Typical power cable specifications (copper) and wiring torque
Harmonic filter
model
PIHF-0004-4-10
PIHF-0007-4-10
PIHF-0012-4-10
PIHF-0015-4-10
PIHF-0030-4-10
PIHF-0045-4-10
PIHF-0075-4-10
PIHF-0090-4-10
PIHF-0160-4-10
PIHF-0205-4-10
300MCM
2x95mm2
PIHF-0290-4-10
2xAWG3/0
PIHF-0363-4-10
2*150mm2
2x300MCM
PIHF-0430-4-10
Parameter setting
Under the default setting of ACS510, the parameter 26.19
the DC voltage regulator) is used for disabling.
The DC voltage regulator is used to prevent possible voltage oscillation in the
DC bus of the frequency converter due to the motor load or weak grid. In case of
voltage fluctuation, the frequency converter will adjust the frequency reference
to stabilize the bus voltage, thereby stabilizing the oscillation of load torque.
When the filter is matched with ACS510 frequency converter, if bus oscillation
occurs, the parameter 26.19 shall be set to ENABLE state to reduce bus
oscillation so as to avoid input phase loss of the frequency converter.
When the filter is matched with ACS530/ACx580/ACS880 frequency converter,
the parameter 97.48 and 227.17 shall be set to obtain the same adjusting effect.
Guide on Installation and Debugging of Filters 13
Incoming and
outgoing line
switching terminal
terminal
U1/V1/W1
U2/V2/W2
1.5mm2
1.5mm2
AWG14
1.1-1.5
6mm2
2.5mm2
N.m
AWG8
10mm2
AWG6
16mm2
2.5-2.8
AWG6
N.m
35mm2
4.3-4.6
AWG3
N.m
120mm2
AWG3/0
150mm2
37.5-
50.8
N.m
AWG2/0
Capacitor
control terminal
A1/B1/C1
A2/B2/C2
AWG14
AWG14
4mm2
1.1-1.5
AWG10
N.m
4mm2
AWG10
6mm2
1.5mm2
AWG8
AWG16
10mm2
AWG6
16mm2
2.5-3
AWG6
N.m
25mm2
AWG3
3.2-3.7
N.m
35mm2
AWG2
70mm2
8-10
N.m
Temperature
T1/T2
1.5mm2
AWG14
6mm2
AWG8
10mm2
AWG6
16mm2
0.6-0.8
AWG6
N.m
70mm2
AWG2/0
95mm2
AWG3/0
150mm2
300MCM
(enabling or disabling
PE
1.1-1.5
N.m
4.2-5.1
N.m
10-13.5
N.m