Modbus interface
Modbus-Master
(Locally procured)
A
B
(+)
(-)
The shielded wire of the RS-485
communication cable must be earthed
on address 1
CAUTION: RS-485 communication
cables A(+) and B(-) have polarity.
Be careful when connecting the RS-
485 wires.
7-EN
Do not connect the shielded wire of
Uh Line communication cable to the
earth.
LINK(Uh) U3 and
U4 have no polarity.
RS-485 terminator resistor is set by
Modbus interface of address setting
switch SW1=1 only.
Set the RS-485 terminator resistor on the
address1 unit (Modbus interface address
SW1=1) and host system. Do not set it here.
Uh Line terminator resistor is set on
SW1
the air conditioner side. SW6 should
be OFF.
4
SW5
SW6
U4 U3
U2 U1
U2 U1
SW1
1
SW5
SW6
U4 U3
U2 U1
U2 U1
Set the Modbus interface address with SW1. Assign 1 to
F(15) to each address to avoid duplication.
CAUTION: The SW1 setting is read when the power is
turned on. Push the reset switch SW7 after changing the
address.