Modbus interface
 Central controller ID setting mode
The central controller ID setting mode changes the central controller ID of the Modbus interface. (central controller
ID at the time of factory shipping is central controller ID 20.)
The central controller ID number indicates the Uh Line address and communication priority for the Uh Line
compatible central control device.
Change the central controller ID in the following cases.
• If using Modbus interface with a central control device not compatible with Uh Line, set the central controller ID
as "old controller."
(1) Transition to central controller ID setting mode
• If setting the Modbus slave address with SW1, make a note of the SW1 value before performing central
controller ID setting operations.
• Turn on bit1 of SW3.
(2) Verification of central controller ID
• If SW1 is set to 0, central controller ID is displayed by LED2 to LED5.
Central controller ID7
Central controller ID8
Central controller ID9
Central controller ID10
Central controller ID11
Central controller ID12
Central controller ID13
Central controller ID14
Central controller ID15
Central controller ID16
Central controller ID17
Central controller ID18
Central controller ID19
Central controller ID20 (initial value)
Old controller
Central controller ID
Installation Manual
=ON,
=OFF
LED5
LED4
LED3
LED2
10-EN