16 Guide on Installation and Debugging of Filters

Technical data

This chapter describes the technical specifications of the harmonic filter, such
as operating conditions, frame size and parameter settings.
Power connection
Rated voltage
Protection class
Harmonic filtering effect*
Frequency
Insulation class
Overheating protection
Operating conditions
Cooling mode
Ambient temperature
(operating)
Storage temperature
Work altitude
Relative humidity
* In a typical motor drive system, the THDI can be reduced to less than 19% at any load ratio.Under
100% load ratio, the THDI can be controlled below 10%.
Three-phase, U
=380 to 415V +10% to -15%
N
IP00
Under full load conditions, the total harmonic current
distortion at the input of the filter (THDI) is less than 10%
(the background voltage THDU is lower than 2%, and the
ratio between the short-circuit power of the grid and the
installed load is higher than 66)
50 Hz
Overvoltage category III (in accordance with EN61800-5-1)
155 ℃
Air cooling
Under full load, -25 ℃ to +40 ℃
-25 ℃ to +70 ℃
0 to 2000m
0 to 95%, no condensation