.67 Max. power input 6500 6500 EER or COP 3.02(B) 3.23(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1N~,220~230, 50/60 Running /Max.Running current A / A 7.8/10.5...
  • Page 66 Super Match Item Model AC48FS1ERA(S)/1U48LS1ERA(S) Function cooling heating Capacity 12.5(6.0-14.5) 14.1(6.0~16.5) Sensible heat ratio 0.74 Total power input 3.89(2.0---6.0) 4.10(2.0---6.0) Max. power input 5600 5600 EER or COP 3.21(A) 3.44(B) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A...
  • Page 67 Super Match Item Model AC48FS1ERA(S)/1U48LS1ERB(S) Function cooling heating Capacity 12.5(6.0-14.5) 14.1(6.0~16.5) Sensible heat ratio 0.74 Total power input 3.89(2.0---6.0) 4.10(2.0---6.0) Max. power input 6000 6000 EER or COP 3.21(A) 3.44(B) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 3, 380~400, 50 Running /Max.Running current A / A...
  • Page 68 Super Match Item Model AC60FS1ERA(S)/1U60IS1EAB(S) Function cooling heating Capacity 15.5 16.8 Sensible heat ratio 0.74 Total power input 5.13 5.23 Max. power input 6500 6500 EER or COP 3.02(B) 3.21(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50/60 Running /Max.Running current A / A...
  • Page 69 Super Match Item Model AC60FS1ERA(S)/1U60IS1ERB(S) Function cooling heating Capacity 15.5(4.0~16.0) 16.5(4.0~18.0) Sensible heat ratio 0.74 Total power input 5.13(2.0---6.5) 4.83(2.0----6.5) Max. power input 6500 6500 EER or COP 3.02(B) 3.42(B) Dehumidifying capacity 10‐³×m³/h Power cable 1, 220 ~ 230, 50/60 Power source N, V, Hz Running /Max.Running current...
  • Page 70 Super Match Item Model AC60FS1ERA(S)/1U60IS2ERB(S) Function cooling heating Capacity 14(6.0-15) 15(6.0~17) Sensible heat ratio 0.74 Total power input 4.34(2.0---6.0) 4.14(2.0---6.0) Max. power input 6000 6000 EER or COP 3.23(A) 3.62(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50/60 Running /Max.Running current A / A...
  • Page 71 Super Match Item Model AC60FS1ERA(S)/1U60IS2EAB(S) Function cooling heating Capacity 14.5 15.5 Sensible heat ratio 0.74 Total power input 4.51 4.28 Max. power input 6500 6500 EER or COP 3.22(A) 3.62(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50/60 Running /Max.Running current A / A...
  • Page 72: Piping Diagram

    Super Match 2.3 Piping diagram Liquid pipe Gas pipe Filter Filter Indoor heat exchanger...
  • Page 73: Wiring Diagram

    Super Match 2.4 Wiring diagram AC12CS1ERA(S) AC18CS1ERA(S) AC24CS1ERA(S)
  • Page 74 Super Match AC28ES1ERA(S) AC36ES1ERA(S) AC48FS1ERA(S) AC60FS1ERA(S)
  • Page 75: Air Velocity And Temperature Distribution

    Super Match 2.5 Air velocity and temperature distribution AC12CS1ERA(S) AC18CS1ERA(S) AC24CS1ERA(S) AC28ES1ERA(S) AC36ES1ERA(S) A) On the floor a. Cooling / Air Velocity Distribution Coolin g Blow y angle:2 5 Ai r Velocit y Distributio n 2.4m 0.5m/s 1.0m/s 1.5m/s 5.5 m b.
  • Page 76 Super Match c. Heating / Air Velocity Distribution Heating Blowy angle:5 Air velocity Distribution 2.4m 0.5m/s 1.0m/s 1.5m/s 5.5m d. Heating / Temperature Distribution Heating Blowy angle:5 Temperature Distribution 2.4m 5.5m...
  • Page 77 Super Match B) Ceiling a. Cooling / Air Velocity Distribution Cooling Blowy angle:25 Air Velocity Distribution 2.4m 1.5m/s 1.0m/s 0.5m/s 5.5m b. Cooling / Temperature Distribution Cooling Blowy angle:25 Temperature Distribution 2.4m...
  • Page 78 Super Match c. Heating / Air Velocity Distribution Heating Blowy angle:65 Air velocity Distribution 2.4m 1.5m/s 1.0m/s 0.5m/s 5.5 m d. Heating / Temperature Distribution Heating Blowy angle:65 Temperature Distribution 2.4m 5.5 m...
  • Page 79 Super Match AC48FS1ERA(S) AC60FS1ERA(S) A) On the floor a. Cooling / Air Velocity Distribution Cooling Blowy angle:25 Air Velocity Distribution 2.4m 0.5m/s 1.0m/s 1.5m/s 10 m b. Cooling / Temperature Distribution Cooling Blowy angle:25 Temperature Distribution 2.4m 10 m...
  • Page 80 Super Match c. Heating / Air Velocity Distribution Heating Blowy angle:5 Air velocity Distribution 2.4m 0.5m/s 1.0m/s 1.5m/s d. Heating / Temperature Distribution Heating Blowy angle:5 Temperature Distribution 2.4m...
  • Page 81 Super Match B) Ceiling a. Cooling / Air Velocity Distribution Cooling Blowy angle:25 Air Velocity Distribution 2.4m 1.5m/s 1.0m/s 0.5m/s b. Cooling / Temperature Distribution Cooling Blowy angle:25 Temperature Distribution 2.4m...
  • Page 82 Super Match c. Heating / Air Velocity Distribution Heating Blowy angle:65 Air velocity Distribution 2.4m 1.5m/s 1.0m/s 0.5m/s 10 m d. Heating / Temperature Distribution Heating Blowy angle:65 Temperature Distribution 2.4m 10 m...
  • Page 83: Sound Pressure Level

    Super Match 2.6 Sound Pressure Level (1)Testing illustrate: (2)Testing condition: a. Unit running in the nominal condition b. Test in the semi-anechoic chamber c. Noise level varies from the actual factors such as room structure, etc. (3) Octave band level...
  • Page 84 Super Match...
  • Page 85 Super Match...
  • Page 86 Super Match...
  • Page 87: Installation

    Super Match Installation For AC12~24CS1ERA(S) Please ask the dealer or specialist to install, never try by the users themselves. After the installation please be sure of the following conditions. WARNING ■ Please call dealer to install the air-conditioner. Incorrect installation may cause water leaking, shock and fire hazard.
  • Page 88 Super Match SELECTING THE MOUNTING POSITION Decide the mounting position with the customer as follows: (1) Install the indoor unit level on a strong wall, floor, ceiling which is not subject to vibration. (2) The inlet and outlet ports should not be obstructed.The air should be able to blow all over the room. (3) Install the unit near an electric outlet or special branch circuit.
  • Page 89 Super Match PREPARING INDOOR UNIT INSTALLATION Remove the intake grill Open the intake grill and remove the three or four or six screws. Note: The main unit can be wired before the indoor unit is installed. Select the most appropriate installation order. A.FLOOR CONSOLE TYPE 1.
  • Page 90 Super Match Be sure to arrange the drain hose correctly so that it is leveled lower than the drain hose connecting port of the indoor unit. (Fig.7) CAUTION Do not install the unit drain hose side is too high. Height A should be less than 5 mm.(Fig.8) B.
  • Page 91 Super Match 3. Installing brackets Install the brackets with nuts, washers and spring washers. (Fig.14) Reset the hex bolts as shown in Fig.15. Apply the indoor unit to the brackets. (Fig.16) Now, securely tighten the hex bolts in both sides. 5.
  • Page 92 Super Match CONNECTING THE PIPING Table 1 1. Flare processing Pipe Flare nut (1) Cut the connection pipe with pipe cutters so that the pipe is not Small (width across deformed. Small pipe flats 22mm) (2) Holding the pipe downward so that cuttings cannot enter the pipe, remove the burrs.
  • Page 93 Super Match CAUTION ■ Match the terminal block numbers and connection cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the electric parts. ■ Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire. ■...
  • Page 94 Super Match CAUTION (1) The power source capacity must be the sum of the room air conditioner current and the current of other electrical appliances. When the current contracted capacity is insufficient, change the contracted capacity. (2) When the voltage is too low and the air conditioner is difficult to start, contact the power company the voltage raised.
  • Page 95 Super Match For AC28~AC60 SELECTING THE MOUNTING POSITION WARNING ■ Install at a place that can withstand the weight of the indoor unit and install it positively so that the unit will not topple or fall. CAUTION ■ Do not install the unit where there is the danger of combustible gas leakage. ■...
  • Page 96 Super Match INSTALLING THE INDOOR UNIT Connection pipe requirement Maximum height Diameter Model Maximum length (between indoor and Liquid side Gas side outdoor) AC28ES1ERA(S) 9.52mm 15.88mm AC36ES1ERA(S) AC48FS1ERA(S) 9.52mm 19.05mm AC60FS1ERA(S) Install the room air conditioner as follows 1. Remove the intake grill and side cover (1) Remove the Air filters (2) Remove the intake grilles (3) Remove the Side cover (Right and left side)
  • Page 97 Super Match 3. Drilling the holes and attaching the suspension bolts (1) Drill 25mm holes at the suspension-bolt locations. The two special nuts are provided with the unit. The M1O nut must be obtained locally. (2) Install the bolts, then temporarily attach Special nuts A and B and a normal M1O nut to each bolt.
  • Page 98 Super Match INSTALLING THE DRAIN HOSE ■ Install the drain pipe with downward gradient (1/50 to 1/100) and so there are no rises or traps in the pipe. ■ Use general hard polyvinyl chloride pipe (VP25) (outside diameter 38 mm) ■...
  • Page 99 Super Match B.For strand wiring (1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to about 3/8”(1Omm) to expose the solid wire. (2) Using a screwdriver, remove the terminal screw(s) on the terminal board. (3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
  • Page 100 Super Match Wiring diagram AC28ES1ERA(S) AC36ES1ERA(S) AC48FS1ERA(S) AC60FS1ERA(S) WARNING ■ The power cable and connecting cable are self-provided. ■ Always use a special branch circuit and install a special receptacle to supply power to the room air conditioner. ■ Use a circuit breaker and receptacle matched to the capacity of the room air conditioner. ■...
  • Page 101: Duct Indoor Type

    Super Match 3. Duct indoor type 3.1 Features ................................100 3.2 Specification ..............................103 3.3 Dimension ...............................143 3.4 Piping diagram ..............................146 3.5 Wiring diagram ..............................147 3.6 Air velocity and temperature distribution ......................152 3.7 Maintenance ..............................159 3.8 Installation ...............................167...
  • Page 102: Features

    Super Match 3.1 Features AD12~18MS1ERA AD09~12SS1ERA(N)(P) AD18~24SS1ERA(N)(P) AD12~18MS1ERA(D) AD09~12SS1ERA(N) AD18~24SS1ERA(N) AD24~28MS2ERA AD09~12SS1ERA AD18~24SS1ERA AD24~28MS2ERA(S) AD28MS2ERA(S)(D) AD24MS1ERA AD09LS1ERA AD18LS1ERA AD24MS1ERA(D) AD12LS1ERA AD24LS1ERA AD28NS1ERA(S) AD48HS1ERA(S) AD36NS1ERA(S) AD60HS1ERA(S) AD48NS1ERA(S)
  • Page 103 Super Match Super thin design Super thin design make all the models only 185mm height, 185mm which is super slim and most advanced in the industry, this feature will bring slimest ceiling drop. Super Slient New fan design, the shape and large diameter is designed for silent, optimize the air path, with DC fan motor, brings minimum 21dB(A) super quiet performance.
  • Page 104 Super Match Multi-mode for installation The indoor unit can be installed with an air return duct or without an air return duct according to the installation need Embedded Hanging the Ceiling from the Ceiling Hanging Embedded from the the Ceiling Ceiling Different ESP Choice There are low/medium/high static pressure duct models fit for different design application.
  • Page 105: Specification

    Super Match 3.2 Specification Item Model AD09SS1ERA Function —— Cooling Heating Capacity 2700 2800 Sensible heat ratio 0.71 Dehumidifying capacity 10-³xm³/h Power supply 1PH, 220-230V~, 50/60Hz Type × Number —— centrifugal*1 Speed(H-M-L) r/min 850/750/650 Fan motor output/input power 11/15 Air-flows (H/M/L) m³/h 530/460/390 Type / Diameter...
  • Page 106 Super Match AD09SS1ERA(N) Item Model Cooling Heating Function —— capacity 2700 2800 0.71 sensible heat ratio Dehumidifying capacity 10-³xm³/h 1PH, 220-230V~, 50Hz power supply centrifugal*1 Type × Number —— 850/750/650 Speed(H-M-L) r/min Fan motor output/input power 11/15 Air-flows (H/M/L) 530/460/390 m³/h inner grooved pipe/¢...
  • Page 107 Super Match Item Model AD09SS1ERA(N)(P) Function —— Cooling Heating capacity 2700 2800 sensible heat ratio 0.71 Dehumidifying capacity 10-³xm³/h power supply 1PH, 220-230V~, 50Hz Type × Number —— centrifugal*1 Speed(H-M-L) r/min 850/750/650 Fan motor output/input power 11/15 Air-flows (H/M/L) m³/h 530/460/390 Type / Diameter inner grooved pipe/¢...
  • Page 108 Super Match Item Model AD09LS1ERA Function —— Cooling Heating Capacity 2500 2900 Sensible heat ratio 0.71 Dehumidifying capacity 10-³xm³/h 1.0/1.5 Power supply 1PH, 220-230V~, 50/60Hz Type × Number —— centrifugal*1 Speed(H-M-L) r/min 1230/1120/1030/900±40 Fan motor output/input power 27/64 Air-flows (H/M/L) m³/h 550/450/400 Type / Diameter...
  • Page 109 Super Match Item Model AD12SS1ERA Function Cooling Heating 3.50(0.9 ~ 4.5) 4.00(1 ~ 4.8) Capacity Sensible heat ratio 0.71 1.03(0.28 ~ 1.8) 1.07(0.28 ~ 1.8) Total power input Max. power input 1800 1800 EER or COP 3.39 3.73 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 4.0mm...
  • Page 110 Super Match Item Model AD12SS1ERA(N)/1U12BS3ERA Function cooling heating 3.50(0.9 ~ 4.5) 4.00(1 ~ 4.8) Capacity Sensible heat ratio 0.71 1.03(0.28 ~ 1.8) 1.07(0.28 ~ 1.8) Total power input 1800 1800 Max. power input EER or COP 3.39 3.73 Dehumidifying capacity 10-³×m³/h Power cable H05RN-F 4G 4.0mm...
  • Page 111 Super Match Item Model AD12SS1ERA(N)(P)/1U12BS3ERA Function cooling heating 3.50(0.9 ~ 4.5) 4.00(1 ~ 4.8) Capacity Sensible heat ratio 0.71 1.03(0.28 ~ 1.8) 1.07(0.28 ~ 1.8) Total power input 1800 1800 Max. power input EER or COP 3.39 3.73 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 4.0mm2...
  • Page 112 Super Match Item Model AD12MS1ERA/1U12BS3ERA Function cooling heating Capacity 3.50(0.9~4.5) 4.00(1~4.8) Sensible heat ratio Total power input 1.08(0.28~1.8) 1.08(0.28~1.8) 1800 1800 Max. power input EER or COP 3.23 3.71 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 4.0mm2 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 113 Super Match Item Model AD12MS1ERA(D)/1U12BS3ERA Function cooling heating Capacity 3.50(0.9~4.5) 4.00(1~4.8) Sensible heat ratio Total power input 1.08(0.28~1.8) 1.08(0.28~1.8) 1800 1800 Max. power input EER or COP 3.23 3.71 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 4.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 114 Super Match Item Model AD18SS1ERA Function cooling heating Capacity 5.0(1.8~6) 5.5(2~6.2) Sensible heat ratio 0.73 Total power input 1.53(0.55~2.1) 1.47(0.6~2.1) 2100 2100 Max. power input EER or COP 3.26 3.73 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 4.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 115 Super Match Item Model AD18SS1ERA(N)/1U18FS2ERA(S) Function cooling heating Capacity 5.0(1.8~6) 5.5(2~6.2) Sensible heat ratio 0.73 Total power input 1.53(0.55~2.1) 1.47(0.6~2.1) 2100 2100 Max. power input EER or COP 3.26 3.73 Dehumidifying capacity 10-³×m³/h Power cable H05RN-F 4G 4.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 116 Super Match Item Model AD18SS1ERA(N)(P)/1U18FS2ERA(S) Function cooling heating Capacity 5.0(1.8~6) 5.5(2~6.2) Sensible heat ratio 0.73 Total power input 1.53(0.55~2.1) 1.47(0.6~2.1) 2100 2100 Max. power input EER or COP 3.26 3.73 Dehumidifying capacity 10-³×m³/h Power cable H05RN-F 4G 4.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 117 Super Match Item Model AD18LS1ERA Function cooling heating Capacity 5.0(1.8~6) 5.5(2~6.2) Sensible heat ratio 0.73 Total power input 1.53(0.55~2.1) 1.47(0.6~2.1) 2100 2100 Max. power input EER or COP 3.26 3.73 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 4.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 118 Super Match Item Model AD18MS1ERA/1U18FS2ERA(S) Function cooling heating Capacity 5.0(1.8~6) 5.5(2~6.2) Sensible heat ratio 0.73 Total power input 1.55(0.55~2.0) 1.48(0.6~2.0) 2000 2000 Max. power input EER or COP 3.23 3.71 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 4.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 119 Super Match Item Model AD18MS1ERA(D)/1U18FS2ERA(S) Function cooling heating Capacity 5.0(1.8~6) 5.5(2~6.2) Sensible heat ratio 0.73 Total power input 1.55(0.55~2.0) 1.48(0.6~2.0) 2000 2000 Max. power input EER or COP 3.23 3.71 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 4.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 120 Super Match Item Model AD24SS1ERA/1U24GS1ERA Function cooling heating Capacity 7.1(2~7.6) 7.1(3~8.3) Sensible heat ratio 0.74 Total power input 2.19(0.6~2.6) 1.91(0.6~2.6) 2600 2600 Max. power input EER or COP 3.24 3.72 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 6.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 121 Super Match Item Model AD24SS1ERA(N)/1U24GS1ERA Function cooling heating Capacity 7.1(2~7.6) 7.1(3~8.3) Sensible heat ratio 0.74 Total power input 2.19(0.6~2.6) 1.91(0.6~2.6) 2600 2600 Max. power input EER or COP 3.24 3.72 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 6.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 122 Super Match Item Model AD24SS1ERA(N)(P)/1U24GS1ERA Function cooling heating Capacity 7.1(2~7.6) 7.1(3~8.3) Sensible heat ratio 0.74 Total power input 2.19(0.6~2.6) 1.91(0.6~2.6) 2600 2600 Max. power input EER or COP 3.24 3.72 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 6.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 123 Super Match Item Model AD24LS1ERA/1U24GS1ERA Function cooling heating Capacity 6.8(2~7.6) 7.1(3~8.3) Sensible heat ratio 0.72 Total power input 2.10(0.6~2.6) 1.91(0.6~2.6) Max. power input 2600 2600 EER or COP 3.24 3.72 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 6.0mm2 Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current...
  • Page 124 Super Match Item Model AD24MS1ERA/1U24GS1ERA Function cooling heating Capacity 7.1(2.0~8.2) 7.5(2.5~8.5) Sensible heat ratio 0.74 Total power input 2.19(0.6~2.6) 2.02(0.6~2.6) 2600 2600 Max. power input EER or COP 3.23 3.71 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 6.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 125 Super Match Item Model AD24MS2ERA/1U24GS1ERA Function cooling heating Capacity 7.1(2.0~8.2) 8.0(2.5~8.5) Sensible heat ratio 0.74 Total power input 2.19(0.6~2.6) 2.16(0.6~2.6) 2600 2600 Max. power input EER or COP 3.23 3.71 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 6.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 126 Super Match Item Model AD24MS2ERA(D)/1U24GS1ERA Function cooling heating Capacity 7.1(2.0~8.2) 8.0(2.5~8.5) Sensible heat ratio 0.74 Total power input 2.19(0.6~2.6) 2.16(0.6~2.6) 2600 2600 Max. power input EER or COP 3.23 3.71 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 6.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 127 Super Match Item Model AD28MS2ERA(S)/1U28GS2ERA(S) Function cooling heating Capacity 8(2.5~8.0) 9.0(3.0~9.5) Sensible heat ratio 0.74 Total power input 2.48(0.6~3.1) 2.42(0.6~3.1) 3100 3100 Max. power input EER or COP 3.23 3.71 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 6.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 128 Super Match Item Model AD28MS2ERA(S)(D)/1U28GS2ERA(S) Function cooling heating Capacity 8(2.5~8.0) 9.0(3.0~9.5) Sensible heat ratio 0.74 Total power input 2.48(0.6~3.1) 2.42(0.6~3.1) 3100 3100 Max. power input EER or COP 3.23 3.71 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 6.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 129 Super Match Item Model AD28NS1ERA(S)/1U28HS1ERA(S) Function Cooling Heating Capacity 8.5(2.1-9.8) 9.5(2.2-10.5) Sensible heat ratio Total power input 2.648(0.5-4.2) 2.631(0.5-4.2) Max. power input 4200 4200 EER or COP 3.21 3.61 Dehumidifying capacity 10‐³×m³/h Power cable H05RN-F 4G 6.0mm Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A...
  • Page 130 Super Match Item Model AD28NS1ERA(S)/1U28GS2ERA(S) Function cooling heating Capacity 8.0(2.1-9.8) 9.0(2.2-10) Sensible heat ratio 0.74 Total power input 2.648(0.5-4.2) 2.631(0.5-4.2) 4200 4200 Max. power input EER or COP 3.21 3.61 Dehumidifying capacity ³×m³/h Power cable H05RN-F 4G 6.0mm 1PH, 220-230V~, 50/60Hz Power source N, V, Hz Running /Max.Running current...
  • Page 131 Super Match Item Model AD36NS1ERA(S)/1U36HS1ERA(S) Function cooling heating Capacity 10(2.2-11) 11(2.2-12) Sensible heat ratio Total power input 3.29(0.5-4.3) 3.05(0.5-4.3) Max. power input 4300 4300 EER or COP 3.01 3.61 Dehumidifying capacity 10‐³×m³/h Power cable H05RN-F 4G 6.0mm Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A...
  • Page 132 Super Match Item Model AD48HS1ERA(S)/1U48IS1EAB(S) Function cooling heating Capacity 14.1 15.5 Sensible heat ratio 0.74 Total power input 4.62 4.27 Max. power input 6500 6500 EER or COP 3.05(B) 3.63(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50/60 Running /Max.Running current A / A...
  • Page 133 Super Match Item Model AD48NS1ERA(S)/1U48IS1EAB(S) Function cooling heating Capacity 14.1 15.2 Sensible heat ratio 0.74 Total power input 4.66 4.45 Max. power input 6500 6500 EER or COP 3.03(B) 3.42(B) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50/60 Running /Max.Running current A / A...
  • Page 134 Super Match Item Model AD48NS1ERA(S)/1U48IS1ERB(S) Function cooling heating Capacity 13.6(6.0-15) 15(6.0~17) Sensible heat ratio 0.74 Total power input 4.22(2.0---6.0) 4.08(2.0---6.0) Max. power input 6000 6000 EER or COP 3.22(A) 3.68(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50Hz Running /Max.Running current A / A...
  • Page 135 Super Match Item Model AD48HS1ERA(S)/1U48IS1ERB(S) Function cooling heating Capacity 13.6(6.0-15) 15.5(6.0~17.5) Sensible heat ratio 0.74 Total power input 4.22(2.0---6.0) 4.21(2.0---6.0) Max. power input 6000 6000 EER or COP 3.22(A) 3.68(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A...
  • Page 136 Super Match Item Model AD48HS1ERA(S)/1U48LS1EAB(S) Function cooling heating Capacity 13.5 Sensible heat ratio 0.72 Total power input Max. power input 6500 6500 EER or COP 2.84(C) 3.41(B) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1N~,220~230, 50/60 Running /Max.Running current A / A 7.7/10.5 7.4/10.5...
  • Page 137 Super Match Item Model AD48NS1ERA(S)/1U48LS1ERA(S) Function cooling heating Capacity 12.1(6.0-14.5) 14.1(6.0~16.5) Sensible heat ratio 0.74 Total power input 4.3(2.0---6.0) 4.39(2.0---6.0) Max. power input 5600 5600 EER or COP 2.81(C) 3.21(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A...
  • Page 138 Super Match Item Model AD48HS1ERA(S)/1U48LS1ERA(S) Function cooling heating Capacity 12.5(6.0-14.5) 14.1(6.0~16.5) Sensible heat ratio 0.74 Total power input 4.4(2.0---6.0) 3.9(2.0---6.0) Max. power input 5600 5600 EER or COP 2.84(C) 3.62(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A...
  • Page 139 Super Match Item Model AD48NS1ERA(S)/1U48LS1ERB(S) Function cooling heating Capacity 12.1(6.0-14.5) 14.1(6.0~16.5) Sensible heat ratio 0.74 Total power input 4.3(2.0---5.8) 4.39(2.0---5.8) Max. power input 6000 6000 EER or COP 2.81(C) 3.21(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 3, 380~400, 50 Running /Max.Running current A / A...
  • Page 140 Super Match Item Model AD48HS1ERA(S)/1U48LS1ERB(S) Function cooling heating Capacity 12.5(6.0-14.5) 14.1(6.0~16.5) Sensible heat ratio 0.74 Total power input 4.4(2.0---6.0) 3.9(2.0---6.0) Max. power input 6000 6000 EER or COP 2.84(C) 3.62(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 3N~, 380-400V, 50Hz Running /Max.Running current A / A...
  • Page 141 Super Match Item Model AD60HS1ERA(S)/1U60IS1EAB(S) Function cooling heating Capacity 16.0 17.2 Sensible heat ratio 0.76 Total power input 5.29 4.76 Max. power input 6500 6500 EER or COP 3.02(C) 3.61(A) Dehumidifying capacity 10‐³×m³/h Power cable H05RN-F 4G 4.0mm2 Power source N, V, Hz 1, 220~230, 50/60 Running /Max.Running current...
  • Page 142 Super Match Item Model AD60HS1ERA(S)/1U60IS1ERB(S) Function cooling heating Capacity 15.5(4.0~16.0) 16.5(4.0~18.0) Sensible heat ratio 0.76 Total power input 5.13(2.0---6.5) 4.57(2.0----6.5) Max. power input 6500 6500 EER or COP 3.02(C) 3.61(A) Dehumidifying capacity 10‐³×m³/h Power cable H05RN-F 4G 4.0mm2 1, 220 ~ 230, 50/60 Power source N, V, Hz Running /Max.Running current...
  • Page 143 Super Match Item Model AD60HS1ERA(S)/1U60IS2ERB(S) Function cooling heating Capacity 13.6(6.0-15) 15.5(6.0~17.5) Sensible heat ratio 0.74 Total power input 4.22(2.0---6.0) 4.21(2.0---6.0) Max. power input 6000 6000 EER or COP 3.22(A) 3.68(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A...
  • Page 144 Super Match Item Model AD60HS1ERA(S)/1U60IS2EAB(S) Function cooling heating Capacity Sensible heat ratio 0.74 Total power input 4.92 4.41 Max. power input 6500 6500 EER or COP 3.05(B) 3.63(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50/60Hz Running /Max.Running current A / A 8.6/10.5...
  • Page 145: Dimension

    Super Match 3.3 Dimension AD12MS1ERA AD12MS1ERA(D) 595.5 Note: The cushion pasted in the bottom plate isn't included in the thickness data. AD18MS1ERA AD18MS1ERA(D) AD24MS2ERA AD24MS2ERA(D) AD28MS2ERA(S) AD28MS2ERA(S)(D) 595.5 Note: The cushion pasted in the bottom plate isn't included in the thickness data.
  • Page 146 Super Match AD24MS1ERA AD24MS1ERA(D)
  • Page 147 Super Match AD28NS1ERA(S) AD36NS1ERA(S) AD48NS1ERA(S) fresh air hole drain pipe( O.D38 ) liquid pipe gas pipe air return hole AD48HS1ERA(S) AD60HS1ERA(S)
  • Page 148: Piping Diagram

    Super Match 3.4 Piping diagram Liquid pipe Gas pipe Filter Filter Indoor heat exchanger...
  • Page 149: Wiring Diagram

    Super Match 3.5 Wiring diagram AD09~24SS1ERA AD09~24SS1ERA(N) AD09~24SS1ERA(N)(P)
  • Page 150 Super Match AD12MS1ERA AD18MS1ERA AD12MS1ERA(D) AD18MS1ERA(D) AD24MS2ERA AD24MS2ERA(D) AD28MS2ERA(S) AD28MS2ERA(S)(D)
  • Page 151 Super Match AD09LS1ERA AD12LS1ERA AD18LS1ERA AD24LS1ERA AD24MS1ERA AD24MS1ERA(D)
  • Page 152 Super Match AD28NS1ERA(S) AD36NS1ERA(S) AD48NS1ERA(S)
  • Page 153 Super Match AD48HS1ERA (S) AD60HS1ERA(S)
  • Page 154: Air Velocity And Temperature Distribution

    Super Match 3.6 Air velocity and temperature distribution AD09SS1ERA AD09SS1ERA(N) AD09SS1ERA(N)(P) AIRFLOW AND STATIC PRESSURE CHART 30 Pa 30 Pa 20 Pa 20 Pa 10 Pa 10 Pa 0 Pa 0 Pa static pressure (Pa) static pressure (Pa) AD12SS1ERA AD12SS1ERA(N) AD12SS1ERA(N)(P) AIRFLOW AND STATIC PRESSURE CHART 30 Pa 20 Pa...
  • Page 155 Super Match AD18SS1ERA AD18SS1ERA(N) AD18SS1ERA(N)(P) AIRFLOW AND STATIC PRESSURE CHART 30 Pa 30 Pa 20 Pa 20 Pa 10 Pa 10 Pa 0 Pa 0 Pa static pressure (Pa) static pressure (Pa) AD24SS1ERA AD24SS1ERA(N) AD24SS1ERA(N)(P) AIRFLOW AND STATIC PRESSURE CHART 1200 1200 1000...
  • Page 156 Super Match AD09LS1ERA/AD12LS1ERA AIR FLOW AND STATIC PRESSURE CHART 20Pa 15Pa 10Pa static pressure (Pa) AD18LS1ERA AIRFLOW AND STATIC PRESSURE CHART 20Pa 15Pa 10Pa static pressure (Pa)
  • Page 157 Super Match AD24LS1ERA Air flow and static pressure curves for AD24LS1ERA 1400 1350 1300 1250 1200 10pa 1150 20pa 1100 30pa 1050 40pa 1000 50pa indoor 27/19 indoor 20/14.5 outdoor 35/24 outdoor 7/6 indoor/outdoor temperature Air flow and static pressure chart---AD12MS1ERA AD12MS1ERA(D) Static pressure (Pa)
  • Page 158 Super Match Air flow and static pressure chart---AD18MS1ERA AD18MS1ERA(D) Static pressure (Pa) AD48NSIERA(S) air flow and static pressure curves 2400 2200 2000 super high 1800 high 1600 1400 1200 1000 static pressure Pa External static AD24MS1ERA AD24MS1ERA(D) external static pressure curves pressure(Pa) high speed m id speed...
  • Page 159 Super Match Air flow and static pressure chart AD24MS2ERA AD24MS2ERA(D) 1300 1200 1100 1000 10pa 20pa 30pa 40pa 50pa 60pa 70pa static pressure AD28MS2ERA(S) AD28MS2ERA(S)(D)External static pressure curves 1400 1300 1200 1100 high 1000 10Pa 30Pa 50Pa 70Pa AD28/36NS1E R A (S) external static pressure curves 2400 2300...
  • Page 160 Super Match AD48NSIERA(S) air flow and static pressure curves 2400 2200 2000 super high 1800 high 1600 1400 1200 1000 static pressure Pa External static pressure ( Pa ) external static pressure curves AD48/ 60HS1ERA(S) high speed m id speed low speed Air flow (...
  • Page 161: Maintenance

    Super Match 3.7 Sound pressure level (1)Testing illustrate: (2) Testing condition: a: Unit running in the normal condition b: Test in the semi-anechoic chamber c: Noise level varies from the actual factors such as room structure, etc. (3)Octave band level:...
  • Page 162 Super Match...
  • Page 163 Super Match...
  • Page 164 Super Match...
  • Page 165 Super Match...
  • Page 166 Super Match...
  • Page 167 Super Match...
  • Page 168 Super Match...
  • Page 169: Installation

    Super Match Installation For AD09~24LS1ERA AD09~24SS1ERA AD09~24SS1ERA(N) AD09~24SS1ERA(N)(P) The machine is adaptive in following situation 1. Applicable ambient temperature range: Max. DB/WB 32/23°C Indoor temperature Min. DB/WB 18/14°C Cooling Max. DB/WB 46/24°C Outdoor temperature Min. DB/WB 18°C Max. DB/WB 27°C Indoor temperature Min.
  • Page 170 Super Match Installation Procedure Selecting the mounting position to install the indoor units ■ Select suitable places where the outlet air can be sent to the entire room, and convenient to lay out the connection pipe, connection wire and the drainage pipe to outdoor. ■...
  • Page 171 Super Match ■ Each of the air sending duct and air return duct shall be fixed on the prefabricated panel of the floor by the iron bracket. The recommended distance between the edge of the air return duct and the wall is over 150mm. ■...
  • Page 172 Super Match Installing the suspension screw Use M8 or M10 suspension screws (4, prepared in the field) (when the suspension screw height exceeds 0.9m, M10 size is the only choice). These screws shall be installed as follows with space adapting to air conditioner overall dimensions according to the original building structures.
  • Page 173 Super Match Connection of refrigerant pipe Connecting pipe Installing torque Conduct flared connection work to connect all refrigerant pipes. O.D.(mm) (N-m) ■ The connection of indoor unit pipes must use double spanners. Ø6.35 11.8 (1.2kgf·m) ■ The installing torque shall be as given in the following table. Ø9.52 24.5 (2.5 kgf·m) Double-spanner...
  • Page 174 Super Match Hose Drain pipe size: (3/4”) PVC pipe The hose is used for adjusting the off-center and angle of the rigid PVC pipe. ■ Directly stretch the hose to install without making any deformation. ■ The soft end of the hose must be fastened with a hose clamp. ■...
  • Page 175 Super Match There are three methods to connection wire controller and the indoor units: A. One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the wire controller and the master unit (the indoor unit connected with wire controller directly), the others connect with the master unit through 2 pieces of polar wire(3 pieces for model AD**SS1ERA, AD**SS1ERA(N), AD**SS1ERA(N)(P), and the bridge CN22 CN23 on slave units PCB should be cut off).
  • Page 176 Super Match Safety Precautions AD12MS1ERA AD12MS1ERA(D) AD18MS1ERA AD18MS1ERA(D) AD24MS1ERA AD24MS1ERA(D) AD24MS2ERA AD24MS2ERA(D) AD28MS2ERA(S) AD28MS2ERA(S)(D) AD28NS1ERA(S) AD36NS1ERA(S) AD48NS1ERA(S) The machine is adaptive in following situation 1. Applicable ambient temperature range: Max. DB/WB 32/23°C Indoor temperature Min. DB/WB 18/14°C Cooling Max. DB/WB 46/24°C Outdoor temperature Min.
  • Page 177 Super Match Parts and Functions AD12MS1ERA AD12MS1ERA (D) Electrical components Case Electrical components Case Air outlet frame Air outlet frame The pump drain opening Drain pan Evaporator Drain pan Evaporator Drain opening AD18MS1ERA AD24MS2ERA AD28MS2ERA(S) AD18MS1ERA(D) AD24MS2ERA(D) AD28MS2ERA(S)(D) Electrical components Case Electrical components Case Air outlet frame Air outlet frame...
  • Page 178 Super Match Installation manual for wire controller Wiring connections of wire controller: TYPE 1, FOR AD12/18MS1ERA,AD12/18MS1ERA(D),AD24MS2ERA,AD24MS2ERA(D),AD28MS2ERA(S),AD28MS2ERA(S)(D) TYPE 2, FOR AD24MS1ERA, AD24MS1ERA(D),AD28/36/48NS1ERA(S) There are three methods to connection wire controller and the indoor units: A. One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the wire controller and the master unit (the indoor unit connected with wire controller directly), the others connect with the master unit through 2 pieces of polar wire( 3 pieces for model AD12/18MS1ERA, AD12/18MS1ERA(D), AD24MS2ERA, AD24MS2ERA(D), AD28MS2ERA(S), AD28MS2ERA(S)(D) and the bridge CN22 CN23 on slave...
  • Page 179 Super Match Installation Procedure Note All wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to your local distributor. WARNING Be sure to read these instructions carefully before beginning installation.
  • Page 180 。。 Super Match 1. Preparation for suspending the unit a. Size of hole at ceiling and position of hanging bolts <Combination with silent panel> AD12MS1ERA AD12MS1ERA(D) AD24MS1ERA AD24MS1ERA(D) AD18MS1ERA AD18MS1ERA(D) AD28NS1ERA(S) AD36NS1ERA(S) AD24MS2ERA AD24MS2ERA(D) AD48NS1ERA(S) AD28MS2ERA(S) AD28MS2ERA(S)(D) Hanging bolt position Hanging bolt position ~...
  • Page 181 Super Match ~ Drain Piping ~ (a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making traps. Good piping Improper piping Suspension bolts 1.5m~2m Avoid riding across an elevation Air vent Keep free from traps 。...
  • Page 182 Super Match Drainage Test (1) Conduct a drainage test after completion of the electrical work. (2) During the trial, make sure that drain flows properly through the piping and that no water leaks from connections. (3) In case of a new building, conduct the test before it is furnished with the ceiling.
  • Page 183 Super Match WARNING Danger of bodily injury or death ■ Turn off electric power at circuit breaker or power source before making any electric connections. ■ Ground connections must be completed before making line voltage connection. Precautions for electrical wiring ■...
  • Page 184 Super Match For AD48HS1ERA(S) AD60HS1ERA(S) Safety precautions The machine is adaptive in following situation 1. Applicable ambient temperature range: Max. DB/WB 32/23°C Indoor temperature Min. DB/WB 18/14°C Cooling Max. DB/WB 46/24°C Outdoor temperature Min. DB/WB 10/6°C Max. DB/WB 27°C Indoor temperature Min.
  • Page 185 Super Match Before installation (Before finishing installation, do not throw the attached parts installation needs) ■ Confirm the way to move the unit to the installation place. ■ Before moving the unit to the installation place, do not remove their packages. When having to remove the package, use a soft material or protection board with rope to lift the unit assembly to avoid unit damage or bumping a scrape.
  • Page 186 Super Match 3. Hanger bolts installation Use care of the piping direction when the unit is installed.(Use M10 screw bolt) In order to bear the weight of the unit, for existed ceiling, using foundation screw bolt, and for new ceiling, using burying embedded screw bolt, burying screw bolt or spot supplied other parts.
  • Page 187 Super Match (b) When connecting the drain pipe to unit, pay sufficient attention not to apply excess force to the piping on the unit side. Also, fix the piping at a point as close as possible to the unit. (c) For drain pipe, use hard PVC general purpose pipe VP-25(I.D.1”) which can be purchased locally.
  • Page 188 Super Match Please consult the after-sales service personnel for the choosing and installation of suction inlet, suction duct, discharging outlet and discharging duct. calculating the design drawing and outer static pressure, and choose the discharging duct with proper length and shape. ■...
  • Page 189 Super Match The attentive matters in installation of air suction and discharging duct ■ Recommend to use anti-frost and sound-absorbing duct. (locally bought) ■ The duct installation work should be finished before the fitment of ceiling. ■ The duct must be heat insulated. ■...
  • Page 190 Super Match WARNING Danger of bodily injury or death ■ Turn off electric power at circuit breaker or power source before making any electric connections. ■ Ground connections must be completed before making line voltage connection. Precautions for Electrical wiring ■...
  • Page 191: Cabinet Indoor Type

    Super Match 4. Cabinet indoor type 4.1 Features ................................190 4.2 Specification ..............................192 4.3 Dimension ...............................206 4.4 Piping diagram ..............................207 4.5 Wiring diagram ..............................208 4.6 Sound Pressure Level .............................210 4.7 Installation ...............................213...
  • Page 192: Features

    Super Match 4.1 Features AP48KS1ERA(S) AP48DS1ERA(S) AP60KS1ERA(S)
  • Page 193 Super Match Side Aire Inlet (for AP48DS1ERA(S)) Different from downside air inlet, the downside panel is new flat screen appearance with side air inlet grill. make the grill easy clean and low sound level. Touch LED screen (for AP48DS1ERA(S)) Touch LED screen make the cabinet unit appearance fashionable, end user only to have a glance to read the data.
  • Page 194: Specification

    Super Match 4.2 Specification Item Model AP48KS1ERA(S)/1U48IS1EAB(S) Function cooling heating Capacity 14.5 15.6 Sensible heat ratio 0.74 Total power input 4.51 4.57 Max. power input 6500 6500 EER or COP 3.22(A) 3.41(B) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50 Running /Max.Running current A / A...
  • Page 195 Super Match Item Model AP48DS1ERA(S)/1U48IS1EAB(S) Function cooling heating Capacity 14.1 15.5 Sensible heat ratio 0.74 Total power input 4.68 4.69 Max. power input 6500 6500 EER or COP 3.01(B) 3.31(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50 Running /Max.Running current A / A...
  • Page 196 Super Match Item Model AP48DS1ERA(S)/1U48IS1ERB(S) Function cooling heating Capacity 14.0(6.0-14.5) 15.5(6.0~16.5) Sensible heat ratio 0.74 Total power input 4.36(2.0---6.5) 4.55(2.0----6.5) Max. power input 6000 6000 EER or COP 3.21(A) 3.41(B) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50Hz Running /Max.Running current A / A...
  • Page 197 Super Match Item Model AP48KS1ERA(S)/1U48IS1ERB(S) Function cooling heating Capacity 13.6(6.0~14.5) 15.5(6.0~16.5) Sensible heat ratio 0.74 Total power input 4.5(2.0---6.5) 4.55(2.0----6.5) Max. power input 6000 6000 EER or COP 3.02(B) 3.41(B) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50Hz Running /Max.Running current A / A...
  • Page 198 Super Match Item Model AP48DS1ERA(S)/1U48LS1EAB(S) Function cooling heating Capacity 14.1 15.1 Sensible heat ratio 0.81 Total power input Max. power input 6500 6500 EER or COP 2.94(C) 3.02(D) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50Hz Running /Max.Running current A / A 8.0/10.5...
  • Page 199 Super Match Item Model AP48KS1ERA(S)/1U48LS1EAB(S) Function cooling heating Capacity 14.1 15.1 Sensible heat ratio 0.81 Total power input Max. power input 6500 6500 EER or COP 2.94(C) 3.02(D) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1N~,220~230, 50 Running /Max.Running current A / A 8.0/10.5...
  • Page 200 Super Match Item Model AP48DS1ERA(S)/1U48LS1ERA(S) Function cooling heating Capacity 12.1(6.0-14.5) 13.5(6.0~16.5) Sensible heat ratio 0.74 Total power input 4.02(2.0---6.0) 4.2(2.0----6.0) Max. power input 6000 6000 EER or COP 3.01(B) 3.21(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50Hz Running /Max.Running current A / A...
  • Page 201 Super Match Item Model AP48KS1ERA(S)/1U48LS1ERA(S) Function cooling heating Capacity 12.5(6.0-14.5) 13.0(6.0~16.5) Sensible heat ratio 0.74 Total power input 3.9(2.0---6.0) 4.05(2.0---6.0) Max. power input 5600 5600 EER or COP 3.21(A) 3.21(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50Hz Running /Max.Running current A / A...
  • Page 202 Super Match Item Model AP48DS1ERA(S)/1U48LS1ERB(S) Function cooling heating Capacity 12.5(6.0-14.5) 13.0(6.0~16.5) Sensible heat ratio 0.74 Total power input 3.89(2.0---6.0) 4.05(2.0----6.0) Max. power input 6000 6000 EER or COP 3.21(A) 3.21(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50Hz 6.7(2.9-10.0)...
  • Page 203 Super Match Item Model AP48KS1ERA(S)/1U48LS1ERB(S) Function cooling heating Capacity 12.5(6.0-14.5) 13.0(6.0~16.5) Sensible heat ratio 0.74 Total power input 3.89(2.0---6.0) 4.05(2.0---6.0) Max. power input 6000 6000 EER or COP 3.21(A) 3.21(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1PH, 220-230V~, 50Hz 6.7(2.9-10.0)...
  • Page 204 Super Match Item Model AP60KS1ERA(S)/1U60IS1EAB(S) Function cooling heating Capacity 15.5 16.3 Sensible heat ratio 0.73 Total power input 5.14 5.07 Max. power input 6500 6500 EER or COP 3.01(B) 3.21(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50 Running /Max.Running current A / A...
  • Page 205 Super Match Item Model AP60KS1ERA(S)/1U60IS1ERB(S) Function cooling heating Capacity 15.5(4.0~16.0) 16.5(4.0~18.0) Sensible heat ratio 0.74 Total power input 5.13(2.0---6.5) 5.14(2.0----6.5) Max. power input 6500 6500 EER or COP 3.02(B) 3.21(C) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50 Running /Max.Running current A / A...
  • Page 206 Super Match Item Model AP60KS1ERA(S)/1U60IS2ERB(S) Function cooling heating Capacity 13.6(6.0~14.5) 15.5(6.0~16.5) Sensible heat ratio 0.74 Total power input 4.24(2.0---6.0) 4.29(2.0----6.0) Max. power input 6000 6000 EER or COP 3.21(A) 3.61(A) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50 Running /Max.Running current A / A...
  • Page 207 Super Match Item Model AP60KS1ERA(S)/1U60IS2EAB(S) Function cooling heating Capacity Sensible heat ratio 0.74 Total power input 4.66 4.69 Max. power input 6500 6500 EER or COP 3.22(A) 3.41(B) Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz 1, 220~230, 50 Running /Max.Running current A / A 8.4/10.5...
  • Page 208: Dimension

    Super Match 4.3 Dimension AP48DS1ERA(S) AP48KS1ERA(S) AP60KS1ERA(S) Speed Mode...
  • Page 209: Piping Diagram

    Super Match 4.4 Piping diagram Liquid pipe Gas pipe Filter Filter Indoor heat exchanger...
  • Page 210: Wiring Diagram

    Super Match 4.5 Wiring diagram AP48KS1ERA(S) AP60KS1ERA(S)
  • Page 211 Super Match AP48DS1ERA(S)
  • Page 212: Sound Pressure Level

    Super Match 4.6 Sound Pressure Level (1)Testing illustrate: (2) Testing condition: a: Unit running in the normal condition b: Test in the semi-anechoic chamber c: Noise level varies from the actual factors such as room structure, etc. (3)Octave band level:...
  • Page 213 Super Match...
  • Page 214 Super Match...
  • Page 215: Installation

    Super Match 4.7 Installation AP48KS1ERA(S) AP48DS1ERA(S) AP48KS1ERA(S) , AP60KS1ERA(S) AP60KS1ERA(S) AP48DS1ERA(S) Indoor unit ¥∆ = NKM M M Outlet grill Operation panel Intel grill Remote controller Air filter (inside the unit) Outdoor unit Air inlet Air outlet Compressor (Inside of unit)
  • Page 216 Super Match Indoor & outdoor unit connection Installation figure please refers to AP60KS1ERA(S) Pipe direction Left Rear Right Bottem...
  • Page 217 Super Match Installation Procedure Before installation ■ Try to bring the packed unit to the installation place. ■ When it is inevitable to unpack the unit, be careful not to damage the unit. Wrap it with nylon etc. ■ After unpacking, be sure to put it with the front side of the unit facing up. ■...
  • Page 218 Super Match Connecting method ■ Apply refrigerant oil at half union and flare nut. ■ To bend a pipe, give the roundness as large as possible not to crash the pipe. ■ When connecting pipe, hold the pipe center to center then screw nut on by hand, refer to Fig. ■...
  • Page 219 Super Match Note: ■ Electrical wiring must be done by qualified person. ■ The power supply connects from the outdoor unit. ■ The connecting cable and power cable are self-provided. ■ Use copper wire only. ■ Air conditioner must use an exclusive line (over 30A) ■...
  • Page 220: Part 3 Outdoor Units

    Super Match Part 3 Outdoor Units 1. Specification ................................219 2. Dimension................................238 3. Wiring diagram ..............................242 4. Wiring connection ..............................250 5. Refrigerant diagram .............................253 6. Limitation values on pipe installation ........................262 7. Combination and the data ...........................266 8. Sound pressure level ............................282 9.
  • Page 221: Specification

    Super Match 1. Specification Item Model 1U24GS1ERA Power cable H05RN-F 4G 6.0mm2 Communication cable/Connecting cable H05RN-F 4G 2.5mm2 Power source 1PH,220-230VAC,50/60HZ N, V, Hz Start Current Unit model (color) 1U24GS1ERA(WHITE) Model / Manufacture SNB130FGYM2/SNB130FGYMC-L1(MGC) Oil model FV50S Compressor Oil type Oil charging 500CC Type...
  • Page 222 Super Match Item Model 1U28HS1ERA(S) Power cable H05RN-F 3G 6.0mm2 Communication cable/Connecting cable H05RN-F 4G 2.5mm2 Power source 1PH, 220-230V~, 50/60Hz N, V, Hz Start current Unit model (color) 1U28HS1ERA(S)(WHITE) Model / Manufacture/Place TNB220FLHMC-L / MELCOM OIL model FV50S Compressor Oil charging 870CC Type...
  • Page 223 Super Match Item Model 1U28GS2ERA(S) Power cable H05RN-F 4G 6.0mm2 Communication cable/Connecting cable H05RN-F 4G 2.5mm2 Power source 1PH, 220-230V~, 50/60Hz N, V, Hz Start current Unit model (color) 1U28GS2ERA(S)(WHITE) SNB172FJGMC-L(MITSUBISHI ELECTRIC Model / Manufacture/Place COMPRESSOR CO.,LTD) Compressor OIL model FV50S Oil charging 600CC...
  • Page 224 Super Match Item Model 1U36HS1ERA(S) Power cable H05RN-F 4G 6.0mm2 Communication cable/Connecting cable H05RN-F 6G 2.5mm2 Power source 1PH, 220-230V~, 50/60Hz N, V, Hz Start current Unit model (color) 1U36HS1ERA(S)(WHITE) Model / Manufacture/Place TNB220FLHMC-L / MELCOM OIL model FV50S Compressor Oil charging 870CC Type...
  • Page 225 Super Match Item Model 1U48IS1EAB(S) Power cable H05RN-F 4G 4.0mm2 Connecting cable(including communication cable) H05RN-F 4G 2.5mm2 Power source 3N~,380 ~ 400, 50Hz N, V, Hz Start Current 62.5 Unit model (color) 1U48IS1EAB(S)(WHITE) Model / Manufacture/ JT160G-P8Y1/XIAN DAIKIN place CORPORATION Compressor Oil model PVE(FV50S or the same)
  • Page 226 Super Match Item Model 1U48IS1ERB(S) Power cable H07RN-F 5G 4.0mm2 Connecting cable H05RN-F 4G 2.5mm2 (including communication table) Power source 3N~,380 ~ 400V, 50Hz N, V, Hz Start Current Unit model (color) 1U48IS1ERB(S)(WHITE) TNB306FPNMC(MITSUBISHI ELECTRIC Model / Manufacture/place COMPRESSOR CO.,LTD) Oil model Compressor FV50S...
  • Page 227 Super Match Item Model 1U48LS1EAB(S) Power cable H05RN-F 5G 4.0mm2 Connecting cable(including communication table) H05RN-F 4G 2.5mm2 Power source 3N~,380 ~ 400, 50 N, V, Hz Start Current 62.5 Unit model (color) 1U48LS1EAB(S)(WHITE) JT160G-P8Y1/XIAN DAIKIN Model / Manufacture/place CORPORATION Compressor Oil model PVE (FV50S or the same) Oil charging...
  • Page 228 Super Match Item Model 1U48LS1ERA(S) Power cable H05RN-F 3G 6.0mm2 connecting cable(including communication cable) H05RN-F 4G 2.5mm2 Power source N, V, Hz 1PH, 220-230V~, 50Hz Start Current Unit model (color) 1U48LS1ERA(S)(WHITE) TNB306FPGMC/MITSUBISHI ELECTRIC Model / Manufacture/place CORPORATION Oil model Compressor PVE(FV50S)...
  • Page 229 Super Match Item Model 1U48LS1ERB(S) Power cable H05RN-F 4G 4.0mm Connecting cable H05RN-F 4G 2.5mm (including communication table) Power source 3N~,380 ~ 400, 50 N, V, Hz Start Current Unit model (color) 1IU48LS1ERB(S)(WHITE) Model / Manufacture/ TNB306FPNMC/MITSUBISHI place ELECTRIC CORPORATION Oil model Compressor PVE(FV50S)...
  • Page 230 Super Match Item Model 1U60IS1EAB(S) Power cable H07RN-F 5G 4.0mm2 Connecting cable(including communication table H05RN-F 4G 2.5mm2 Power source 3N~,380 ~ 400, 50Hz N, V, Hz Start Current 62.5 Unit model (color) 1U60IS1EAB(S)(WHITE) Model / Manufacture/place JT170G-P8Y1(XI AN Daikin ) Oil model FV50S Compressor...
  • Page 231 Super Match Item Model 1U60IS1ERB(S) Power cable H05RN-F 5G 2.5mm2 Connecting cable(including communication cable) H05RN-F 4G 2.5mm Power source 3N~,380 ~ 400, 50/60Hz N, V, Hz Start Current Unit model (color) 1U60IS1ERB(S)(WHITE) LNB42FUAMC(MITSUBISHI ELECTRIC COMPRESSOR Model / Manufacture/place CO.,LTD) Oil model Compressor FV50S Oil charging...
  • Page 232 Super Match Item Model 1U60IS2EAB(S) Power cable H05RN-F 4G 4.0mm2 Communication cable H05RN-F 4G 2.5mm2 Connecting cable H05RN-F 4G 0.75mm2 Power source N, V, Hz 3N~,380~400, 50Hz Start Current 62.5 Unit model (color) 1U60IS2EAB(S)(WHITE) JT160G-P8Y1/XIAN DAIKIN Model / Manufacture/place CORPORATION Compressor OIL model PVE(FV50S)...
  • Page 233 Super Match Item Model 1U60IS2ERB(S) Power cable H07RN-F 5G 4.0mm2 Communication cable Connecting cable H05RN-F 4G 1.5mm2 Power source(outdoor unit) N, V, Hz 3N~,380~400V, 50Hz Start Current Unit model (color) 1U60IS2ERB(S)(WHITE) TNB306FPNMC(MITSUBISHI ELECTRIC Model / Manufacture/place COMPRESSOR CO.,LTD) Compressor OIL model FV50S Oil charging 870CM3...
  • Page 234 Super Match Item Model 3U19FS1ERA 3U19FS1ERA(N) Function Cooling Heating —— Rating capacity 5400 6500 Cooling Pdesign 5400 Heating Pdesign(-10 4500 Rated power input (indoor + outdoor) 1317 1457 Rated current input (indoor + outdoor) EER / COP 4.46 SEER / SCOP Minimum capacity 1500 1800...
  • Page 235 Super Match Item Model 3U24GS1ERA 3U24GS1ERA(N) Function Cooling Heating —— Rating capacity 6700 8000 Cooling Pdesign 6700 Heating pdesign(-10℃ ) 5300 Rated power input (indoor + outdoor) 1675 1826 Rated current input (indoor + outdoor) 7.28 EER / COP 4.38 SEER / SCOP Minimum capacity 1500...
  • Page 236 Super Match Item Model 4U26HS1ERA Function Cooling Heating —— Rating capacity 7600 8600 Cooling Pdesign 8800 Heating pdesign(-10℃ ) 6200 Rated power input (indoor + outdoor) 2000 2177 Rated current input (indoor + outdoor) 8.70 9.47 EER / COP 3.95 SEER / SCOP Minimum capacity 1500...
  • Page 237 Super Match Item Model 4U30HS1ERA Function Cooling Heating —— Rating capacity 8800 9800 Cooling Pdesign 8800 Heating pdesign(-10℃ ) 7100 Rated power input (indoor + outdoor) 2316 2390 Rated current input (indoor + outdoor) 10.1 10.4 EER / COP SEER / SCOP Minimum capacity 1500 1800...
  • Page 238 Super Match Item Model 5U34HS1ERA Function Cooling Heating —— Rating capacity 10000 10700 Cooling Pdesign 10000 Heating pdesign(-10℃ ) 8100 Rated power input (indoor + outdoor) 2770 2675 Rated current input (indoor + outdoor) 12.1 11.6 EER / COP 4.00 SEER / SCOP Minimum capacity 1500...
  • Page 239 Super Match Item Model 5U45LS1ERA Function Cooling Heating —— Rating capacity 12200 12680 Cooling Pdesign 12200 Heating pdesign(-10℃ ) 9000 Rated power input (indoor + outdoor) 3631 3251 Rated current input (indoor + outdoor) 15.8 14.1 EER / COP 3.36 SEER / SCOP Minimum capacity 1500...
  • Page 240: Dimension

    Super Match 2. Dimension 1U24GS1ERA(S) 1U28HS1ERA(S) 1U36HS1ERA(D) 1U48IS1EAB(S) 1U48IS1ERB(S) 1U60IS1ERA(S) 1U48LS1ERA(S) 1U48LS1ERB(S) 1U48LS1EAB(S) 1U60IS1ERB(S) 1U60IS1EAB(S) 1U60IS2EAB(S) 1U60IS2ERB(S) 1008...
  • Page 241 Super Match 3U19FS1ERA 3U19FS1ERA(N): Air inlet Air inlet Air outlet Handle Handle Liquid pipe:Φ6.35(flared)1/4 A unit connection Gas pipe :Φ9.52(flared)3/8 Liquid pipe:Φ6.35(flared)1/4 Gas pipe :Φ9.52(flared)3/8 B unit connection Liquid pipe:Φ6.35(flared)1/4 Gas pipe :Φ9.52(flared)3/8 C unit connection 4U26HS1ERA, 4U30HS1ERA: Air inlet Air inlet Gas pipe Φ...
  • Page 242 Super Match 3U24GS1ERA 3U24GS1ERA(N) 5U34HS1ERA: Air inlet Air inlet Gas pipe Air outlet Φ9.52(flared) 3/8(A,B,C,D unit) Φ12.7(flared) 1/2(E unit) Handle Indoor and outdoor Handle connect wiring hole (30*48) Handle A unit connection B unit connection C unit connection D unit connection E unit connection Liquid pipe Φ6.35(flared) 1/4...
  • Page 243 Super Match 5U45LS1ERA: Air inlet Air inlet Gas pipe Ø9.52(flared) 3/8(A,B,C, unit) Ø12.7(flared) 1/2(D,E unit) Air outlet 1008 Indoor and outdoor Handle connect wiring hole (30*48) Handle A unit connection B unit connection C unit connection D unit connection E unit connection Liquid pipe Ø6.35(flared) 1/4...
  • Page 244: Wiring Diagram

    Super Match 3. Wiring diagram 1U24GS1ERA 1U28GS2ERA(S)
  • Page 245 Super Match 1U28HS1ERA(S) 1U36HS1ERA(S) CN13...
  • Page 246 Super Match 1U48LS1ERA(S)
  • Page 247 Super Match 1U48LS1ERB(S) 1U48IS1ERB(S) 1U60IS1ERB(S)
  • Page 248 Super Match 1U48IS1EAB(S) 1U48LS1EAB(S) 1U60IS1EAB(S) 1U60IS2EAB(S)
  • Page 249 Super Match 3U19FS1ERA 3U24GS1ERA 3U19FS1ERA(N) 3U24GS1ERA(N)
  • Page 250 Super Match 4U26HS1ERA 4U30HS1ERA 5U34HS1ERA...
  • Page 251 Super Match 5U45LS1ERA...
  • Page 252: Wiring Connection

    Super Match 4. Wiring connection 3U19FS1ERA 3U19FS1ERA(N) 3U24GS1ERA 3U24GS1ERA(N) Outdoor 1PH, 220-230V, 50Hz Indoor Indoor Unit A Indoor Unit B Indoor Unit C Power Supply Cable: H05RN-F3G 4.0mm² Connecting Cable: H05RN-F4G 2.5mm² Connecting Cable: H05RN-F2G 2.5mm² If this outdoor unit connects with AS*S1ERA, the connecting cable is 1.5mm² Connect the connecting wires between indoor and outdoor units and ensure the sequence numbers on terminals match with each other.
  • Page 253 Super Match 4U26HS1ERA 4U30HS1ERA 1PH, 220-230V, 50Hz Power Supply Cable: H05RN-F3G 4.0mm² Connecting Cable: H05RN-F4G 2.5mm² Connecting Cable: H05RN-F2G 2.5mm² If this outdoor unit connects with AS*S1ERA, the connecting cable is 1.5mm² Connect the connecting wires between indoor and outdoor units and ensure the sequence numbers on terminals match with each other.
  • Page 254 Super Match 5U34HS1ERA 5U45LS1ERA: Power Supply Cable: H05RN-F3G 4.0mm² Connecting Cable: H05RN-F4G 2.5mm² Connecting Cable: H05RN-F2G 2.5mm² If this outdoor unit connects with AS*S1ERA, the connecting cable is 1.5mm² Connect the connecting wires between indoor and outdoor units and ensure the sequence numbers on terminals match with each other.
  • Page 255: Refrigerant Diagram

    Super Match 5. Refrigerant diagram 1U24GS1ERA...
  • Page 256 Super Match 1U28GS2ERA(S) 1U28GS2ERA(S)(D)
  • Page 257 Super Match 1U28HS1ERA (S) 1U36HS1ERA (S)
  • Page 258 Super Match 1U49LS1EAB (S) 1U48LS1ERB (S) 1U48LS1ERA (S) 1U60LS2EAB (S)
  • Page 259 Super Match 1U60LS1EAB (S) 1U60LS1ERB (S) 1U60LS1ERA (S)
  • Page 260 Super Match 1U48IS1ERB (S) 1U60IS1ERB (S) 1U60IS2ERB (S)
  • Page 261 Super Match 3U19FS1ERA 3U19FS1ERA (N) 3U24GS1ERA 3U24GS1ERA (N)
  • Page 262 Super Match 4U26HS1ERA 4U30HS1ERA...
  • Page 263 Super Match 5U34HS1ERA 5U45LS1ERA...
  • Page 264: Limitation Values On Pipe Installation

    Super Match 6. Limitation values on pipe installation 3U19FS1ERA 3U19FS1ERA(N) 3U24GS1ERA 3U24GS1ERA(N) The piping length information, please refer the following table. Item Unit Description Standard Maximum φ6.35 A,B,C liquid pipe mm Size of the liquid side connection pipe φ9.52 A,B,C Gas pipe mm Size of the gas side connection pipe Max.piping length between IU and OU of the way ≤...
  • Page 265 Super Match 4U26HSIERA 4U30HS1ERA The piping length information, please refer the following table. Item Unit Description Standard Maximum φ6.35 A,B,C, Dliquid pipe mm Size of the liquid side connection pipe φ9.52 A,B,C Gas pipe mm Size of the gas side connection pipe φ12.7 D Gas pi[pe mm Size of the gas side connection pipe...
  • Page 266 Super Match 5U34HS1ERA 5U45LS1ERA The piping length information, please refer the following table. Item Unit Description Standard Maximum φ6.35 A,B,C,D,E liquid pipe mm Size of the liquid side connection pipe φ9.52 A,B,C,D Gas pipe mm Size of the gas side connection pipe φ12.7 E Gas pi[pe mm Size of the gas side connection pipe...
  • Page 267 Super Match Connection cautions model 3U19FS1ERA 3U24GS1ERA 4U26HS1ERA,4U30HS1ERA 5U34HS1ERA connection priority between indoor and stop valve higher from down to up when there is 1 indoor,the prior stop valve is when there are 2 D 、 C C 、 B 、...
  • Page 268: Combination And The Data

    Super Match 7. Combination and the data 3U19FS1ERA 3U19FS1ERA(N) combination and the data COOLING Rated total cooling total power input total current Combinations capacity(Kw) capacity(kW) (kW) (A)@230V (W/W) (Nom. cooling) Energy Energy SEER Comb. label (W/W) label Unit Unit Unit Unit Unit Unit...
  • Page 269 Super Match HEATING Rated total heating total power input total current Combinations capacity(kW) capacity(KW) (A)@230V (W/W) Energy Energy SEER (Nom. heating) Comb. label (W/W) label Unit Unit Unit Unit Unit Unit min. rated max. min. rated max. min. rated max. rated data data...
  • Page 270 Super Match 3U24GS1ERA 3U24GS1ERA(N) combination and the data COOLING Rated total cooling total power input total current Combinations capacity(Kw) capacity(kW) (kW) (A)@230V (W/W) Energy Energy SEER (Nom. cooling) Comb. label (W/W) label Unit Unit Unit Unit Unit Unit min. rated max.
  • Page 271 Super Match HEATING Rated total heating total power input total current Combinations capacity(kW) capacity(KW) (A)@230V (W/W) Energy Energy SEER (Nom. heating) Comb. label (W/W) label Unit Unit Unit Unit Unit Unit min. rated max. min. rated max. min. rated max. rated data data...
  • Page 272 Super Match 4U26HS1ERA combination and the data COOLING Rated capacity total power total cooling total current Combinations Output/kW input capacity(kW) (A)@230V (W/W) Energy Energy SEER (Nom. cooling) (kW) Comb. label (W/W) label Unit Unit Unit Unit Unit Unit Unit Unit min.
  • Page 273 Super Match HEATING Rated capacity total power total cooling total current Combinations Output/kW input capacity(kW) (A)@230V (W/W) Energy Energy SEER Comb. (Nom. cooling) (kW) label (W/W) label Unit Unit Unit Unit Unit Unit Unit Unit min. rated max. min. rated max.
  • Page 274 Super Match 4U30HS1ERA combination and the data COOLING Rated capacity total power total cooling total current Combinations Output/kW (Nom. input capacity(kW) (A)@230V (W/W) Energy Energy SEER cooling) (kW) Comb. label (W/W) label Unit Unit Unit Unit Unit Unit Unit Unit min.
  • Page 275 Super Match Rated capacity total power total cooling total current Combinations Output/kW (Nom. input capacity(kW) (A)@230V (W/W) Energy Energy cooling) (kW) SEER Comb. label (W/W) label Unit Unit Unit Unit Unit Unit Unit Unit min. rated max. min. rated max. min.
  • Page 276 Super Match 5U34HS1ERA combination and the data COOLING Rated capacity Output/kW total cooling total power input total current Combinations (Nom. cooling) capacity(kW) (kW) (A)@230V (W/W) Energy Energy SEER Comb. label (W/W) label Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit min.
  • Page 277 Super Match Rated capacity Output/kW total cooling total power input total current Combinations (Nom. cooling) capacity(kW) (kW) (A)@230V (W/W) Energy Energy SEER Comb. label (W/W) label Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit min. rated max. min. rated max.
  • Page 278 Super Match 5U34HS1ERA combination and the data HEATING Rated capacity Output/ total power total cooling total current Combinations input capacity(kW) (A)@230V (W/W) Energy Energy (Nom. cooling) (kW) SEER Comb. label (W/W) label Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit min.
  • Page 279 Super Match Rated capacity Output/ total cooling total power input total current Combinations capacity(kW) (kW) (A)@230V (W/W) Energy Energy SEER (Nom. cooling) Comb. label (W/W) label Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit min. rated max. min. rated max.
  • Page 280 Super Match 5U45LS1ERA combination and the data COOLING Rated capacity Output/ total power total cooling total current Combinations input capacity(kW) (A)@230V (W/W) Energy Energy (Nom. cooling) (kW) SEER Comb. Label (W/W) Label Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit min.
  • Page 281 Super Match Rated capacity Output/ total cooling total power input total current Combinations capacity(kW) (kW) (A)@230V (W/W) Energy Energy SEER (Nom. cooling) Comb. Label (W/W) Label Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit min. rated max. min. rated max.
  • Page 282 Super Match 5U45LS1ERA combination and the data HEATING Rated capacity Output/ total power total cooling total current Combinations input capacity(kW) (A)@230V (W/W) Energy Energy SEER (Nom. cooling) (kW) Comb. Label (W/W) Label Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit min.
  • Page 283 Super Match Rated capacity Output/ total power total cooling total current Combinations input capacity(kW) (A)@230V (W/W) Energy Energy SEER (Nom. cooling) (kW) Comb. Label (W/W) Label Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit min. rated max. min. rated max.
  • Page 284: Sound Pressure Level

    Super Match 8. Sound pressure level Test method Set the unit: 1) the unit is placed on the rubber whose thickness is 5mm; 2) if the height between the air outlet and ground is less than 1m, block the unit up to 1m.far from ground Test position: After setting the unit ,the test position for the noise is 1m far from the front panel...
  • Page 285 Super Match...
  • Page 286 Super Match...
  • Page 287 Super Match...
  • Page 288 Super Match...
  • Page 289 Super Match...
  • Page 290 Super Match...
  • Page 291 Super Match...
  • Page 292 Super Match...
  • Page 293: Outdoor Performance Curves

    Super Match 9. Outdoor performance curves 1U24GS1ERA cooling capacity curves 8.00 7.00 18/12 20/14.5 6.00 22/16 25/18 5.00 27/19 30/22 32/23 4.00 3.00 2.00 10/6 21/15 25/18 32/20 38/24 43/26 46/26 53/32 Outdoor DB(℃) 1U24GS1ERA heating capacity curves 8.50 8.00 16/10 18/12 7.50...
  • Page 294 Super Match 1U28HS1ERA (S) Heating capacity curves 12000 -6/-7 11000 -4/-5 -1/-2 10000 9000 8000 12/10 7000 16/15 6000 5000 4000 16/10 18/12 20/14.5 21/15 22/16 24/17 26/18 indoor DB./WB. Cooling capacity curves 10000 9000 8000 7000 6000 5000 4000 3000 18/12 20/14...
  • Page 295 Super Match 1U36HS1ERA0(S) 1U36HS1ERA(S) heating capacity curves -6/-7 heating capacity 13000 -6/-7 power input 12500 12000 -4/-5 heating 11500 capacity 11000 -4/-5 power 10500 input 10000 0/-1 heating 9500 capacity 9000 0/-1 power input 8500 8000 2/1 heating 7500 capacity 7000 2/1 power input 6500...
  • Page 296 Super Match 1U48LS1EAB (S) heating capacity curves -7/ -8 heating 16000 capacity 15000 -7/ -8 power input 14000 -5/ -6 heating capacity 13000 -5/ -6 power input 12000 -1/ -2 heating 11000 capacity -1/ -2 power 10000 input 2/1 heating 9000 capacity 8000...
  • Page 297 Super Match 1U48LS1ERB(S) heating capacity curves 18000 ‐ 6/‐ 7 heating capacity 17000 ‐ 6/‐ 7 power input 16000 ‐ 4/‐ 5 heating 15000 capacity ‐ 4/‐ 5 power 14000 input 13000 ‐ 1/‐ 2 heating capacity 12000 ‐ 1/‐ 2 power input 11000 1/0 heating...
  • Page 298 Super Match 1U48LS1ERA(S) heating capacity curves 18000 -6/-7 heating capacity 17000 -6/-7 power input 16000 -4/-5 heating 15000 capacity -4/-5 power 14000 input 13000 -1/-2 heating capacity 12000 -1/-2 power input 11000 1/0 heating 10000 capacity 1/0 power input 9000 8000 6/5 heating capacity...
  • Page 299 Super Match 1U48IS1EAB(S)/1U60IS2EAB(S) heating capacity curves 16/10 cooling capacity 18000 17000 18/12 cooling capacity 16000 15000 20/14.5 cooling capacity 14000 22/16 cooling capacity 13000 12000 24/17 cooling capacity 11000 10000 26/18 coolingcapacity 9000 8000 16/10 power input 7000 6000 18/12 power input 5000 4000 20/14.5 power input...
  • Page 300 Super Match 1U48IS1ERB(S)/1U60IS2ERB(S) heating capacity curves 17000 -6/-7 heating capacity -6/-7 power input 15000 -4/-5 heating capacity -4/-5 power input 13000 -1/-2 heating capacity -1/-2 power input 11000 1/0 heating capacity 9000 1/0 power input 6/5 heating capacity 7000 6/5 power input 7/6 heating capacity 5000 7/6 power input...
  • Page 301 Super Match 1U60IS1ERB(S) heating capacity curves 19000 -6/-7 heating capacity 18000 -6/-7 power 17000 input -4/-5 heating 16000 capacity 15000 -4/-5 power input 14000 -1/-2 heating 13000 capacity -1/-2 power 12000 input 11000 1/0 heating capacity 10000 1/0 power input 9000 6/5 heating 8000...
  • Page 302 Super Match 1U60IS1EAB(S) heating capacity curves 16/10 cooling capacity 19000 18000 18/12 cooling capacity 17000 16000 20/14.5 cooling capacity 15000 14000 22/16 cooling capacity 13000 12000 24/17 cooling capacity 11000 10000 26/18 cooling capacity 9000 8000 16/10 power input 7000 6000 18/12 power input 5000...
  • Page 303 Super Match 3U19FS1ERA 3U19FS1ERA(N) cooling capacity in relation to temperature 7000 Indoor 6500 temperature WB./DB. 6000 5500 5000 14/20 16/22 4500 19/27 22/30 4000 3500 Outdoor temperature DB. 3U19FS1ERA 3U19FS1ERA(N) heating capacity in relation to temperature Indoor temperatureD 8500 7500 6500 5500 4500...
  • Page 304 Super Match 3U24GS1ERA 3U24GS1ERA (N)cooling capacity in relation to temperature 35000 indoor 30000 temperature 25000 WB./DB. 20000 22/30 15000 19/27 16/22 10000 14/20 5000 outdoor temperatureDB. outdoor temperatureDB. 3U24GS1ERA 3U24GS1ERA (N)heating capacity in relation to temperature 40000 indoor temperature 35000 30000 30000 25000...
  • Page 305 Super Match 4U26HS1ERA cooling capacity in relation to temperature 10000 Indoor temperature W.B./D.B. 9000 8000 7000 14/20 16/22 6000 19/27 22/30 5000 4000 Outdoor temperature DB . 4U26HS1ERA heating capacity in relation to temperature 10000 Indoor temperatureD 9000 8000 7000 6000 5000 4000...
  • Page 306 Super Match 4U30HS1ERA cooling capacity in relation to temperature 11000 Indoor temperature WB./DB. 10000 9000 8000 14/20 7000 16/22 19/27 22/30 6000 5000 Outdoor temperature DB. 4U30HS1ERA heating capacity in relation to temperature 12000 Indoor temperatureD 11000 10000 9000 8000 7000 6000 5000...
  • Page 307 Super Match 5U34HS1ERA cooling capacity in relation to temperature 13000 Indoor temperature 12000 WB./DB. 11000 10000 9000 14/20 16/22 8000 19/27 22/30 7000 6000 Outdoor temperature DB. 5U34HS1ERA heating capacity in relation to temperature 14500 Indoor temperatureD 13500 12500 11500 10500 9500 8500...
  • Page 308 Super Match 5U45LS1ERA heating capacity curves 18000 -6/-7 heating capacity 17000 -6/-7 power input 16000 -4/-5 heating 15000 capacity -4/-5 power 14000 input 13000 -1/-2 heating capacity 12000 -1/-2 power input 11000 1/0 heating 10000 capacity 1/0 power input 9000 8000 6/5 heating capacity...
  • Page 309: Installation

    Super Match 10. Installation WARNING CAUTION...
  • Page 310 Super Match...
  • Page 311 Super Match...
  • Page 312 Super Match...
  • Page 313 Super Match Items to Be Checked...
  • Page 314 Super Match...
  • Page 315 Super Match...
  • Page 316 Super Match For 1U24GS1ERA Air outlet Wind direction Cushion rubber...
  • Page 317 Super Match Piping size φ9.52 X 0.8mm Liquid Pipe 1U24GS1ERA φ15.88 X 1.0mm Gas Pip Connection of pipes To bend a pipe, give the roundness as large as possible not to crush the pipe , ● and the bending radius should be 30 to 40 mm or longer. Connecting the pipe of gas side first makes working easier.
  • Page 318 Super Match 3 Air discharging method...
  • Page 319 Super Match...
  • Page 320 Super Match 6. Wiring Connection Item Circuit breaker Earth leakage breaker phase Overcurrent Power source Switch breaker Switch breaker(A) Leak Current(mA) protector capacity wire size(min)(mm Model 1U24GS1ERA T 25A/250V.
  • Page 321 Super Match Outdoor unit Model 1U24GS1ERA Connecting wiring ≥4G0.75mm2 Power cable ≥3G4.0mm2 1PH,220-230VAC,50HZ...
  • Page 322 1U36HS1ERA(S) FQG-2Y100A AC18CS1ERA(S) YR-E16 1U48LS1ERB(S) AB24ES1ERA(S) YR-E14 or 1U48LS1ERA(S) YR-E16 AC24CS1ERA(S) 1U48IS1ERB(S) FQG-2Y200A AB28ES1ERA(S) 1UI60S1ERB(S) YR-E14 or 1UI60S2REB(S) YR-E16 AC28ES1ERA(S) AB12CS1ERA(S) YR-E14 or 1U36HS1ERA(S) FQG-3Y100A YR-E16 AC12CS1ERA(S) 1U48LS1ERB(S) AB18CS1ERA(S) 1U48LS1ERA(S) YR-E14 or 1U48IS1ERB(S) FQG-3Y200A YR-E16 1U60IS1ERB(S) AC18CS1ERA(S) 1U60IS2ERB(S) 1U48LS1ERB(S) AB12CS1ERA(S)
  • Page 323 Super Match When installing MAXI SPLIT Series(1U36HS1ERA(S)/1U48LS1ERA(S)/1U48LS1ERB(S)/1U48IS1ERB(S)/1U60IS 1ERB(S)),Please refer to the table below concerning the pipe lengths , heights and sizes. Height between Total one-way Branch piping Height between Max model Piping daigram outdoor unit and piping length length indoors indoor unit Size remark L1 or L2...
  • Page 324 Super Match Name of parts 1U24GS1ERA 1U28GS2ERA(S) 1U28HS1ERA(S) 1U36HS1ERA(S) Air inlet Air inlet Air outlet Air outlet Compressor Compressor (Inside of unit) (Inside of unit) 1U48LS1ERA(S) 1U48LS1ERB(S) 1U48LS1EAB(S) 1U48IS1EAB(S) 1U48IS1ERB(S) 1U60IS1ERA(S) 1U60IS1ERB(S) 1U60IS1EAB(S) 1U60IS2EAB(S) 1U60IS2ERB(S) Air inlet Air inlet Air outlet Compressor Air outlet (Inside of unit)
  • Page 325 Super Match 1. Piping diagram for single split 1U24GS1ERA 1U28GS2ERA(S) 1U28HS1ERA(S) 1U36HS1ERA(S) 1U48LS1ERA(S) 1U48LS1ERB(S) 1U48LS1EAB(S) 1U48IS1EAB(S) 1U48IS1ERB(S) 1U60IS1ERA(S) 1U60IS1ERB(S) 1U60IS1EAB(S) 1U60IS2EAB(S) 1U60IS2ERB(S) 2. Piping size for single split 1U24GS1ERA 1U28GS2ERA(S) Liquid pipe Ф9.52×0.8mm Gas pipe Ф15.88×1.0mm 1U28HS1ERA(S) 1U36HS1ERA(S) Liquid pipe Ф9.52×0.8mm 1U48LS1ERA(S) 1U48LS1ERB(S) 1U48LS1EAB(S) 1U48IS1EAB(S)
  • Page 326 Super Match After finishing connection of refrigerant pipe, it shall perform air tightness test. ■ The air tightness test adopts nitrogen tank to give pressure according to the pipe connection mode as the following figure shown. ■ The gas and liquid valve are all in close state. In order to prevent the nitrogen entering the circulation system of outdoor unit, tighten the valve rod before giving pressure (both gas and liquid valve rods).
  • Page 327 Super Match ■ Only in COOLING operation can charge the additional refrigerant. ■ When charging, the refrigerant shall be charged from the charging nozzle of low pressure valve. ■ Be carefull when charging refrigerant, do not let the air mix into the system, and must charge the additional refrigerant in liquid state.
  • Page 328 Super Match WARNING DANGER OF BODILY INJURY OR DEATH TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS. Precautions for Electrical wiring ■ Electrical wiring work should be conducted only by authorized personnel. ■...
  • Page 329 Super Match The specification of power cable For models 1U24GS1ERA,1U28GS2ERA(S),1U28HS1ERA(S), 1U36HS1ERA(S), 1U48LS1ERA(S), 1U60IS1ERA(S), 1U60IS2ERB(S) the power cable should be H05RN-F 3G 6.0mm For models 1U48LS1EAB(S), 1U48IS1EAB(S), 1U60IS1EAB(S), 1U48LS1ERB(S), 1U48IS1ERB(S), 1U60IS1ERB(S), 1U60IS2EAB(S) the power cable should be H07RN-F 5G 4.0mm Wiring procedure 1) Remove set screws on the side before taking off the front panel toward the direction.
  • Page 330 Super Match Accessories Accessories supplied with the outdoor unit: Drawing Name of parts Quantity Note 3U19FS1ERA(N) 3U24GS1ERA(N) Drainage elbow 4U26HS1ERA 4U30HS1ERA 5U34HS1ERA 5U45LS1ERA 3U19FS1ERA(N) 4U30HS1ERA 3U24GS1ERA(N) Rubber cushion 5U34HS1ERA 4U26HS1ERA 5U45LS1ERA 3U19FS1ERA(N) 3U24GS1ERA(N) Clap 4U26HS1ERA 4U30HS1ERA 5U34HS1ERA 5U45LS1ERA 3U19FS1ERA(N) 4U30HS1ERA 3U24GS1ERA(N) Adaptor(3/8→1/2) 5U34HS1ERA 4U26HS1ERA 5U45LS1ERA 4U26HS1ERA 4U30HS1ERA 5U34HS1ERA...
  • Page 331 Super Match Note: 1) Cannot be installed hanging from ceiling or stacked. 2) If installing on a high place such as a roof, with a fence or guard rail around it. 3) If there is a potential for accumulated snow to block the air inlet or heat exchanger, install the unit on a higher base.
  • Page 332 Super Match Super Match Installation drawings of indoor and outdoor units 1 Do not connected the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor unit in order to add another indoor unit later. Make sure no dirt or moisture gets into either side of the embedded branch piping.
  • Page 333 Super Match Precautions on Installation ■ Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed. ■ In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts.(Prepare four sets of M8 or M10 foundation bolts, nuts and washers each which are available on the market.)
  • Page 334 Super Match Refrigerant piping work 1. Installing outdoor unit 1) When installing the outdoor unit, refer to "Precautions for Selecting the Location" and the "Indoor/Outdoor Unit Installation Drawings". 2) If drain work is necessary, follow the procedures below. 2. Drain work 1) Use drain plug for drainage.
  • Page 335 Super Match 3. Refrigerant piping work 1). Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the tor wrenches. Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas.
  • Page 336 Super Match 5. Refilling the refrigerant Check the type of refrigerant to be used on the machine nameplate. Precautions when adding R410A Fill from the liquid pipe in liquid form. It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
  • Page 337 Super Match 3) Use separate thermal insulation pipes for gas and liquid refrigerant pipe 8. Cutting and Flaring work of piping ■ Pipe cutting is carried out with a pipe cutter and burs must be removed. ■ After inserting the flare nut, flaring work is carried out. Pipe diameter Size A (mm) Pipe Liquid side...
  • Page 338 Super Match Pump Down Operation In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 1) Remove the valve caps from liquid stop valve and gas stop valve. liquid 2) Carry out forced cooling operation. stop valve Hexagonal 3) After five to ten minutes, close the liquid stop valve with a...
  • Page 339 Super Match 3. Wiring method of outdoor unit: ■ Power line Remove the repair board of the outdoor unit and loosen the wire cover A,then put the live wire, neutral wire and grounding wire through the wire cover ,and connect them to terminal block correspondingly. After connection, fasten wire cover to its previous state.
  • Page 340 Super Match Test running ■ Before starting the test running, please confirm the following works have been done successfully. 1) Correct piping work; 2) Correct wiring work; 3) Correct match of indoor and outdoor unit; 4) Proper recharge of refrigerant if needed. Make sure that all the stop valves are fully open. ■...
  • Page 341: Part 4 Electric Control And Debugging

    Super Match Part 4 Electric Control and Debugging 1. Indoor unit PCB ..............................340 2. Indoor unit dip switch setting and function......................342 3. Outdoor unit PCB photo, dip switch setting and function ..................349 4. Diagnostic code ..............................375 5. Trouble shooting ..............................392 6.
  • Page 342: Indoor Unit Pcb

    Super Match 1. Indoor unit PCB PCB(0151800106) AD09/12/18/24LS1ERA AD24MS1ERA AD24MS1ERA(D) AD28/36/48NS1ERA(S) AD48/60HS1ERA(S) AB09CS1ERA AB12/18CS1ERA(S) AB24/28/36/48ES1ERA(S) AB60CS1ERA(S) AB60ES2ERA(S) AC12/18/24CS1ERA(S) AC28/36ES1ERA(S) AC48/60FS1ERA(S) AC60FS1ERA(S) AP48KS1ERA(S) AP60KS1ERA(S) PCB(0151800106A) AP48DS1ERA(S)
  • Page 343 Super Match PCB(0151800175B) AD09~24SS1ERA AD09~24SS1ERA(N)(P) AD09~24SS1ERA(N) AD12MS1ERA AD18MS1ERA AD12MS1ERA(D) AD18MS1ERA(D) AD24MS2ERA AD24MS2ERA(D) AD28MS2ERA(S) AD28MS2ERA(S)(D)
  • Page 344: Indoor Unit Dip Switch Setting And Function

    Super Match 2. Indoor unit dip switch setting and function Indoor unit dip switch setting AD24MS1ERA AD28/36/48NS1ERA(S) AD48/60HS1ERA(S) AB09/12/18CS1ERA(S) AB24/28/36/48ES1ERA(S) AB60CS1ERA(S) AB60ES2ERA(S) AP48/60KS1ERA(S) AC12/18/24CS1ERA(S) AC28/36ES1ERA(S) AC48/60FS1ERA(S) AD09LS1ERA AD12LS1ERA AD18LS1ERA AD24LS1ERA AD24MS1ERA(D) (1: ON 0: OFF) SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description 09K indoor unit 12K indoor unit...
  • Page 345 Super Match Note: Static pressure value for AD09~24SS1ERA,AD09~24SS1ERA(N),AD09~24SS1ERA(N)(P), AD12/18/MS1ERA and AD12/18/MS1ERA(D) AD24MS2ERA AD24MS2ERA(D) (selection by SW1-4 SW1-5 ) Static pressure(Pa) AD**SS1ERA AD**SS1ERA(N) AD**SS1ERA(N)(P) AD12MS1ERA AD18MS1ERA AD12MS1ERA(D) AD18MS1ERA(D) AD24MS2ERA AD24MS2ERA(D) AD28MS2ERA(S) AD28MS2ERA(S) AD48NS1ERA(S) AP48DS1ERA(S) SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description 48K indoor unit...
  • Page 346 Super Match Indoor unit function 2.2.1 Sign definition Indoor outdoor Toci Thick pipe Compressor Compressor Ambient Outlet Inlet pipe Mid coil Ambient Defrost of heat condenser suction discharging temp pipe temp. temp temp temp temp exchanger temp. temp. temp. Tcomp1,2 Tset Temp.
  • Page 347 Super Match 2.2.6 Control for discontinuous operation After the unit starts up in cooling/heating mode, in 5 minutes, the compressor run/stop will not be controlled by the room temp., but after changing the set temp., if compressor stop condition can be met, the system will stop compressor immediately.
  • Page 348 Super Match 2.2.11 Water pump control A: Water pump will be electrified when indoor unit enters non-heating mode until indoor unit stops. 5 minutes later after indoor unit stops, water pump will stop. B: When indoor unit is in heating mode, water pump will not operate. C: In OFF state and in any mode, once float switch signal is measured, indoor unit will send OFF signal to outdoor and send the failure code of drainage system to the wired controller, then the water pump will work until the float switch signal is cancelled.
  • Page 349 Super Match If the fan motor stops, the negative ion generator will stop. 2.2.17 Auto-restart function A: Wired control type: YR-E14: pls refer to the dip switch setting SW1-6: ON means auto-restart unavailable; OFF(default means available. YR-E16:if this function is on, the state before power failure will be in the memory; after restoration of power failure, the unit will continue operating in the state as before the power failure.
  • Page 350 Super Match In cooling mode: In 24 C cooling mode, press SLEEP(or SWING) button 7 times continuously within 5 seconds, indoor buzzer sounds twice, that shows temp. compensation works. Switch on the unit in heating mode by the remote controller, press TEMP button to set the set temp., so temperature compensation=24 C-the current set temp.
  • Page 351: Outdoor Unit Pcb Photo, Dip Switch Setting And Function

    Super Match 3. Outdoor unit PCB photo, dip switch setting and function Outdoor unit PCB photo and dip swith setting Model Power module Filter board 1U24GS1ERA 0011800241C 0011800258G 1U28HS1ERA(S) 0151800054A 0150400908 0150400699 1U28GS2ERA(S) 0011800241S 0011800258H 1U36HS1ERA(S) 0151800054A 0150400908 0150400699 1U48LS1ERA(S) 0151800054A 0150400644A 0150400567...
  • Page 352 Super Match PCB(0011800241C) 1U24GS1ERA...
  • Page 353 Super Match PCB(0011800241S) 1U28GS2ERA(S) 1U28GS2ERA(S)(D)
  • Page 354 Super Match PCB(0151800054A) 1U28HS1ERA(S) 1U36HS1ERA(S) 1U48LS1ERA(S) 1U48LS1ERB(S) 1U48IS1ERB(S) 1U60IS1ERB(S) 1U60IS2ERB(S) PCB(0151800129A) 1U48LS1EAB(S) 1U48IS1EAB(S) 1U60IS1EAB(S) 1U60IS2EAB(S)
  • Page 355 Super Match PCB(0151800076) 3U19FS1ERA 3U24GS1ERA 4U26HS1ERA 4U30HS1ERA 5U34HS1ERA 5U45LS1ERA 3U19FS1ERA(N) 3U24GS1ERA(N) PCB (0151800075) 3U19FS1ERA 3U24GS1ERA 4U26HS1ERA 4U30HS1ERA 5U34HS1ERA 5U45LS1ERA 3U19FS1ERA(N) 3U24GS1ERA(N)
  • Page 356 Super Match Power module(0010400352C) 1U24GS1ERA Power module(0150400908) 1U28HS1ERA(S) 1U36HS1ERA(S) 4U26HS1ERA 4U30HS1ERA 5U34HS1ERA...
  • Page 357 Super Match Power module(0150400644A) 1U48LS1ERA(S) Power module(0150400939) 1U48LS1ERB(S) 1U48IS1ERB(S) 1U60IS1ERB(S) 1U60IS2ERB(S)
  • Page 358 Super Match Power module(0151800105) 5U45LS1ERA Power module(0150400643) 3U19FS1ERA 3U24GS1ERA...
  • Page 359 Super Match Power module(0150400643A) 3U24GS1ERA (N) Power module(0150400643B) 3U19FS1ERA (N)
  • Page 360 Super Match Filter board(0150400699) 1U28HS1ERA(S) 1U36HS1ERA(S) 3U24GS1ERA 4U26HS1ERA 4U30HS1ERA 5U34HS1ERA 3U24GS1ERA(N) 3U19FS1ERA(N) Filter board(0150400567) 1U48LS1ERA(S) 5U45LS1ERA...
  • Page 361 Super Match Filter board(0010452726) 1U48LS1ERB(S) 1U48IS1ERB(S) 1U60IS1ERB(S) Filter board(0150400660) 3U19FS1ERA...
  • Page 362 Super Match Dip switch setting PCB 0151800054A dip switch setting SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description 28K outdoor unit 36K outdoor unit 48K outdoor unit+1U60IS2ERB(S) 60K outdoor unit(except 1U60IS2ERB(S)) Power module choose 1 Power module choose 2 DC fan motor AC fan motor Double fan...
  • Page 363 Super Match Outdoor main PCB 0151800075 dip switch setting Decription Cooling only Heating pump(default) set ON if frost easily set OFF if hard to frost(default) Max.running current is 15A Normal control(default) 3U19 3U24 4U26 4U30 5U34 5U45 temperature correction valid temperature correction null(default) Quiet operation valid Quiet opoperationeration vaild(default)
  • Page 364 Super Match Outdoor main PCB 0151800075 dip switch setting Outdoor central control address Indoor unit terminal 3U*** 4U*** 5U*** Indoor unit centrol control address SW06...
  • Page 365 Super Match 3.2 Outdoor unit control 3.2.1 Outdoor frequency control A. Compressor running frequency range: 1U: 30-91RPS 3U19:20-100RPS 3U24:20-94RPS, the others are 20~95RPS B. defination of high-efficiency operation and its frequency control In order to meet the cooling request at a high ambient temperature and the heating request at low ambient temperature, we set the high-efficiency operation.
  • Page 366 Super Match Indoor modification angle Cooling mode +50degree/30seconds, it will stop until up to the max. permitted C<discharging temp. opening angle C< discharging temp.<=100 C Keep the angle <=90 -5degree/30seconds, and reduce to 0 degree gradually Indoor modification angle Heating mode +50degree/30seconds, it will stop until up to the max.
  • Page 367 Super Match the defrosting temp. sensor Te and outdoor ambient temp. sensor Tao, if they can meet the following condition, entering in defrosting operation. 1. 5 C<(E)<Tao,Te<=-6 C<(E); C,Te≤C×Tao-α; 2. -6 C<(E)<=Tao<=5 Herein :α=8(E) ;C:Tao<0 C;C=0.8; Tao≥0 C,C=0.6; C,Te≤-15 3.Tao<-6 C<(E)and defrosting compressor run for 48 minutes in all.
  • Page 368 Super Match 3.2.6 Defrosting operation flow chart: Unitary Beginning Defrosting FQY 85 Hz ( E) Inverter compressor Indicated FQY Soft startup 50HZ 32HZ Outdoor fan motor Send signal to indoor unit Auto 4-way valve Unload valve SV1 Auto 250pulse(E) PMV auto open angle Auto open angle Indoor fan motor Anti-cold air function...
  • Page 369 Super Match Multi: Beginning Defrosting FQY 80 Hz ( E) Fixed frequency Indicated FQY 60s Soft startup Compressor Outdoor motor Send defrosting signal to indoor Auto 4-way valve 450-pulse 450-pulse 350-pulse(E) All EEVs Auto open angle Auto open angle All indoor motors ON Anti- cold air fun ction...
  • Page 370 Super Match 3.2.7 Frequency control when Td is too high Purpose: make compressor frequency control if the discharging temp. is too high, to lower the discharging temp. efficiently and ensure the system can run normally. Unitary: If keeping for 10s, the unit stops, 3 minutes later, the unit can re-startup.
  • Page 371 Super Match 3.2.8. Frequency control when there is CT over current protection Stop immediately, if abnormal stop 3 times in 1 hour, the unit will stop and alarm. 1.0 I Reduce FQY rapidly 2HZ/S 0.95I Reduce FQY rapidly 1HZ/S 0.93I Reduce FQY slowly 1HZ/10S 0.90I Remain FQY...
  • Page 372 Super Match · When unit stops, the reason that system still checks the low pressure : in a long time stop, make protection for the compressor on the condi tion of great refrigerant leakage. · The reason that low pressure switch action time is 30 seconds: when compressor stops, low pressure does not change, so it will be shorter than the set time in operation.
  • Page 373 Super Match 3.2.11 Oil return operation control Unitary: Entering condition When the compressor running frequency is lower than 58Hz continuously in all and outdoor unit Tcm is lower than 50 degree for 5 hours, the system will enter oil return operation. In the course of mode changeover, manual unit stop or protective unit stop, the time will be accumulative.
  • Page 374 Super Match Quit condition of oil return: 1 minute later after oil return is over & Td‐Tcm>30℃ Ts‐Tc>30℃ Tc<‐35℃ Max. 10 minutes Oil return procedure in heating mode: Send oil return signal oil return beginning oil return over Inverter compressor indicated FQY oil return frequency 120s Soft startup...
  • Page 375 Super Match MULTI: D: Entering condition When the compressor running frequency is lower than 58Hz (E) continuously for 8 hrs, the system will enter oil return operation. In the course of mode changeover, manual unit stop or protective unit stop, the time will be accumulative. After the compressor restarts up, the time will be counted continuously.
  • Page 376 Super Match After oil return in cooling mode, the quit condition of refrigerant eliminated: 1 minute later after oil return is over & ‐ >30℃ Td Tc ‐ >30℃ Ts Tc2AVE ‐ ℃ Tc2AVE< 35 Max. 10 minutes Oil return procedure in heating mode: Send oil return signal oil return begins oil return over...
  • Page 377: Diagnostic Code

    Super Match 4. Diagnostic code 1U24GS1ERA 1U28GS2ERA(S) Flash times of LED on Trouble description Analyze and diagnose mainboard Eeprom failure Outdoor main board eeprom fail IPM failure IPM failure Communication error between main board Communication fail over 4 min and spdu module SPDU Communicition error High pressure protection System high pressure over 4.15 Mpa Module over-voltage protection(only for Spdu)
  • Page 378 Super Match 1U28HS1ERA(S) 1U36HS1ERA(S) 1U48LS1ERA(S) 1U48LS1ERB(S) 1U48IS1ERB(S) 1U60IS1ERB(S) 1U60IS2ERB(S) Malfunction Trouble description Analyze and diagnose Remark code EEPROM faulty Non-resumable Over current protection in course of If it occurs 3 times in 1 hour, confirm the compressor frequency going down Resumable failure, the former twice will not alarm detected by software...
  • Page 379 Super Match Malfunction Trouble description Analyze and diagnose Remark code Over current protection in course of If it occurs 3 times in 1 hour, confirm the compressor fixed speed operation Non-resumable failure, the former twice will not alarm detected by software If it occurs 3 times in 1 hour, confirm the Module temp.
  • Page 380 Super Match 1U48LS1EAB(S) 1U48IS1EAB(S) 1U60IS1EAB(S) 1U60IS2EAB(S) Flash times Trouble description Analyze and diagnose Remark of LED1 EEPROM faulty Wrong EEPROM used Non-resumable Overcurrent after compressor running or power supply phase Compressor overcurrent/ sequence wrong before compressor running.If ir occurs 3 timesin Non-resumable phase sequence wrong 1 hour,confim the failure, the former twice will not alarm.
  • Page 381 Super Match 3U19FS1ERA 3U24GS1ERA 4U26HS1ERA 4U30HS1ERA 5U34HS1ERA 5U45LS1ERA 3U19FS1ERA(N) 3U24GS1ERA(N)
  • Page 382 Super Match Wired controller and pannel error code display when Outdoor unit(3U 4U 5U) conneting indoor units Wired controller Wired controller Panel Outdoor display(Hex-YR- display(Decimal- display(Hex)-- Error code discription E17)---for duct/ YR-E16/YR-E16A)--- -for round way display cassette for duct/cassette cassette Faulty of outdoor unit EEPROM IPM overcurrent or short circuit Communication failure between Module...
  • Page 383 Super Match Wired controller Wired controller Panel Outdoor display(Hex-YR- display(Decimal- display(Hex)-- Error code discription E17)---for duct/ YR-E16/YR-E16A)--- -for round way display cassette for duct/cassette cassette Malfunction of gas pipe temp. sensor for indoor unit C Malfunction of gas pipe temp. sensor for indoor unit D Malfunction of gas pipe temp.
  • Page 384 Super Match Error code for Outdoor unit(3U 4U 5U) conneting 4-way cassette------- ------ AB09CS2ERA AB12/18CS2ERA(S) Round way cassette--- indoor display outdoor error code use the timer and running lamp OR I.D. PCB LED Outdoor Error code discription Timer lamp Running lamp display flash time(I.D.
  • Page 385 Super Match Round way cassette--- indoor display outdoor error code Outdoor use the timer and running lamp OR I.D. PCB LED Error code discription Timer lamp Running lamp display flash time(I.D. PCB flash time(I.D. PCB LED5) LED1) Malfunction of gas pipe temp. sensor for indoor unit A Malfunction of gas pipe temp.
  • Page 386 Super Match Error code for Outdoor unit(3U 4U 5U) conneting the other compact design 4-way cassette(AB*CS1ERA ,AB*ES1ERA) /Convertible unit/Duct unit Compact design 4-way cassette/Convertible unit/Duct unit--- indoor display outdoor error code use the timer and Outdoor running lamp OR I.D. PCB LED Error code discription Timer lamp Running lamp...
  • Page 387 Super Match Compact design 4-way cassette/Convertible unit/Duct unit--- indoor display outdoor error code use the timer and Outdoor running lamp OR I.D. PCB LED Error code discription Timer lamp Running lamp display flash time(I.D. PCB flash time(I.D. PCB LED4) LED3) Malfunction of gas pipe temp.
  • Page 388 Super Match Error code for Outdoor unit(3U 4U 5U) conneting RAC Wall mounted indoor unit Outdoor Error code discription Wall mounted indoor display display Faulty of outdoor unit EEPROM IPM overcurrent or short circuit Communication failure between Module and Module operated overload Module low or high voltage Discharging temperature overheating.Lack of refrigerant, ambient temperature too high...
  • Page 389 Super Match Outdoor LED Error code discription Wall mounted indoor display display Malfunction of gas pipe temp. sensor for indoor unit A Malfunction of gas pipe temp. sensor for indoor unit B Malfunction of gas pipe temp. sensor for indoor unit C Malfunction of gas pipe temp.
  • Page 390 Super Match AD09~24SS1ERA AD09~24SS1ERA(N)(P) AD09~24SS1ERA(N) AD12MS1ERA AD18MS1ERA AD12MS1ERA(D) AD18MS1ERA(D) AD24MS2ERA AD24MS2ERA(D) AD28MS2ERA(S) AD28MS2ERA(S)(D) LED flash times Wired of indoor PCB controller Contents of Malfunction Possible reasons display LED4 LED3 Malfunction of indoor unit Sensor disconected,or broken,or at wrong ambient temperature sensor position,or short circuit Malfunction of indoor unit piping Sensor disconected,or brok- en,or at wrong...
  • Page 391 Super Match AD24MS1ERA AD28~48NS1ERA(S) AD48~60HS1ERA(S) AB09~18CS1ERA(S) AB24~48ES1ERA(S) AB60CS1ERA(S) AB60ES2ERA(S) AC12~24CS1ERA(S) AC28~48ES1ERA(S) AC60FS1ERA(S) AD24MS1ERA(D) LED flash times Wired of indoor PCB controller Contents of Malfunction Possible reasons display LED4 LED3 Malfunction of indoor unit Sensor disconected,or broken,or at wrong ambient temperature sensor position,or short circuit Malfunction of indoor unit piping Sensor disconected,or brok- en,or at wrong...
  • Page 392 Super Match AP48~60KS1ERA(S) LED flash times of Remote indoor PCB receiver Contents of Malfunction display LED4 LED3 Malfunction of indoor unit ambient temperature sensor Malfunction of indoor unit piping temperature sensor EEPROM wrong of indoor PCB Indoor anti-freezed protection Abnormal communication between indo- or and outdoor units Abnormal communication between wired controller and indoor unit Protection of overload of heat mode...
  • Page 393 Super Match INDOOR UNIT TROUBLE SHOOTING AP48DS1ERA(S) LED flash times Pannel Contents of Possible reasons of indoor PCB controller Malfunction display LED4 LED3 Sensor disconected or brok- Malfunction of indoor en,or at wrong position,or unit ambient temper- short circuit ature sensor Sensor disconected or brok- Malfunction of indoor...
  • Page 394: Trouble Shooting

    Super Match 5. Trouble shooting Outdoor EEPROM failure if faulty disappears after powe on again Ckeck outdoor PCB, If faulty ,replace it. IPM over current or short circuit Check if wire of electric box Correct the wiring due to diagram is correct , and if compressor wire is fixed well If compressor is...
  • Page 395 Super Match Communication failure between module ans ECU Check if wire between PCB and power module is Adjust communication wire abnormal Check if communication circuit of PCB is Replace PCB abnormal(if signal LED flashes abnormally) If power module is Replace power module abnormal Solve the failures due to relative information...
  • Page 396 Super Match Voltage too high or low Check if voltage of power Improve power supply circuit supply is normal Check if wiring of Correct the wiring due to diagram electric box is correct In operation, check power module voltage between Replace power module terminal P&N more than 390V or less than 160V...
  • Page 397 Super Match Discharging temperature overheating Check if sensor is fixed well Reconnect Replace pressure switch If sensor resistor/ characteristic is proper Check the piping system Check if the system is clogged If the system is lack of Charge refrigerant refrigerant Check the piping system Check if stop valve is open Reconnet...
  • Page 398 Super Match DC fan motor failure Check if fan motor wires are Replace wire and test again conductive(to CN11 of PCB) Check if motor is Replace PCB running Power off and rotate fan Replace fan motor motor by hand to check if there is obviously friction Test the terminial...
  • Page 399 Super Match temperature sensor failure Check if the corresponding Replace it correctly by after-sales personnel on site. connector of sensor is normal Check if resistance characteristic of the Replace it correctly by after-sales personnel on site. sensor is normal Check if the temperature loop Replace it correctly by after-sales personnel on site.
  • Page 400 Super Match 4-way valve reversing failure If connection between 4-way Reconnect valve and PCB is good If coil of 4-way valve Fix again or replace the sensor fixed well and if its characteristic is correct If system meets Check if compressor is operation condition of 4-way valve reversing: Pd- Ps>0.6Mpa...
  • Page 401 Super Match Compressor out of control circuit Improve power supply circuit Check if voltage of power supply is normal Check if wire between Correct the wiring due to diagram power module and compressor are correct Replace power module If power module is normal If compressor is Repalce compressor normal(compressor coil...
  • Page 402 Super Match Indoor thermal overload If sensor terminal is Reconnect fixed well If sensor resistor / Replace sensor characteristic is proper If indoor air passage is unimpeded Modify air passage Charge refrigerant If system is lack of refrigerant Check the system piping If stop valve is open Reconnect If PMV coil is connection well...
  • Page 403 Super Match Indoor frosted If sensor terminal is Reconnect fixed well If sensor resistor / Replace sensor characteristic is proper If indoor air passage is unimpeded Modify air passage Charge refrigerant If system is lack of refrigerant Check the system piping If stop valve is open Reconnect If EEV coil is connection well...
  • Page 404 Super Match Module thermal overload If screw of module is fixed Correct the wire due to diagram well, Replace power module Compressor startup failure Check if voltage of power Improve power supply circuit supply is normal Check if wire between Correct the wiring due to diagram power module and compressor are correct...
  • Page 405 Super Match Module input over-current Check if wire of electric box is correct, and if compressor wire Correct the wiring due to diagram is fixed well If compressor is Repalce compressor normal(compressor coil resistor, insulation) Replace power module If power module is normal Solve the failures due to relative information MCU reset...
  • Page 406 Super Match Module current detect circuit failure Check if wire between IPM Correct the wire due to diagram and compressor is correct Replace power module Suction temperature too high In heating mode: Check if there is power Replace the O.D. PCB supply output from O.D.
  • Page 407 Super Match High or low pressure switch shut off failure Check if the pressure switch Reconnect connection is ok If the system pressure Replace pressure switch match the condition that pressure switch shut off Make pressure switch close,measure if terminal is conductive by multimeter Check if the system is Check the piping system...
  • Page 408 Super Match Trouble 1: No display on the operation panel Start Check if display Replace display panel and the panel and check unit matched again well If the red diode If the power Check the terminal and green diode terminal block is block and the on indoor PCB 220V input...
  • Page 409 Super Match Trouble 3: Communication failure between indoor and outdoor Start As per the wiring Re-wiring, and diagram, check if check again communication wiring is correct Check if the If the power cable and the PCB is faulty, communication port communication wire are replace and connecting to the...
  • Page 410 Super Match Trouble 8: Outdoor unit alarms sensor failure Start As per the wiring Re-fix the diagram, check if sensor and connection port check again between sensor and PCB is correct Check if the sensor is in open circuit or Check if the Replace sensor sensor resistor...
  • Page 411 Super Match Failure 11: Low pressure switch failure Reason: 1. Too low system pressure causes that the unit stops and the compressor protection works, the failure can be resumed. 2. Pressure switch wire is not fixed well or in open circuit. Start Check if the connector Check if the 2...
  • Page 412: Controller Function

    Super Match 6. Controller function YR-HD Base Operation Remote controller TEMP display Additional functions display Remote controller Supplemented electrical Operation mode QUITE SLEEP HEALTH POWER heating Remote controller . . 9 QUIET but . 0. 0 1. COOL but 2. AUTO but .
  • Page 413 Super Match Sleep Operation 4. In FAN mode It has no SLEEP function. Press button to enter additional options, when Set the wind speed change when sleeping cycle display to will flash. And then press If the wind speed is high or middle before setting for the enter to sleep function.
  • Page 414 Super Match Timer On/Off On-Off Operation All the products are in conformity with the following European provision: 1.After unit starts, select your desired operation mode. - Low Voltage Directive 73/23/EEC 2.Press TIMER button to change TIMER mode. Every - Low Voltage Directive 2006/95/EC time the button is pressed, display changes as follows: -Electomagnetic CompatibilitY 89/336/EEC Remote controller:...
  • Page 415 Super Match YR-E14 Parts and Functions Display of the wire controller Centralized display When controlled by centralized controller, and chosen by "centralize or lock" mode, this information is shown. Air volume display Display the setting speed Running display When the compressor runs, it displays. Standby display Running mode display When the unit is on power and in...
  • Page 416 Super Match Buttons of the wire controller Fan speed switch Mode switch Change wind speed Choose running mode Swing switch Open and close air flap Health switch Used to control oxygen TEMP switch function and negative ion Used for changing set temperature Time switch It is used to regulate setting time.
  • Page 417 Super Match Operation ON/OFF operation Press ON/OFF switch on line controller directly The line controller displays the running state in the latest time (timing and swing state may not be displayed). 1. Press "ON/OFF" switch. The air conditioner starts operating, and the light on the wired controller is on.
  • Page 418 Super Match Present time setting The timing is based on the real time. Thus, the real time should be regulated in advance. The clock regulation steps are as follows: 1.Press "CLOCK" switch "CLOCK" flickers, and the time displayed is the real time. 2.Press "...
  • Page 419 Super Match Timing setting OFF timing: when a set time has elapsed, the unit stops running. Press "ON/OFF" switch firstly, ON timing: when a set time has elapsed, the unit starts. and set up operation mode. Please regulate the clock in advance before using the timing function.
  • Page 420 Super Match Query indoor malfunction history: In the state of power on or power off, press [CHECK] button, enter the malfunction-querying mode of all indoor units in the group. Then [CHECK] and [UNIT NO.] will display, and the actual indoor numbers will be displayed in some sequence (unit number is in decimals).
  • Page 421 Super Match Installation Manual For Wire Controller 1. Take down wire controller from the holder Wire controller Bracket Screw holes Screw holes 2. Install the controller holder According to the position of 2 screw holes on the holder, drill 2 holes on the wall, and strike the wood stopper to the holes respectively.
  • Page 422 Super Match TYPE 2: For other indoor units. Installation Manual For Wire Controller There are three methods to connection wire controller and the indoor units: A.One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the wire controller and the master unit (the indoor unit connected with wire controller directly), the others connect with the master unit through 2 pieces of polar wire.
  • Page 423 Super Match Parts and Functions Key instructions for the wired controller ① ⑥ ② ⑦ ③ ⑧ ④ ⑨ ⑤ ① Up direction key: It provides temperature rise function in the mode switching interface; if this key is pressed in the menu interface, the cursor moves upward;...
  • Page 424 Super Match ⑥ Right function key: According to the function prompt above the key, it provides swing on/off function or air speed (when both the left- right and up-down options are not selected in the air direction setting interface) switching in the mode interface; it provides the confirmation function in the menu interface and it provides the "Next step"...
  • Page 425 Super Match ① Online units display area: it displays the number of the units controlled by one wired controller ② Special function/fault icon display area: such as weekly timer, Swing, sleep, children lock, force, air exchange and energy conservation; each icon corresponds to a function;...
  • Page 426 Super Match •Explanation of the icons of the wired controller •Display and adjustment of air speed 1. Default air speed upon initial energization Dehumidification Mode Cooling Heating Intelligent Automatic Air speed Strong air Weak air Automatic air Weak air 2. Press the "left-right"key to set air speed Strong air: Moderate air: Weak air:...
  • Page 427 Super Match Operation Weekly timer setting: 1. Proceed with main interface→Menu→Weekly timer→"Enter" to enter, which is shown in Figure 1; When the cursors is at " ", press "Enter" key to add a group of timing information; non-initial setting may be displayed as shown in Figure 2;...
  • Page 428 Super Match 3.Time setting of timing switch A. After the timing items for week have been set, each group of set timing information displays 5 seconds cyclically; when it is displayed in the timing information group, press the "Downward" key to initiate the time setting of the timing switch of the current group;...
  • Page 429 Super Match Note: In the time setting state of week timing(cursor still), if no order input for 1 minute, screen saver will be activated and it will automatically return to main interface; In which state, non-conflicting orders are effective and otherwise no interface popping out;...
  • Page 430 Super Match 2. Password setting A. Common users are provided with a four-digit password which is initially 1234; high-class users are provided with a six-digit password 841226 which can be operated by the technical personnel only. B. Press the "upward" key or "downward" key to select "password" and press "Enter" key to initiate password setting, which is shown in Figure8.
  • Page 431 Super Match Fault code query: Proceed through main interface→Menu→Other→enter password→press "Enter" key→Error code→enter 14. The password entry interface is shown in Figure 13 and the entry method is the same as password setting. Figure 13 Figure 14 1. Use the "leftward" key and "rightward" key to check the fault codes inside the unit; where <1> can be 1 to 16, which is the address code within the wired controller group.
  • Page 432 Super Match Air direction setting Figure 16 1. Proceed through main interface→Menu→Swing→press "Enter" key; the default air direction is up/down. If a left/ right air deflector is being controlled, the "left/right" option can be selected. 2. If only the left/right direction is selected when setting the swing function, only the left/right air deflector will swing; if only the up/down direction is selected when setting the swing function, only the up/down air deflector will swing;...
  • Page 433 Super Match Sleep setting Figure 17 1. Proceed through main interface→Menu→Sleep→press "Enter" key to initiate this mode; The default state is shutdown. 2. Use the up ,down, left and right keys to adjust the cursor; The location where the cursor stays has the circle flickering;...
  • Page 434 Super Match Unit number setting (This function is intended for debugging by technical personnel. The wired controller No. with no permission of address setting by indoor DIP switch setting displays grey, with access to checking and no access to changing the communication No.) Figure 18 Figure 19...
  • Page 435 Super Match Mode lock setting 1. Proceed through main interface→Menu→Other →enter password→Mode→press "Enter" key. The default state is "Normal". 2. In single cold mode, only cooling, dehumidification and fan modes can be executed and the intelligent key is ineffective. In single heating mode, only heat and fan modes can be executed and the intelligent key is ineffective. In normal mode, the heating, cooling, dehumidification, fan and intelligent modes can be executed.
  • Page 436 Super Match Additional functions Figure 22 1. Proceed through main interface→Menu→Addition→press "Enter" key to initiate. The default state is shutdown. 2. Ventilation: Some models have the air ventilation and some models do not. For those models that do not have this function, the ventilation setting will not be usable.
  • Page 437 Super Match Temperature compensation (This function is intended for debugging by technical personnel and can only be entered by high-class users) Figure 23 1. Proceed through main interface→Menu→Other→enter the high-class user password→Temp. Compensation→press "Enter" to initiate. 2. When in this interface, use the upward and downward keys to set the temperature value; the range of Celsius degrees is -4°C to 4°C;...
  • Page 438 Super Match Detailed information (The common user password is required for access) 1. Proceed through main interface→Menu→other→enter the password→Details→press "Enter" to initiate. 2. 063 is the address of the wired controller inside the group; if one unit is controlled by one wired controller, the default address is 01;...
  • Page 439 Super Match 5. Unit of temperature: Temperature is set in the units of Celsius degree and Fahrenheit degree. 6. Indoor sensor: Set the temperature source collection for ambient temperature sensor. Differences between the function of the master wired controller and slave wired controller: Comparison Master wired Slave wired controller...
  • Page 440 Super Match Wiring connections of wire controller: Indoor 1 Indoor 2 Indoor N Indoor 15 Indoor 16 (master unit) Wire controller Wire controller Wire controller Wire controller Wire controller Indoor 1 Indoor 1 Control wiring of wire Wire controller Wire controller controller, polar.
  • Page 441 Super Match • Installation of wire controller: 1. Pass the communication cable through the hole of the concealed box. 2. Pass the cable through the back cover of the wired controller at the place No.1. 3. Mounted the back cover on the concealed box by screws. 4.
  • Page 442: Appendix Sensor Characteristic

    Super Match Appendix Sensor characteristic Model Function Part code Characteristic R25=10KΩ±3% Defrost temperature sensor 0010450194 1U28HS1ERA(S) B25/50=3700K±3% 1U36HS1ERA(S) R25=10KΩ±3% Outdoor ambient temperature sensor 0010450192 1U48LS1ERA(S) B25/50=3700K±3% 1U48IS1ERB(S) R80=50KΩ±3% 1U48LS1ERB(S) Discharge temperature sensor 0010451303 B25/50=4450K±3% 1U60IS1ERA(S) R25=10KΩ±3% 1U60IS1ERB(S) Coil temperature sensor 0010451329 B25/50=3700K±3% 1U60IS2ERB(S)
  • Page 443 Super Match Model Function Part code Characteristic AB09CS1ERA AB12CS1ERA (S) AB18CS1ERA (S) AB24ES1ERA (S) R25=23KΩ±3% AB28ES1ERA (S) Indoor ambient 001A3900159 B25/50=4200K±3% AB36ES1ERA (S) temperature sensor AB48ES1ERA (S) AB60CS1ERA (S) AB60ES2ERA(S) AC28ES1ERA (S) AC36ES1ERA (S) AP48DS1ERA (S) AP48KS1ERA (S) AP60KS1ERA (S)
  • Page 444 Super Match R80=50KΦ±3% R80=50KΦ±3% B25/80=4450K±3% B25/80=4450K±3% T ( ℃ ) T ( ℃ ) Rnom (KΦ) Rnom (KΦ) 11600 760.8 10860 722.8 10170 687.3 9529 653.8 8932 8375 7856 553.6 7372 536.6 6920 511.1 6498 486.9 6104 5736 442.3 5392 421.7 5071 402.1...
  • Page 445 Super Match R25=10KΦ±3% R25=10KΦ±3% B25/50=3700K±3% B25/50=3700K±3% T ( ℃ ) T ( ℃ ) Rnom (KΦ) Rnom (KΦ) -20℃ 90.79 7.83 85.72 7.52 80.96 7.23 76.51 6.95 72.33 6.68 68.41 5.43 64.73 61.27 5.59 58.02 5.73 54.97 5.52 52.1 5.32 49.4 5.12 46.86...
  • Page 446 Super Match R25=23KΩ±3%B25/50=4200K±3% Rnom(KΩ) Rnom(KΩ) Rnom(KΩ) Rnom(KΩ) T(℃ ) T(℃ ) T(℃ ) T(℃ ) 149.07 20.94 4.52 1.32 140.35 20.00 4.36 1.28 132.20 19.10 4.21 1.25 124.59 18.24 4.05 1.21 117.46 17.43 3.91 1.18 110.79 16.66 3.77 1.14 104.54 15.93 3.64 1.11...
  • Page 447 Super Match R50=17K±2%B25/50=4170K±3% Rnom(KΩ) Rnom(KΩ) Rnom(KΩ) Rnom(KΩ) T(℃ ) T(℃ ) T(℃ ) T(℃ ) 320.02 45.60 9.96 2.94 301.43 43.55 9.60 2.85 284.05 41.60 9.26 2.77 267.80 39.75 8.93 2.69 252.58 38.00 8.62 2.61 238.33 36.33 8.32 2.54 224.99 34.75 8.03 2.47...
  • Page 448 Haier Commercial Air Condition Web: Http://www.haier.com Haier reserves the right to make change without any notice.