ABB Relion 670 Series Applications Manual
Hide thumbs Also See for Relion 670 Series:

Advertisement

Quick Links

®
Relion
670 SERIES
Busbar protection REB670
Version 2.2 ANSI
Application manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 670 Series

  • Page 1 ® Relion 670 SERIES Busbar protection REB670 Version 2.2 ANSI Application manual...
  • Page 3 Document ID: 1MRK 505 370-UUS Issued: June 2021 Revision: K Product version: 2.2 © 2017 - 2021 Hitachi Power Grids. All rights reserved...
  • Page 4 (eay@cryptsoft.com) and Tim Hudson (tjh@cryptsoft.com). Trademarks ABB is a registered trademark of ABB Asea Brown Boveri Ltd. Manufactured by/for a Hitachi Power Grids company. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
  • Page 5 Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with.
  • Page 6 Conformity This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC).
  • Page 7: Table Of Contents

    1MRK 505 370-UUS Rev. K Table of contents Table of contents Section 1 Introduction.......................17 This manual..........................17 Intended audience........................17 Product documentation......................18 1.3.1 Product documentation set......................18 1.3.2 Document revision history....................... 19 1.3.3 Related documents......................... 20 Document symbols and conventions..................20 1.4.1 Symbols...........................20 1.4.2 Document conventions......................21 IEC 61850 edition 1 / edition 2 mapping...................
  • Page 8 Table of contents 1MRK 505 370-UUS Rev. K 4.2.2.3 Example 3.......................... 57 4.2.2.4 Examples on how to connect, configure and set CT inputs for most commonly used CT connections........................61 4.2.2.5 Example on how to connect a wye connected three-phase CT set to the IED ....62 4.2.2.6 Example how to connect delta connected three-phase CT set to the IED......
  • Page 9 1MRK 505 370-UUS Rev. K Table of contents 6.1.3.9 Tripping arrangements......................110 6.1.3.10 Mechanical lock-out function.................... 112 6.1.3.11 Contact reinforcement with heavy duty relays..............113 6.1.3.12 Trip circuit supervision...................... 113 6.1.4 Two-zone busbar arrangements....................113 6.1.4.1 General..........................113 6.1.4.2 Single busbar arrangements.................... 114 6.1.4.3 Single busbar arrangements with sectionalizer..............
  • Page 10 Table of contents 1MRK 505 370-UUS Rev. K 7.2.4.2 Second harmonic restrain....................161 Directional residual overcurrent protection, four steps EF4PTOC (51N/67N)......165 7.3.1 Function revision history......................166 7.3.2 Identification.......................... 166 7.3.3 Setting guidelines........................166 7.3.3.1 Common settings for all steps..................167 7.3.3.2 harmonic restrain......................168 7.3.3.3...
  • Page 11 1MRK 505 370-UUS Rev. K Table of contents 7.10.2 Application..........................211 7.10.2.1 SCB protection......................... 213 7.10.3 Setting guidelines........................214 7.10.3.1 Restrike detection......................217 Section 8 Voltage protection...................219 Two step undervoltage protection UV2PTUV (27)..............219 8.1.1 Identification.......................... 219 8.1.2 Setting guidelines........................219 8.1.2.1 Equipment protection, such as for motors and generators..........219 8.1.2.2...
  • Page 12 Table of contents 1MRK 505 370-UUS Rev. K 8.5.2 Application..........................232 8.5.3 Setting guidelines........................232 8.5.3.1 Advanced users settings....................232 Section 9 Frequency protection..................233 Underfrequency protection SAPTUF (81)................233 9.1.1 Identification.......................... 233 9.1.2 Application..........................233 9.1.3 Setting guidelines........................233 Overfrequency protection SAPTOF (81)................. 234 9.2.1 Identification..........................
  • Page 13 1MRK 505 370-UUS Rev. K Table of contents 11.1.3.3 Negative sequence based....................252 11.1.3.4 Zero sequence based.......................253 11.1.3.5 Delta V and delta I ......................254 11.1.3.6 Dead line detection......................254 11.2 Fuse failure supervision VDSPVC (60)................... 254 11.2.1 Identification.......................... 254 11.2.2 Application..........................255 11.2.3 Setting guidelines........................
  • Page 14 Table of contents 1MRK 505 370-UUS Rev. K 12.2.2.4 Blocking of the auto recloser.................... 284 12.2.2.5 Control of the auto reclosing dead time for shot 1............284 12.2.2.6 Long trip signal......................... 285 12.2.2.7 Maximum number of reclosing shots................285 12.2.2.8 ARMode = 3ph, (normal setting for a three-phase shot)..........285 12.2.2.9 ARMode = 1/2/3ph ......................
  • Page 15 1MRK 505 370-UUS Rev. K Table of contents 12.4.2.3 Signals from bus-coupler....................319 12.4.2.4 Configuration setting......................323 12.4.3 Interlocking for bus-coupler bay ABC_BC (3)............... 323 12.4.3.1 Application ........................323 12.4.3.2 Configuration........................324 12.4.3.3 Signals from all feeders....................324 12.4.3.4 Signals from bus-coupler....................326 12.4.3.5 Configuration setting......................
  • Page 16 Table of contents 1MRK 505 370-UUS Rev. K 12.7.3 Setting guidelines........................353 12.8 Single point generic control 8 signals SPC8GAPC..............353 12.8.1 Identification.......................... 353 12.8.2 Application..........................353 12.8.3 Setting guidelines........................353 12.9 AutomationBits, command function for DNP3.0 AUTOBITS........... 353 12.9.1 Identification.......................... 354 12.9.2 Application..........................354 12.9.3...
  • Page 17 1MRK 505 370-UUS Rev. K Table of contents 13.9 Integer to Boolean 16 conversion IB16................... 364 13.9.1 Identification.......................... 364 13.9.2 Application..........................364 13.10 Integer to Boolean conversion for six-zone busbar BCTZCONN..........365 13.10.1 Identification.......................... 365 13.10.2 Application..........................365 13.11 Integer to Boolean 16 conversion with logic node representation ITBGAPC......367 13.11.1 Identification..........................
  • Page 18 Table of contents 1MRK 505 370-UUS Rev. K 14.3.4 Setting guidelines........................386 14.4 Breaker monitoring SSCBR.....................386 14.4.1 Identification.......................... 386 14.4.2 Application..........................387 14.4.3 Setting guidelines........................389 14.4.3.1 Setting procedure on the IED................... 390 14.5 Event function EVENT......................391 14.5.1 Identification.......................... 391 14.5.2 Application ..........................391 14.5.3 Setting guidelines........................
  • Page 19 1MRK 505 370-UUS Rev. K Table of contents 14.11.4.1 Setting procedure on the IED................... 404 14.12 Fault current and voltage monitoring function FLTMMXU ............405 14.12.1 Function revision history......................405 14.12.2 Identification.......................... 406 14.12.3 Application..........................406 14.12.4 Setting guidelines........................408 14.12.5 Setting example........................408 Section 15 Metering......................413 15.1...
  • Page 20 Table of contents 1MRK 505 370-UUS Rev. K 17.3.3 Bay out of service for maintenance..................432 17.3.4 Setting guidelines........................432 17.3.4.1 Specific settings related to the IEC/UCA 61850-9-2LE communication......432 17.3.4.2 Setting examples for IEC/UCA 61850-9-2LE and time synchronization......433 17.4 LON communication protocol....................
  • Page 21 1MRK 505 370-UUS Rev. K Table of contents 20.1 IED identifiers TERMINALID....................463 20.1.1 Application ..........................463 20.2 Product information PRODINF....................463 20.2.1 Application ..........................463 20.2.2 Factory defined settings......................463 20.3 Measured value expander block RANGE_XP.................464 20.3.1 Identification.......................... 464 20.3.2 Application..........................464 20.3.3 Setting guidelines........................
  • Page 22 Table of contents 1MRK 505 370-UUS Rev. K 20.13.2 Setting guidelines........................479 20.13.2.1 System time........................479 20.13.2.2 Synchronization........................479 20.13.2.3 Process bus IEC/UCA 61850-9-2LE synchronization............481 Section 21 Requirements....................483 21.1 Current transformer requirements................... 483 21.1.1 Current transformer basic classification and requirements........... 483 21.1.2 Conditions..........................
  • Page 23: Introduction

    1MRK 505 370-UUS Rev. K Section 1 Introduction Section 1 Introduction This manual GUID-AB423A30-13C2-46AF-B7FE-A73BB425EB5F v20 The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also provide assistance for calculating settings.
  • Page 24: Product Documentation

    Section 1 1MRK 505 370-UUS Rev. K Introduction Product documentation 1.3.1 Product documentation set GUID-3AA69EA6-F1D8-47C6-A8E6-562F29C67172 v16 Engineering manual Installation manual Commissioning manual Operation manual Application manual Technical manual Communication protocol manual Cyber security deployment guideline IEC07000220-4-en.vsd IEC07000220 V4 EN-US Figure 1: The intended use of manuals throughout the product lifecycle The engineering manual contains instructions on how to engineer the IEDs using the various tools available within the PCM600 software.
  • Page 25: Document Revision History

    1MRK 505 370-UUS Rev. K Section 1 Introduction describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault. The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used.
  • Page 26: Related Documents

    Section 1 1MRK 505 370-UUS Rev. K Introduction 1.3.3 Related documents GUID-94E8A5CA-BE1B-45AF-81E7-5A41D34EE112 v8 Documents related to REB670 Document numbers Application manual : 1MRK 505 370-UUS Commissioning manual : 1MRK 505 372-UUS Product guide 1MRK 505 373-BEN Technical manual ANSI: 1MRK 505 371-UUS Type test certificate ANSI: 1MRK 505 373-TUS 670 series manuals...
  • Page 27: Document Conventions

    1MRK 505 370-UUS Rev. K Section 1 Introduction The information icon alerts the reader of important facts and conditions. The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death.
  • Page 28 Section 1 1MRK 505 370-UUS Rev. K Introduction Function block name Edition 1 logical nodes Edition 2 logical nodes BCZPDIF BCZPDIF BCZPDIF BCZSPDIF BCZSPDIF BCZSPDIF BCZTPDIF BCZTPDIF BCZTPDIF BDCGAPC SWSGGIO BBCSWI BDCGAPC BDZSGAPC BBS6LLN0 LLN0 BDZSGAPC BDZSGAPC BFPTRC_F01 BFPTRC BFPTRC BFPTRC_F02 BFPTRC BFPTRC...
  • Page 29 1MRK 505 370-UUS Rev. K Section 1 Introduction Function block name Edition 1 logical nodes Edition 2 logical nodes BUSPTRC_B2 BUSPTRC BUSPTRC BUSPTRC_B3 BUSPTRC BUSPTRC BUSPTRC_B4 BUSPTRC BUSPTRC BUSPTRC_B5 BUSPTRC BUSPTRC BUSPTRC_B6 BUSPTRC BUSPTRC BUSPTRC_B7 BUSPTRC BUSPTRC BUSPTRC_B8 BUSPTRC BUSPTRC BUSPTRC_B9 BUSPTRC BUSPTRC...
  • Page 30 Section 1 1MRK 505 370-UUS Rev. K Introduction Function block name Edition 1 logical nodes Edition 2 logical nodes BZNSPDIF_A BZNSPDIF BZASGAPC BZASPDIF BZNSGAPC BZNSPDIF BZNSPDIF_B BZNSPDIF BZBSGAPC BZBSPDIF BZNSGAPC BZNSPDIF BZNTPDIF_A BZNTPDIF BZATGAPC BZATPDIF BZNTGAPC BZNTPDIF BZNTPDIF_B BZNTPDIF BZBTGAPC BZBTPDIF BZNTGAPC BZNTPDIF...
  • Page 31 1MRK 505 370-UUS Rev. K Section 1 Introduction Function block name Edition 1 logical nodes Edition 2 logical nodes GUPPDUP GUPPDUP GUPPDUP PH1PTRC INDCALH INDCALH INDCALH ITBGAPC IB16FCVB ITBGAPC L4UFCNT L4UFCNT L4UFCNT LD0LLN0 LLN0 LOVPTUV LOVPTUV LOVPTUV LPHD LPHD MVGAPC MVGGIO MVGAPC NS4PTOC...
  • Page 32 Section 1 1MRK 505 370-UUS Rev. K Introduction Function block name Edition 1 logical nodes Edition 2 logical nodes SP16GAPC SP16GGIO SP16GAPC SPC8GAPC SPC8GGIO SPC8GAPC SPGAPC SPGGIO SPGAPC SSCBR SSCBR SSCBR SSIMG SSIMG SSIMG SSIML SSIML SSIML SXCBR SXCBR SXCBR SXSWI SXSWI SXSWI...
  • Page 33: Application

    1MRK 505 370-UUS Rev. K Section 2 Application Section 2 Application General IED application SEMOD121007-5 v9 The Intelligent Electronic Device (IED) is designed for the selective, reliable and fast differential protection of busbars, T-connections and meshed corners in up to 6 zones. It can be used for protection of single, double and triple busbar with or without transfer bus, double circuit breaker or breaker-and-a- half stations.
  • Page 34 Section 2 1MRK 505 370-UUS Rev. K Application pickup can be used when high sensitivity is required from busbar differential protection (that is, energizing of the bus via long line). Overall operating characteristic of the differential function in the IED is shown in figure 2. Sensitive differential protection...
  • Page 35 1MRK 505 370-UUS Rev. K Section 2 Application Optionally available circuit breaker failure protection, one for every CT input into the IED, offers secure local back-up protection for the circuit breakers in the station. Optionally available four-stage, non-directional overcurrent protections, one for every CT input into the IED, provide remote backup functionality for connected feeders and remote-end stations.
  • Page 36: Main Protection Functions

    Section 2 1MRK 505 370-UUS Rev. K Application GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 The following tables list all the functions available in the IED. Those functions that are not exposed to the user or do not need to be configured are not described in this manual.
  • Page 37: Back-Up Protection Functions

    1MRK 505 370-UUS Rev. K Section 2 Application Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v17 IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) Current protection OC4PTOC Directional phase overcurrent protection, four steps 51_67 PH4SPTOC Single phase overcurrent protection, four steps 0-24 EF4PTOC 51N_67N...
  • Page 38: Control And Monitoring Functions

    Section 2 1MRK 505 370-UUS Rev. K Application Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v21 IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser APC30 Control functionality for up to 6 bays, max 30 objects (6CBs), including interlocking (see Table 4) QCBAY Bay control...
  • Page 39 1MRK 505 370-UUS Rev. K Section 2 Application IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) Logic TMAGAPC Trip matrix logic ALMCALH Logic for group alarm WRNCALH Logic for group warning INDCALH Logic for group indication AND, GATE, INV, Basic configurable logic blocks (see Table 3) 40-496 LLD, OR,...
  • Page 40 Section 2 1MRK 505 370-UUS Rev. K Application IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) POL_REC Polar to rectangular converter RAD_DEG Radians to degree angle converter CONST_REAL Definable constant for logic functions REALSEL Analog input selctor for real values STOREINT Store value for integer inputs STOREREAL...
  • Page 41 1MRK 505 370-UUS Rev. K Section 2 Application IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) I103EF Function status earth-fault for IEC 60870-5-103 I103FLTPROT Function status fault protection for IEC 60870-5-103 I103IED IED status for IEC 60870-5-103 I103SUPERV Supervison status for IEC 60870-5-103...
  • Page 42 Section 2 1MRK 505 370-UUS Rev. K Application Table 4: Number of function instances in APC30 Function name Function description Total number of instances SCILO Interlocking BB_ES A1A2_BS A1A2_DC ABC_BC BH_CONN BH_LINE_A BH_LINE_B DB_BUS_A DB_BUS_B DB_LINE ABC_LINE AB_TRAFO SCSWI Switch controller SXSWI Circuit switch QCRSV...
  • Page 43: Communication

    1MRK 505 370-UUS Rev. K Section 2 Application Configurable logic blocks Q/T Total number of instances SRMEMORYQT TIMERSETQT XORQT Table 6: Total number of instances for extended logic package Extended configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SLGAPC SRMEMORY TIMERSET...
  • Page 44 Section 2 1MRK 505 370-UUS Rev. K Application IEC 61850 or function ANSI Function description Busbar name REB670 (Customized) IEC 61850SIM IEC 61850 simulation mode GOOSEBINRCV GOOSE binary receive GOOSEDPRCV GOOSE function block to receive a double point value GOOSEINTRCV GOOSE function block to receive an integer value GOOSEMVRCV GOOSE function block to receive a measurand value...
  • Page 45: Basic Ied Functions

    1MRK 505 370-UUS Rev. K Section 2 Application IEC 61850 or function ANSI Function description Busbar name REB670 (Customized) BSR2M_305 Binary signal transfer, 2Mbit receive BSR2M_312 BSR2M_322 BSR2M_306 BSR2M_313 BSR2M_323 BST2M_305 Binary signal transfer, 2Mbit transmit BST2M_312 BST2M_322 BST2M_306 BST2M_313 BST2M_323 LDCMTRN Transmission of analog data from LDCM...
  • Page 46 Section 2 1MRK 505 370-UUS Rev. K Application IEC 61850 or function Description name DSTENABLE Enables or disables the use of daylight saving time DSTEND GPS time synchronization module IRIG-B Time synchronization SETGRPS Number of setting groups ACTVGRP Active parameter setting group TESTMODE Test mode functionality CHNGLCK...
  • Page 47 1MRK 505 370-UUS Rev. K Section 2 Application Table 8: Local HMI functions IEC 61850 or function Description name LHMICTRL Local HMI signals LANGUAGE Local human machine language SCREEN Local HMI Local human machine screen behavior FNKEYTY1–FNKEYTY5 Parameter setting function for HMI in PCM600 FNKEYMD1–...
  • Page 49: Configuration

    1MRK 505 370-UUS Rev. K Section 3 Configuration Section 3 Configuration Description of configuration REB670 SEMOD129261-1 v2 3.1.1 Available ACT configurations for pre-configured REB670 SEMOD129275-87 v6 Three configurations have been made available for pre-configured REB670 IED with two zones. Product variant with six zone is available as customized product only.
  • Page 50: Description Of 3 Ph Package A20A

    Section 3 1MRK 505 370-UUS Rev. K Configuration disconnector/breaker supervision is available. This configuration is available for only three REB670 variants (that is A31, B21 and B31). In order to use X03 configuration, optional breaker failure and overcurrent functions must be ordered. 3.1.5 Description of 3 ph package A20A SEMOD129275-4 v8...
  • Page 51: Description Of 3 Ph Package A31A

    1MRK 505 370-UUS Rev. K Section 3 Configuration 3.1.6 Description of 3 ph package A31A SEMOD129275-22 v9 Three-phase version of the IED with two low-impedance differential protection zones and eight three- phase CT inputs A31A. The version is intended for applications on smaller busbars, with up to two zones and eight CT inputs.
  • Page 52 Section 3 1MRK 505 370-UUS Rev. K Configuration A31 X01 A31 X01 REB670(A31-X01) REB670(A31-X01) REB670(A31-X01) DFR/SER DR DFR/SER DR DFR/SER DR DFR/SER DR DRP RDRE DRP RDRE DRP RDRE DRP RDRE 3Id/I 3Id/I 3Id/I 3Id/I 3Id/I 3Id/I 3Id/I 3Id/I HW LOGIC HW LOGIC HW LOGIC BZIT GGIO...
  • Page 53 1MRK 505 370-UUS Rev. K Section 3 Configuration A31 X02 REB670(A31-X02) DFR/SER DR DRP RDRE BDC GAPC BDC GAPC BDC GAPC BDC GAPC BDC GAPC BDC GAPC BDC GAPC 3Id/I BZIT GGIO 3Id/I C MMXU BUT PTRC 3Id/I BZNT PDIF 3Id/I C MMXU BUT PTRC...
  • Page 54: Description Of 1 Ph Package B20A

    Section 3 1MRK 505 370-UUS Rev. K Configuration A31 X03 REB670(A31-X03) BDC GAPC DFR/SER DR BDC GAPC DRP RDRE BDC GAPC BDC GAPC BDC GAPC BDC GAPC BDC GAPC 3Id/I BZIT GGIO C MMXU 51_67 4(3I>) 50BF 3I>BF 3Id/I OC4 PTOC CC RBRF BUT PTRC 3Id/I...
  • Page 55 1MRK 505 370-UUS Rev. K Section 3 Configuration breaker-and-a-half or double breaker arrangements. Three such IEDs offer cost effective solutions for such simple substation arrangements with up to twelve CT inputs. • This version can be used with external auxiliary 3-phase to 1-phase summation current transformers with different turns ratio for each phase.
  • Page 56: Description Of 1 Ph Package B31A

    Section 3 1MRK 505 370-UUS Rev. K Configuration REB670(B20-X01) /REB670(B21-X01) / REB670(B31-X01) PHASE L3 REB670(B20-X01) /REB670(B21-X01) / REB670(B31-X01) PHASE L2 REB670(B20-X01) /REB670(B21-X01) / REB670(B31-X01) PHASE L1 DFR/SER DR DRP RDRE HW LOGIC Id/I Id/I AC LOGIC BZIS GGIO BCZS PDIF Id/I C MMXU BUS PTRC...
  • Page 57 1MRK 505 370-UUS Rev. K Section 3 Configuration • The IED is intended for busbar protection applications in big substations where dynamic Zone Selection, quite large number of binary inputs and outputs and many CT inputs are needed. The IED includes two differential zones and twenty-four CT inputs.
  • Page 58 Section 3 1MRK 505 370-UUS Rev. K Configuration REB670(B20-X01) / REB670(B21-X01) / REB670(B31-X01) PHASE L3 REB670(B20-X01) / REB670(B21-X01) / REB670(B31-X01) PHASE L2 REB670(B20-X01) / REB670(B21-X01) / REB670(B31-X01) PHASE L1 DFR/SER DR HW LOGIC DRP RDRE AC LOGIC Id/I Id/I BZIS GGIO BCZS PDIF Id/I C MMXU...
  • Page 59 1MRK 505 370-UUS Rev. K Section 3 Configuration B31 X02 REB670(B21-X02)/REB670(B31-X02)- PHASE L3 REB670(B21-X02)/REB670(B31-X02)- PHASE L2 REB670(B21-X02)/REB670(B31-X02)- PHASE L1 BDC GAPC DFR/SER DR DRP RDRE BDC GAPC BDC GAPC BDC GAPC BDC GAPC BDC GAPC BDC GAPC Id/I BZIS GGIO Id/I C MMXU BUS PTRC...
  • Page 60 Section 3 1MRK 505 370-UUS Rev. K Configuration B31 X03 REB670(B21-X03)/REB670(B31-X03)- PHASE L3 REB670(B21-X03)/REB670(B31-X03)- PHASE L2 REB670(B21-X03)/REB670(B31-X03)- PHASE L1 BDC GAPC DFR/SER DR BDC GAPC DRP RDRE BDC GAPC BDC GAPC BDC GAPC BDC GAPC Id/I BDC GAPC BZIS GGIO C MMXU I>...
  • Page 61: Analog Inputs

    1MRK 505 370-UUS Rev. K Section 4 Analog inputs Section 4 Analog inputs Introduction SEMOD55003-5 v11 Analog input channels must be configured and set properly in order to get correct measurement results and correct protection operations. For power measuring, all directional and differential functions, the directions of the input currents must be defined in order to reflect the way the current transformers are installed/connected in the field ( primary and secondary connections ).
  • Page 62: Setting Of Current Channels

    Section 4 1MRK 505 370-UUS Rev. K Analog inputs For a TRM with 6 current and 6 voltage inputs the first VT channel is 7. The setting PhaseAngleRef=7 shall be used if the phase reference voltage is connected to that channel. 4.2.2 Setting of current channels SEMOD55055-16 v6...
  • Page 63: Example 2

    1MRK 505 370-UUS Rev. K Section 4 Analog inputs Line Transformer Line Reverse Forward Definition of direction for directional functions Transformer protection Line protection Setting of current input: Setting of current input: Setting of current input: Set parameter Set parameter Set parameter CT_WyePoint with CT_WyePoint with...
  • Page 64 Section 4 1MRK 505 370-UUS Rev. K Analog inputs Transformer Line Forward Reverse Definition of direction for directional Transformer and line functions Line protection Setting of current input: Setting of current input: Set parameter Set parameter CT_WyePoint with CT_WyePoint with Transformer as Transformer as reference object.
  • Page 65 1MRK 505 370-UUS Rev. K Section 4 Analog inputs Transformer Line Reverse Forward Definition of direction for directional Transformer and line functions Line protection Setting of current input for line functions: Set parameter CT_WyePoint with Line as reference object. Setting of current input Setting of current input Correct setting is for transformer functions:...
  • Page 66 Section 4 1MRK 505 370-UUS Rev. K Analog inputs Busbar Busbar Protection en06000196_ansi.vsd ANSI06000196 V1 EN-US Figure 18: Example how to set CT_WyePoint parameters in the IED For busbar protection, it is possible to set the CT_WyePoint parameters in two ways. The first solution will be to use busbar as a reference object.
  • Page 67 1MRK 505 370-UUS Rev. K Section 4 Analog inputs • CTprim = 1000 (value in A) • CTsec =5 (value in A). 4.2.2.4 Examples on how to connect, configure and set CT inputs for most commonly used CT connections SEMOD55055-296 v7 Figure defines the marking of current transformer terminals commonly used around the world: In the SMAI function block, you have to set if the SMAI block is measuring current or...
  • Page 68 Section 4 1MRK 505 370-UUS Rev. K Analog inputs It is recommended to: • use 1A rated CT input into the IED in order to connect CTs with 1A and 2A secondary rating • use 5A rated CT input into the IED in order to connect CTs with 5A and 10A secondary rating 4.2.2.5 Example on how to connect a wye connected three-phase CT set to the IED...
  • Page 69 1MRK 505 370-UUS Rev. K Section 4 Analog inputs Where: The drawing shows how to connect three individual phase currents from a wye connected three-phase CT set to the three CT inputs of the IED. The current inputs are located in the TRM. It shall be noted that for all these current inputs the following setting values shall be entered for the example shown in Figure 20.
  • Page 70 Section 4 1MRK 505 370-UUS Rev. K Analog inputs SMAI_20_2 BLOCK AI3P REVROT ^GRP2_A ^GRP2_B ^GRP2_C CT 800/1 ^GRP2N Wye Connected Protected Object ANSI11000026-5-en-.vsd ANSI11000026 V5 EN-US Figure 21: Wye connected three-phase CT set with its wye point away from the protected object In the example, everything is done in a similar way as in the above described example (Figure 20).
  • Page 71 1MRK 505 370-UUS Rev. K Section 4 Analog inputs SMAI2 BLOCK AI3P REVROT ^GRP2_A ^GRP2_B ^GRP2_C ^GRP2_N CT 800/1 Star Connected Protected Object ANSI06000644-3-en.vsdx ANSI06000644 V3 EN-US Figure 22: Wye connected three-phase CT set with its wye point away from the protected object and the residual/ neutral current connected to the IED Where: Shows how to connect three individual phase currents from a wye connected three-phase CT set to the three...
  • Page 72 Section 4 1MRK 505 370-UUS Rev. K Analog inputs Is a connection made in the Signal Matrix tool (SMT) and Application configuration tool (ACT), which connects the residual/neutral current input to the fourth input channel of the preprocessing function block 6). Note that this connection in SMT shall not be done if the residual/neutral current is not connected to the IED.
  • Page 73 1MRK 505 370-UUS Rev. K Section 4 Analog inputs Where: shows how to connect three individual phase currents from a delta connected three-phase CT set to three CT inputs of the IED. is the TRM where these current inputs are located. It shall be noted that for all these current inputs the following setting values shall be entered.
  • Page 74 Section 4 1MRK 505 370-UUS Rev. K Analog inputs SMAI2 I_A-I_C BLOCK AI3P REVROT I_B-I_A ^GRP2_A I_C-I_B ^GRP2_B ^GRP2_C ^GRP2_N Protected Object ANSI11000028-4-en.vsdx ANSI11000028 V4 EN-US Figure 24: Delta DAC connected three-phase CT set In this case, everything is done in a similar way as in the above described example, except that for all used current inputs on the TRM the following setting parameters shall be entered: =800A prim...
  • Page 75 1MRK 505 370-UUS Rev. K Section 4 Analog inputs Protected Object SMAI_20_2 BLOCK AI3P REVROT ^GRP2_A ^GRP2_B ^GRP2_C ^GRP2_N ANSI11000029-3-en.vsd ANSI11000029 V3 EN-US Figure 25: Connections for single-phase CT input Where: shows how to connect single-phase CT input in the IED. is TRM where these current inputs are located.
  • Page 76 Section 4 1MRK 505 370-UUS Rev. K Analog inputs short circuit current) the rated current of the protected object is less than 40% of the rated CT primary current, it is strongly recommended to set the parameter IBase in the IED to be equal to the largest rated CT primary current among all CTs involved in the protection scheme and installed on the same voltage level.
  • Page 77 1MRK 505 370-UUS Rev. K Section 4 Analog inputs Where: is the symbol and terminal marking used in this document. Terminals marked with a square indicate the primary and secondary winding terminals with the same (positive) polarity is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-ground connected is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open delta connected VTs is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-phase connected VTs It shall be noted that depending on national standard and utility practices the rated secondary voltage of...
  • Page 78 Section 4 1MRK 505 370-UUS Rev. K Analog inputs AI 07 (I) SMAI2 BLOCK AI3P AI 08 (V) ^GRP2_A ^GRP2_B AI 09 (V) ^GRP2_C ^GRP2N #Not used AI 10 (V) TYPE AI 11 (V) AI 12 (V) ANSI06000599-2-en.vsd ANSI06000599 V2 EN-US Figure 27: A Three phase-to-ground connected VT SMAI2...
  • Page 79 1MRK 505 370-UUS Rev. K Section 4 Analog inputs Where: shows how to connect three secondary phase-to-ground voltages to three VT inputs on the IED is the TRM where these three voltage inputs are located. For these three voltage inputs, the following setting values shall be entered: VTprim =132 kV VTsec = 110 V...
  • Page 80 Section 4 1MRK 505 370-UUS Rev. K Analog inputs 13.8 13.8 AI 07(I) SMAI2 BLOCK AI3P AI 08 (V) ^GRP2_A (A-B) ^GRP2_B (B-C) AI 09 (V) ^GRP2_C (C-A) ^GRP2N #Not Used TYPE AI 10(V) AI 11(V) AI 12(V) ANSI06000600-3-en.vsd ANSI06000600 V3 EN-US Figure 29: A Two phase-to-phase connected VT Where:...
  • Page 81 1MRK 505 370-UUS Rev. K Section 4 Analog inputs are three connections made in the Signal Matrix tool (SMT), Application configuration tool (ACT), which connects these three voltage inputs to first three input channels of the preprocessing function block 5). Depending on the type of functions, which need this voltage information, more than one preprocessing block might be connected in parallel to these three VT inputs shows that in this example the fourth (that is, residual) input channel of the preprocessing block is not...
  • Page 82 Section 4 1MRK 505 370-UUS Rev. K Analog inputs AI 07 (I) AI 08 (V) SMAI2 AI 09 (V) BLOCK AI3P ^GRP2_A # Not Used AI 10 (V) ^GRP2_B # Not Used ^GRP2_C # Not Used AI 11 (V) +3Vo ^GRP2N TYPE AI 12 (V)
  • Page 83 1MRK 505 370-UUS Rev. K Section 4 Analog inputs Where: shows how to connect the secondary side of the open delta VT to one VT input on the IED. +3Vo shall be connected to the IED is the TRM where this voltage input is located. It shall be noted that for this voltage input the following setting values shall be entered: ×...
  • Page 84 Section 4 1MRK 505 370-UUS Rev. K Analog inputs Ph Ph Ph Gnd (Equation 7) EQUATION1927-ANSI V1 EN-US The primary rated voltage of such VT is always equal to VPh-Gnd. Therefore, three series connected VT secondary windings will give the secondary voltage equal only to one individual VT secondary winding rating.
  • Page 85 1MRK 505 370-UUS Rev. K Section 4 Analog inputs Where: shows how to connect the secondary side of open delta VT to one VT input in the IED. +3Vo shall be connected to the IED. is TRM where this voltage input is located. It shall be noted that for this voltage input the following setting values shall be entered: ×...
  • Page 86 Section 4 1MRK 505 370-UUS Rev. K Analog inputs In case of a solid ground fault in high impedance grounded or ungrounded systems the primary value of voltage will be equal to: (Equation 11) EQUATION1932 V2 EN-US Figure 32gives an overview of required actions by the user in order to make this measurement available to the built-in protection and control functions within the IED.
  • Page 87 1MRK 505 370-UUS Rev. K Section 4 Analog inputs Where: shows how to connect the secondary side of neutral point VT to one VT input in the IED. shall be connected to the IED. is the TRM or AIM where this voltage input is located. For this voltage input the following setting values shall be entered: VTprim 3.81...
  • Page 89 1MRK 505 370-UUS Rev. K Section 5 Local HMI Section 5 Local HMI AMU0600442 v15 ANSI13000239-2-en.vsd ANSI13000239 V2 EN-US Figure 33: Local human-machine interface The LHMI of the IED contains the following elements • Keypad • Display (LCD) • LED indicators •...
  • Page 90 Section 5 1MRK 505 370-UUS Rev. K Local HMI Display GUID-55739D4F-1DA5-4112-B5C7-217AAF360EA5 v13 The LHMI includes a graphical monochrome liquid crystal display (LCD) with a resolution of 320 x 240 pixels. The character size can vary. The display view is divided into four basic areas. IEC15000270-1-en.vsdx IEC15000270 V1 EN-US Figure 34:...
  • Page 91 1MRK 505 370-UUS Rev. K Section 5 Local HMI IEC13000281-1-en.vsd GUID-C98D972D-D1D8-4734-B419-161DBC0DC97B V1 EN-US Figure 35: Function button panel The indication LED panel shows on request the alarm text labels for the indication LEDs. Three indication LED pages are available. IEC13000240-1-en.vsd GUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN-US Figure 36: Indication LED panel...
  • Page 92 Section 5 1MRK 505 370-UUS Rev. K Local HMI There are 15 programmable indication LEDs on the front of the LHMI. Each LED can indicate three states with the colors: green, yellow and red. The texts related to each three-color LED are divided into three panels.
  • Page 93 1MRK 505 370-UUS Rev. K Section 5 Local HMI ANSI15000157-1-en.vsdx ANSI15000157 V1 EN-US Figure 38: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port 1...5 Function button Close Open Escape Left Down Right Enter Remote/Local Uplink LED Not in use Multipage Menu...
  • Page 94 Section 5 1MRK 505 370-UUS Rev. K Local HMI Communication port Programmable indication LEDs IED status LEDs Local HMI functionality 5.4.1 Protection and alarm indication GUID-09CCB9F1-9B27-4C12-B253-FBE95EA537F5 v18 Protection indicators The protection Target LEDs are Normal, Pickup and Trip. The yellow and red status LEDs are configured in the digital fault recorder function, DRPRDRE, by connecting a pickup or trip signal from the actual function to a BxRBDR binary input function block using the PCM600 and configure the setting to Disabled,Pickup or Trip for that particular signal.
  • Page 95 1MRK 505 370-UUS Rev. K Section 5 Local HMI Alarm indicators The 15 programmable three-color LEDs are used for alarm indication. An individual alarm/status signal, connected to any of the LED function blocks, can be assigned to one of the three LED colors when configuring the IED.
  • Page 96 Section 5 1MRK 505 370-UUS Rev. K Local HMI IEC13000280-1-en.vsd GUID-94AF2358-6905-4782-B37B-ACD3DCBF7F9C V1 EN-US Figure 39: RJ-45 communication port and green indicator LED 1 RJ-45 connector 2 Green indicator LED The default IP address for the IED front port is 10.1.150.3 and the corresponding subnetwork mask is 255.255.255.0.
  • Page 97 1MRK 505 370-UUS Rev. K Section 6 Differential protection Section 6 Differential protection Busbar differential protection SEMOD121185-1 v2 6.1.1 Identification SEMOD130380-4 v4 Two-zone busbar differential protections, four-or-eight three-phase CTs Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Busbar protection 2Z-3Ph-4/8CT, BZNTPDIF_x, differential protection function...
  • Page 98 Section 6 1MRK 505 370-UUS Rev. K Differential protection GUID-F771BD7B-53F1-437A-A41C-7266323DC02F v1 Two-zone busbar differential protections, twelve-or-twenty-four single-phase Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Busbar protection 2Z-1Ph-12/24CT, BZNSPDIF_x, differential protection function (x = A, B) Id/I IEC16000110 V1 EN-US Busbar protection 2Z-1Ph-12/24CT,...
  • Page 99 1MRK 505 370-UUS Rev. K Section 6 Differential protection 6.1.2 Basic applications SEMOD127448-1 v1 6.1.2.1 General M12097-3 v3 Basic types of applications for REB670 IED are shown and described in this chapter. For these applications usually three phase version of the IED, with two differential zones and four (or even eight) 3- phase CT inputs, is used.
  • Page 100 Section 6 1MRK 505 370-UUS Rev. K Differential protection the similar effect from the operational point of view as simultaneous faults on all power system elements connected to the bus. On the other hand, the IED has to be dependable as well. Failure to operate or even slow operation of the differential IED, in case of an actual internal fault, can have serious consequences.
  • Page 101 1MRK 505 370-UUS Rev. K Section 6 Differential protection Consequently, all these phenomena have to be considered during the design stage of a busbar differential IED in order to prevent the unwanted operation of the IED during external fault conditions. The analog generation of the busbar differential IEDs ( KA2, 87B, RADHA, RADSS, REB 103) generally solves all these problems caused by the CT non-linear characteristics by using the galvanic connection between the secondary circuits of all CTs connected to the protected zone.
  • Page 102 Section 6 1MRK 505 370-UUS Rev. K Differential protection or three-phase faults, which can cause CT saturation. Comparison between these two characteristics is shown in Figure 41. Sensitive differential protection Operate region Differential protection operation characteristic DiffOperLevel SensIinBlock SensOperLevel s=0.53 [Primary Amps] IEC06000142-2-en.vsdx IEC06000142 V2 EN-US...
  • Page 103 1MRK 505 370-UUS Rev. K Section 6 Differential protection will detect faults anywhere in the substation but cannot distinguish in which part of the station the fault is located. When the check zone detects a fault it gives a release signal to the busbar protection relays in all individual, discriminating zones.
  • Page 104 Section 6 1MRK 505 370-UUS Rev. K Differential protection • In two-zone busbar differential protections, it is freely settable by using the setting CheckZoneSel at each bay function block. • In six-zone busbar differential protection, the currents of all active feeder bays are measured unconditionally by the check zone, if the check zone is able to operate.
  • Page 105 1MRK 505 370-UUS Rev. K Section 6 Differential protection • Normally closed auxiliary contact • “b” contact (that is, 52b) • “open” Typically both contacts are used to provide position indication and supervision for busbar protection. SEMOD127523-18 v2 Minimum contact requirements The minimum requirement for the busbar replica is the record of the disconnector position by using just one auxiliary contact, either "normally open"...
  • Page 106 Section 6 1MRK 505 370-UUS Rev. K Differential protection Table 13: Treatment of primary object auxiliary contact status within BBP in REB670 Primary equipment Status in busbar Alarm facility protection Normally Normally when when Alarm after Information visible on Open Closed “Scheme 1 “Scheme 2...
  • Page 107 1MRK 505 370-UUS Rev. K Section 6 Differential protection arcing possible closed open N.O. input „closed“ N.C. input „open“ current assignment 1) disconnector supervision running 2) BI „closed“ should change before arcing distance en06000085.vsd IEC06000085 V1 EN-US Figure 44: Scheme2_INX Circuit breaker replica SEMOD127523-79 v3 The circuit breaker position from a bay shall be given to the busbar protection when the position of this...
  • Page 108 Section 6 1MRK 505 370-UUS Rev. K Differential protection Such feeder set-up can be often found in GIS stations where cable CTs are used for busbar protection. If in such feeder the line disconnector 989 is open and then immediately the grounding switch 189G is closed before the busbar disconnectors 189G &...
  • Page 109 1MRK 505 370-UUS Rev. K Section 6 Differential protection • included to the differential zone A when input signal CTRLZA on corresponding bay block is given logical value one and it will be excluded from the differential zone A when input signal CTRLZA on corresponding bay block is given logical value zero.
  • Page 110 Section 6 1MRK 505 370-UUS Rev. K Differential protection breaker status. However with modern busbar protection it is possible to disconnect both CTs from the relevant zones when the bus-section or bus-coupler circuit breaker is open. This will insure that if internal fault happen, in the overlapping zone, while breaker is open, only the faulty zone will be tripped while other busbar section will remain in service.
  • Page 111 1MRK 505 370-UUS Rev. K Section 6 Differential protection both CT inputs on the bus section or bus coupler function block, and then invert one of them in software by using the parameter setting OperMode in PST. This shall be done taking into account the actual location of the CT star point in this bay.
  • Page 112 Section 6 1MRK 505 370-UUS Rev. K Differential protection With GIS or live tank circuit breakers, owing to high cost of HV CT installations, sometimes no current transformers are available in bus-section or bus-coupler bay. This is the third solution shown in Figure en04000283_ansi.vsd ANSI04000283 V1 EN-US Figure 49:...
  • Page 113 1MRK 505 370-UUS Rev. K Section 6 Differential protection 6.1.3.7 End fault protection SEMOD127750-31 v4 When Live tank CBs or GIS are involved, there is a physical separation between the CT and the CB. End Fault Protection is related to primary faults between main CT and CB in a feeder bay. Therefore, it is directly related to the position of the main CT in feeder bay.
  • Page 114 Section 6 1MRK 505 370-UUS Rev. K Differential protection xx06000139_ansi.vsd ANSI06000139 V1 EN-US Figure 52: Busbar protection measuring and fault clearing boundaries where: Busbar Protection measuring boundary determined by feeder CT locations Busbar Protection internal fault clearing boundary determined by feeder CB locations End fault region for feeders as shown in Figure 51/B End fault region for feeders as shown in Figure 51/C Figure...
  • Page 115 1MRK 505 370-UUS Rev. K Section 6 Differential protection some time after feeder CB opening (that is, after 400 ms). This measure will ensure fast busbar protection tripping for faults within end fault region in that feeder bay, while feeder CB is open. However, it shall be noted that in order to utilize end fault protection feeder circuit breaker status and its closing command must be connected to the binary inputs of busbar protection scheme in order to be available for zone selection logic.
  • Page 116 Section 6 1MRK 505 370-UUS Rev. K Differential protection This situation only means that for this particular bay its busbar disconnectors are closed and therefore zone interconnection switching is happening in the station. When zone switching feature is activated inside the IED, each individual bay current will behave in the predetermined way.
  • Page 117 1MRK 505 370-UUS Rev. K Section 6 Differential protection By a parameter setting it is possible to provide self-rest or latched trip output contacts from the IED. However it shall be noted that the latching is electrical (that is, if DC supply to the IED is lost the output contacts will reset).
  • Page 118 Section 6 1MRK 505 370-UUS Rev. K Differential protection GOOSE for ZoneA ZoneA Trip IED 670 GOOSE for ZoneB ZoneB Trip 50 ms Ext ZoneA Trip Switch IED 670 50 ms Ext ZoneB Trip 50 ms Ext ZoneA Trip IED 670 50 ms Ext ZoneB Trip en06000227.vsd...
  • Page 119 1MRK 505 370-UUS Rev. K Section 6 Differential protection The IED has built-in feature to provide either self-reset or latched tripping in case of busbar protection operation. Which type of trip signal each zone will issue is determined by a parameter setting DiffTripOut which can be set either to SelfReset or Latched.
  • Page 120 Section 6 1MRK 505 370-UUS Rev. K Differential protection 6.1.4.2 Single busbar arrangements M6641-3 v5 The simplest form of busbar protection is a one-zone protection for single busbar configuration, as shown in Figure 54. When different CT ratios exist in the bays compensation is done by setting the CT ratio individually for each bay.
  • Page 121 1MRK 505 370-UUS Rev. K Section 6 Differential protection ANSI11000238-1-en.vsd ANSI11000238 V1 EN-US Figure 55: Example of two single busbar sections with bus-sectionalizing disconnector and eight feeder bays per each busbar section The most common setups for this type of station are described in the following table. Table 15: Typical solutions for stations with two single busbar sections with bus-sectionalizing disconnector Version of REB670 IED...
  • Page 122 Section 6 1MRK 505 370-UUS Rev. K Differential protection xx06000088_ansi.vsd ANSI06000088 V1 EN-US Figure 56: Example of two single busbar sections with bus-section circuit breaker and eight feeder bays per each busbar section This type of busbar arrangement can be quite easily protected. The most common setups for this type of station are described in the following table.
  • Page 123 1MRK 505 370-UUS Rev. K Section 6 Differential protection xx06000121_ansi.vsd ANSI06000121 V1 EN-US Figure 57: Example of H-type station The requirement for the busbar protection scheme for this type of station may differ from utility to utility. It is possible to apply just one overall differential zone, which protects both busbar sections. However, at an internal fault on any of the two buses all feeder circuit breakers have to be tripped, which will cause loss of supply to all loads connected to this station.
  • Page 124 Section 6 1MRK 505 370-UUS Rev. K Differential protection For station with double zone protection and just one set of CTs in the bus-section bay, it might be required, depending on the client requirements, to provide the special scheme for disconnection of bus- section CT when the bus-section CB is open.
  • Page 125 1MRK 505 370-UUS Rev. K Section 6 Differential protection REB 670 Bxxx BBP & Zone A BLKTR TRIP TRIP CTRLZA 152 Internal BFP CONNZA Backup Trip Command CTRLZB CONNZB TRZONE CT Input Parameter ZoneSel must TRBAY be set to "FixedToZA" I3PB1 Other Equipment...
  • Page 126 Section 6 1MRK 505 370-UUS Rev. K Differential protection ANSI11000240-1-en.vsd ANSI11000240 V1 EN-US Figure 60: Example of breaker-and-a-half station All breakers are normally closed. The requirement for the busbar protection scheme is that the scheme must have two independent differential zones, one for each busbar. In case of an internal fault on one of the two buses, all circuit breakers associated with the faulty busbar have to be tripped, but the supply to any load will not be interrupted.
  • Page 127 1MRK 505 370-UUS Rev. K Section 6 Differential protection REB 670 Remote Inter- Bxxx Trip Zone A BLKTR Feeder 1 TRIP CTRLZA 152 Internal BFP CONNZA BBP & Backup Trip Command CTRLZB CONNZB TRIP TRZONE CT Input TRBAY Parameter ZoneSel must be set to "FixedToZA"...
  • Page 128 Section 6 1MRK 505 370-UUS Rev. K Differential protection ANSI11000239-1-en.vsd ANSI11000239 V1 EN-US Figure 62: Example of double busbar station This type of busbar arrangement is very common. It is often preferred for larger installations. It provides good balance between maintenance work requirements and security of supply. If needed, two busbars can be split during normal service.
  • Page 129 1MRK 505 370-UUS Rev. K Section 6 Differential protection Disconnector aux. contact timing (Aux. contact a timing is only crucial when Scheme2_INX is used) Zone A Main Open Closed contact Zone B Aux. a Open Closed contact Aux. b Closed Open contact SSxx REB 670...
  • Page 130 Section 6 1MRK 505 370-UUS Rev. K Differential protection Zone A Disconnector aux. contact timing Zone B Main Open Closed contact Aux . b Closed Open contact REB 670 Set Parameter ZoneSel=" CtrlExcludes" External or Internal Bxxx Feeder BFP Backup Trip Command BLKTR TRIP...
  • Page 131 1MRK 505 370-UUS Rev. K Section 6 Differential protection Zone A Zone B REB 670 Parameter ZoneSel must be set to "FixedToZA" Bxxx BLKTR TRIP CTRLZA CONNZA Other CTRLZB CONNZB Equipment TRZONE CT Input TRBAY I3PB1 External or Internal Bus-Coupler BFP Backup Trip Command Bus-Coupler Bxxx...
  • Page 132 Section 6 1MRK 505 370-UUS Rev. K Differential protection Zone A Zone B REB 670 CB Closing Signal t=1s SSxx DISABLE CLOSED OPEN Bxxx ALARM BLKTR TRIP FORCED CTRLZA CONNZA CTRLZB CONNZB External or Internal ZEROCUR Bus-Coupler BFP Bus-Coupler TRZONE Backup Trip Command TRBAY I3PB1...
  • Page 133 1MRK 505 370-UUS Rev. K Section 6 Differential protection 6.1.4.9 Double busbar arrangements with two bus-section breakers and two bus- coupler breakers M6649-3 v5 This type of station is commonly used for GIS installations. It offers high operational flexibility. For this type of stations, two schemes similar to the double busbar station scheme can be used.
  • Page 134 Section 6 1MRK 505 370-UUS Rev. K Differential protection xx06000123_ansi.vsd ANSI06000123 V1 EN-US Figure 69: Combination between one-and-half and double breaker station layouts This type of stations can be encountered very often in practice. Usually the station is arranged in such a way that double breaker bays can be, at a later stage, transformed into one-and-half breaker setup.
  • Page 135 1MRK 505 370-UUS Rev. K Section 6 Differential protection Accordingly the following solutions are possible: Table 22: Typical solutions for combination between double breaker and double busbar station layouts Version of REB670 IED Number of double Number of REB670 IEDs required for the breaker feeders / scheme Number of double...
  • Page 136 Section 6 1MRK 505 370-UUS Rev. K Differential protection 6.1.5 Six-zone busbar arrangements 6.1.5.1 General GUID-28529398-F8D1-419B-9FB6-700BF19A2989 v1 Busbar differential protection application for some complex busbar arrangements with up to six differential zones are shown and described in the following sections. 6.1.5.2 Typical arrangement which can be covered GUID-2BC52A24-7844-4F83-A11E-944FC3487582 v1...
  • Page 137 1MRK 505 370-UUS Rev. K Section 6 Differential protection Sectionalizing disconnectors QB11 QB21 QB10 QB20 Bus-Interconnector 2 with one CT Feeder 01 Feeder 02-06 Bus-Interconnector 1 with two CTs Feeder 07-12 IEC16000144-1-en.vsdx IEC16000144 V1 EN-US Figure 74: Double busbar station with transfer bus and five protection zones Section 1 Section 2 Sectionalizing disconnectors...
  • Page 138 Section 6 1MRK 505 370-UUS Rev. K Differential protection The feeders located at the first section, namely Section 1, can be connected to either Z1 or Z2 or Z3, depending on the operational status of the three busbar disconnectors, in this particular station. More specifically, the following steps need to be done, for each feeder bay: Connect the two auxiliary contacts (i.e.
  • Page 139 1MRK 505 370-UUS Rev. K Section 6 Differential protection IEC16000148-2-en-us.vsdx IEC16000148 V2 EN-US Figure 78: ACT configuration example for Feeder 17 in Section 2 Step 4: ACT engineering of the Bus Coupler bays at Section 1 The bus-coupler bay is used to interconnect the differential zones via a circuit breaker within one section. In this particular station, the Bus-Coupler 01 is located at Section 1 and consequently it can be connected to either Z1 or Z2 or Z3.
  • Page 140 Section 6 1MRK 505 370-UUS Rev. K Differential protection IEC16000149-2-en-us.vsdx IEC16000149 V2 EN-US Figure 79: ACT configuration example for Bus-Coupler 01 in Section 1 Step 5: ACT engineering of the Bus Section bay The bus-section bay is used to interconnect the two section via a circuit breaker. Similar steps to Step 4 can be done for bus section bay, except that the bus section bay can be connected to Z1 or Z2 or Z3 on the first section and to Z4 or Z5 or Z6 on the second section.
  • Page 141 1MRK 505 370-UUS Rev. K Section 6 Differential protection IEC16000150-2-en-us.vsdx IEC16000150 V2 EN-US Figure 80: ACT configuration example for Bus-Section bay Step 6: ACT engineering of the Bus Sectionalizing Disconnectors Three bus-sectionalizing disconnectors are installed in this station. Each disconnector is used to interconnect the two zones located at the two sections.
  • Page 142 Section 6 1MRK 505 370-UUS Rev. K Differential protection IEC16000151-2-en-us.vsdx IEC16000151 V2 EN-US Figure 81: ACT configuration example for three bus-sectionalizing disconnectors 6.1.6 Summation principle GUID-B09585B4-A1B8-4E29-A469-25997493E434 v1 Summation principle is mainly intended for two-zone busbar protection applications. 6.1.6.1 Introduction M12135-3 v4 A simplified bus differential protection for phase and ground faults can be obtained by using a single one- phase IED with external auxiliary summation current transformers for all busbar arrangements with up to two differential zones.
  • Page 143 1MRK 505 370-UUS Rev. K Section 6 Differential protection calculation is then made on a single-phase basis. By doing so, this more cost effective bus differential protection can be applied. Due to this characteristic, this summation type of bus differential protection can be applied for all types of stations arrangements up to two differential zones as shown in Section Two-zone busbar arrangments, for three one-phase IEDs.
  • Page 144 Section 6 1MRK 505 370-UUS Rev. K Differential protection • Only one measuring circuit is utilized for all fault types (that is, no redundancy for multi-phase faults) • Primary fault sensitivity varies depending on the type of fault and involved phase(s), see Table •...
  • Page 145 1MRK 505 370-UUS Rev. K Section 6 Differential protection • main CT rated primary current is not important for ASCT selection • possible main CT ratio differences will be compensated by a parameter setting in the IED • rated secondary current of ASCT is 1A for all types. That means that secondary ASCT winding should be always connected to the IED with 1A CT inputs, irrespective of the rated secondary current of the main CT All of these features simplify the ordering of the ASCTs.
  • Page 146 Section 6 1MRK 505 370-UUS Rev. K Differential protection Auxiliary Summation CT Main CT type SLCE 8; 2000/1A or 2000/5A 1/1A or 5/1A or 2/1A or 2000/2A SUMM REB 670 with 1A CTs Other relays en06000128_ansi.vsd ANSI06000128 V1 EN-US Figure 85: End-connection with ASCT connected to CT3 input It is important to notice that even in the case of 5A or 2A main CTs, secondary current of the summation CTs shall be connected to the IED with 1A CT inputs (as shown in Figure 85).
  • Page 147 1MRK 505 370-UUS Rev. K Section 6 Differential protection Refer to Section "SLCE 8/ASCT characteristics for series-connection" for detailed ASCT current calculation for series-connection. 6.1.6.4 Main CT ratio mismatch correction M12138-3 v2 As stated before, three types of ASCTs for REB670 are available. The first type shall be used for main CTs with 1A rated secondary current.
  • Page 148 Section 6 1MRK 505 370-UUS Rev. K Differential protection SEMOD127594-37 v4 In addition to busbar protection differential zones, the IED can incorporate other additional functions and features. If and how they can be used together with summation busbar protection design is shown in Table 25: Table 25: Functions...
  • Page 149 1MRK 505 370-UUS Rev. K Section 6 Differential protection 6.1.6.6 SLCE 8/ASCT characteristics for end-connection M12141-3 v4 Typical ASCT end-connection is shown in Figure 85. For this ASCT connection type, the ampere-turn balance equation has the form according to Equation 15: ×...
  • Page 150 Section 6 1MRK 505 370-UUS Rev. K Differential protection external or internal fault), both negative and zero sequence current components will give their own contribution to the summated current. 6.1.6.7 SLCE 8/ASCT characteristics for series-connection M12143-3 v4 Typical ASCT series-connection is shown in Figure 86. For this ASCT connection type, the ampere-turn balance equation has the form according to equation 21: ×...
  • Page 151 1MRK 505 370-UUS Rev. K Section 6 Differential protection From Equation it is obvious that the ASCT rated ratio is declared for balanced three phase current system, when only positive sequence current component exist. For any unbalanced condition (that is, external or internal fault), both negative and zero sequence current components will give their own contribution to the summated current.
  • Page 153 1MRK 505 370-UUS Rev. K Section 7 Current protection Section 7 Current protection Directional phase overcurrent protection, four steps OC4PTOC (51_67) SEMOD129998-1 v8 7.1.1 Function revision history GUID-154CAE8E-8FD4-460C-852D-6E5C93545F0D v1 Document Product History revision revision 2.2.1 2.2.1 2.2.2 2.2.3 2.2.3 2.2.3 2.2.4 2.2.4 2.2.4...
  • Page 154 Section 7 1MRK 505 370-UUS Rev. K Current protection • Short circuit protection of feeders in distribution and subtransmission systems. Normally these feeders have a radial structure. • Back-up short circuit protection of transmission lines. • Back-up short circuit protection of power transformers. •...
  • Page 155 1MRK 505 370-UUS Rev. K Section 7 Current protection 7.1.4 Setting guidelines IP14982-1 v1 M12982-4 v14 When inverse time overcurrent characteristic is selected, the trip time of the stage will be the sum of the inverse time delay and the set definite time delay. Thus, if only the inverse time delay is required, it is important to set the definite time delay for that stage to zero.
  • Page 156 Section 7 1MRK 505 370-UUS Rev. K Current protection ANSI09000636-1-en.vsd ANSI09000636 V1 EN-US Figure 87: Directional function characteristic RCA = Relay characteristic angle ROA = Relay operating angle Reverse Forward 7.1.4.1 Settings for each step M12982-19 v11 x means step 1, 2, 3 and 4. DirModeSelx: The directional mode of step x.
  • Page 157 1MRK 505 370-UUS Rev. K Section 7 Current protection Table 26: Inverse time characteristics Curve name ANSI Extremely Inverse ANSI Very Inverse ANSI Normal Inverse ANSI Moderately Inverse ANSI/IEEE Definite time ANSI Long Time Extremely Inverse ANSI Long Time Very Inverse ANSI Long Time Inverse IEC Normal Inverse IEC Very Inverse...
  • Page 158 Section 7 1MRK 505 370-UUS Rev. K Current protection MultPUx: Multiplier for scaling of the current setting value. If a binary input signal ENMULTx (enableMultiplier) is activated the current operation level is increased by this setting constant. Setting range: 1.0-10.0 Trip time txMin Pickup current...
  • Page 159 1MRK 505 370-UUS Rev. K Section 7 Current protection For the customer tailor-made inverse time delay characteristics (type 17), all three types of reset time characteristics are available: instantaneous (1), IEC (2 = set constant time reset) and ANSI (3 = current dependent reset time).
  • Page 160 Section 7 1MRK 505 370-UUS Rev. K Current protection Current I Line phase current Pickup current Reset current The IED does not reset Time t ANSI09000146-en-1.vsd ANSI09000146 V1 EN-US Figure 89: Pickup and reset current for an overcurrent protection The lowest setting value can be written according to Equation 28. Im ax ³...
  • Page 161 1MRK 505 370-UUS Rev. K Section 7 Current protection £ × 0.7 Isc min (Equation 29) EQUATION1263 V2 EN-US where: is a safety factor Iscmin is the smallest fault current to be detected by the overcurrent protection. As a summary, the pickup current shall be chosen within the interval stated in Equation 30. Im ax ×...
  • Page 162 Section 7 1MRK 505 370-UUS Rev. K Current protection Time-current curves tfunc1 tfunc2 n 0.01 10000 Fault Current en05000204.ai IEC05000204 V2 EN-US Figure 90: Fault time with maintained selectivity The operation time can be set individually for each overcurrent protection. To assure selectivity between different protection functions in the radial network, there has to be a minimum time difference Dt between the time delays of two protections.
  • Page 163 1MRK 505 370-UUS Rev. K Section 7 Current protection Feeder Time axis The fault Protection Breaker at Protection occurs B1 trips B1 opens A1 resets en05000205_ansi.vsd ANSI05000205 V1 EN-US Figure 91: Sequence of events during fault where: is when the fault occurs is when protection IED B1 and protection IED A1 start is when the trip signal from the overcurrent protection at IED B1 is sent to the circuit breaker.
  • Page 164 Section 7 1MRK 505 370-UUS Rev. K Current protection 7.2.1 Function revision history GUID-94DB6C52-230F-4313-B6EE-1D8A1640C292 v1 Document Product History revision revision 2.2.1 2.2.1 2.2.2 2.2.3 2.2.3 2.2.3 2.2.4 2.2.4 2.2.4 2.2.5 The harmonic restraint function changed to freeze the definite and IDMT timers. 7.2.2 Identification SEMOD127810-2 v2...
  • Page 165 1MRK 505 370-UUS Rev. K Section 7 Current protection inverse time characteristics are available: IEC and ANSI. It is also possible to programme a user defined inverse time characteristic. Normally it is required that the phase overcurrent function shall reset as fast as possible when the current level gets lower than the operation level.
  • Page 166 Section 7 1MRK 505 370-UUS Rev. K Current protection Table 28: Inverse time delay characteristics Curve name ANSI Extremely Inverse ANSI Very Inverse ANSI Normal Inverse ANSI Moderately Inverse ANSI/IEEE Definite time ANSI Long Time Extremely Inverse ANSI Long Time Very Inverse ANSI Long Time Inverse IEC Normal Inverse IEC Very Inverse...
  • Page 167 1MRK 505 370-UUS Rev. K Section 7 Current protection Table 29: Reset possibilities Curve name Curve index no. Instantaneous IEC Reset (constant time) ANSI Reset (inverse time) The delay characteristics are described in the “Technical reference manual”. There are some restrictions regarding the choice of reset delay.
  • Page 168 Section 7 1MRK 505 370-UUS Rev. K Current protection 2ndHarmStab: The rate of second harmonic current content for activation of the 2 harmonic restrain signal, to block chosen steps. The setting is given in % of the fundamental frequency residual current. The setting range is 5-100% in step of 1%.
  • Page 169 1MRK 505 370-UUS Rev. K Section 7 Current protection The maximum load current on the line has to be estimated. From operation statistics the load current up to the present situation can be found. The current setting must be valid also for some years ahead. It is, in most cases, realistic that the setting values are updated not more often than once every five years.
  • Page 170 Section 7 1MRK 505 370-UUS Rev. K Current protection shortest fault time with maintained selectivity. Selectivity is assured if the time difference between the curves is larger than a critical time difference. Time-current curves tfunc1 tfunc2 n 0.01 10000 Fault Current en05000204.ai IEC05000204 V2 EN-US Figure 93:...
  • Page 171 1MRK 505 370-UUS Rev. K Section 7 Current protection Feeder Fault I> I> Time axis The fault B1 and A1 B1 trips and Breaker at Protection occurs start A1 starts B1 opens A1 resets =IEC05000205=2=en=Original.vsd IEC05000205 V2 EN-US Figure 94: Sequence of events during fault where: is the fault occurs,...
  • Page 172 Section 7 1MRK 505 370-UUS Rev. K Current protection 7.3.1 Function revision history GUID-0F9199B0-3F86-45E0-AFC2-747052A20AE1 v2 Document Product History revision revision 2.2.1 2.2.1 2.2.2 Technical data table updated with note “Operate time and reset time are only valid if harmonic blocking is turned off for a step”. 2.2.3 2.2.3 2.2.3...
  • Page 173 1MRK 505 370-UUS Rev. K Section 7 Current protection SeqTypeIPol: This is used to select the type of current polarising quantity (that is, Zero seq or Neg seq for direction detection). SeqTypeIDir: This is used to select the type of operating current quantity (that is, Zero seq or Neg seq for direction detection).
  • Page 174 Section 7 1MRK 505 370-UUS Rev. K Current protection the local source can be used to calculate the value of ZN as V/(√3 · 3I ) Typically, the minimum ZNPol (3 · zero sequence source) is set. The setting is in primary ohms. When the dual polarizing method is used, it is important that the setting Pickupx or the product 3I ·...
  • Page 175 1MRK 505 370-UUS Rev. K Section 7 Current protection Power System en05000136_ansi.vsd ANSI05000136 V1 EN-US Figure 96: Application for parallel transformer inrush current logic If the BlkParTransf function is activated, the 2 harmonic restrain signal will latch as long as the residual current measured by the relay is larger than a selected step current level.
  • Page 176 Section 7 1MRK 505 370-UUS Rev. K Current protection HarmBlkSOTF: This is used to On/Off harmonic restrain during SOTF conditions. tSOTF: Time delay for operation of the SOTF function. The setting range is 0.000 - 60.000 s in step of 0.001 s.
  • Page 177 1MRK 505 370-UUS Rev. K Section 7 Current protection IMinx: Minimum pickup current for step x in % of IB. Set IMinx below Pickupx for every step to achieve ANSI reset characteristic according to standard. If IMinx is set above for any step, signal will reset at current equals to zero.
  • Page 178 Section 7 1MRK 505 370-UUS Rev. K Current protection æ ö ç ÷ ç ÷ × ç ÷ æ ö ç ÷ ç ÷ è ø è ipickup ø (Equation 39) EQUATION1722 V1 EN-US Further description can be found in the technical reference manual. tPRCrvx, tTRCrvx, tCRCrvx: Parameters for user programmable of inverse reset time characteristic curve.
  • Page 179 1MRK 505 370-UUS Rev. K Section 7 Current protection 7.4.1 Function revision history GUID-FEAFB742-D0DA-4F9E-B4AC-84E568301282 v2 Document Product History revision revision 2.2.1 2.2.1 2.2.2 2.2.3 2.2.3 2.2.3 2.2.4 2.2.4 Maximum value changed to 2000.0 % of IBase for IMin1, IMin2, IMin3 and IMin4 settings. 2.2.5 7.4.2 Identification...
  • Page 180 Section 7 1MRK 505 370-UUS Rev. K Current protection Choice of time characteristics: There are several types of time characteristics available such as definite time delay and different types of inverse time characteristics. The selectivity between different overcurrent protections is normally enabled by co-ordination between the operating time of the different protections.
  • Page 181 1MRK 505 370-UUS Rev. K Section 7 Current protection Common base IED values for the primary current (IBase), primary voltage (VBase) and primary power (SBase) are set in global base values for settings function GBASVAL. GlobalBaseSel: Selects the global base value group used by the function to define IBase, VBase and SBase.
  • Page 182 Section 7 1MRK 505 370-UUS Rev. K Current protection tx: Definite time delay for step x. The definite time tx is added to the inverse time when inverse time characteristic is selected. Note that the value set is the time between activation of the start and the trip outputs.
  • Page 183 1MRK 505 370-UUS Rev. K Section 7 Current protection For IEC inverse time delay characteristics the possible delay time settings are instantaneous (1) and IEC (2 = set constant time reset). For the programmable inverse time delay characteristics all three types of reset time characteristics are available;...
  • Page 184 Section 7 1MRK 505 370-UUS Rev. K Current protection Reverse Area Vpol=-V2 AngleRCA Forward Area Iop = I2 ANSI10000031-1-en.vsd ANSI10000031 V1 EN-US Figure 100: Relay characteristic angle given in degree In a transmission network a normal value of RCA is about 80°. VPolMin: Minimum polarization (reference) voltage % of VBase.
  • Page 185 1MRK 505 370-UUS Rev. K Section 7 Current protection 7.5.2 Application M15341-3 v5 Transformers in the power system are designed for a certain maximum load current (power) level. If the current exceeds this level the losses will be higher than expected. As a consequence the temperature of the transformer will increase.
  • Page 186 Section 7 1MRK 505 370-UUS Rev. K Current protection GlobalBaseSel: Selects the global base value group used by the function to define IBase, VBase and SBase. Note that this function will only use IBase value. IRef: Reference level of the current given in %. When the current is equal to IRef the final (steady state) heat content is equal to 1.
  • Page 187 1MRK 505 370-UUS Rev. K Section 7 Current protection Tau1Low: Multiplication factor to adjust the time constant Tau1 if the current is lower than the set value ILowTau1. ILowTau1 is set in % of IBase1. Tau2High: Multiplication factor to adjust the time constant Tau2 if the current is higher than the set value IHighTau2.
  • Page 188 Section 7 1MRK 505 370-UUS Rev. K Current protection is the steady state heat content final is the largest phase load current is the given reference load current is the operate level heat content       operate Trip is the selected base current based cooling system...
  • Page 189 1MRK 505 370-UUS Rev. K Section 7 Current protection > Q Here final          ThetaInit 0.5 2509056 1254528 At t=0 init operate At next execution, θ =1254528 and θ =1254555.04.   ...
  • Page 190 Section 7 1MRK 505 370-UUS Rev. K Current protection Document Product History revision revision 2.2.4 2.2.4 2.2.5 7.6.2 Identification M14878-1 v5 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Breaker failure protection, 3-phase CCRBRF 50BF activation and output 3I>BF SYMBOL-U V1 EN-US 7.6.3...
  • Page 191 1MRK 505 370-UUS Rev. K Section 7 Current protection If TRBU has been given and CBCLDLx still has value one in the CB Pos mode or if the CB position part of the Current or CB Pos mode is active, TRBU and TRRET will internally be reset intentionally after approximately 10 seconds.
  • Page 192 Section 7 1MRK 505 370-UUS Rev. K Current protection 30ms 30ms TRRET PICKUP 30ms TRBU Current Check CB Position Check 150ms ANSI 18001002-1-en.vsdx ANSI18001002 V1 EN-US Figure 101: Simplified overall logic for LatchedStart TRRET PICKUP Current Check CB Position Check TRBU ANSI18001003-1-en.vsdx ANSI18001003 V1 EN-US...
  • Page 193 1MRK 505 370-UUS Rev. K Section 7 Current protection Table 32: Dependencies between parameters RetripMode and FunctionMode RetripMode FunctionMode Description The retrip function is disabled UseFunctionMode Current A phase current should be larger than the set operate level to allow retrip once the t1 timer elapses CB Pos retrip is done when the breaker...
  • Page 194 Section 7 1MRK 505 370-UUS Rev. K Current protection where: is the maximum opening time for the circuit breaker CB_open is the maximum time for breaker failure protection to detect correct breaker function (the BFP_reset current criteria reset) is a safety margin margin It is often required that the total fault clearance time shall be less than a given critical time.
  • Page 195 1MRK 505 370-UUS Rev. K Section 7 Current protection tPulse: Trip pulse duration. This setting must be larger than the opening time of circuit breakers to be tripped from the breaker failure protection. Typical setting is 200 ms. tStartTimeout: When one of the two “Follow Modes” is used, there is a settable timer tStartTimeout which will block the external START input signal when it times-out.
  • Page 196 Section 7 1MRK 505 370-UUS Rev. K Current protection StartMode RetripMode t1 and t2 initiated When t1 has When t2 or t2MPh t1 and t2 and t2MPh with elapsed, TRRET will has elapsed, TRBU will be stopped will be given if (reset) if FunctionMode = CB Pos LatchedStart...
  • Page 197 1MRK 505 370-UUS Rev. K Section 7 Current protection StartMode RetripMode t1 and t2 initiated When t1 has elapsed, When t2 or t2MPh t1 and t2 and t2MPh with TRRET will has elapsed, TRBU will be stopped will be given if (reset) if FunctionMode = Current or CB Pos LatchedStart...
  • Page 198 Section 7 1MRK 505 370-UUS Rev. K Current protection StartMode RetripMode t1 and t2 initiated When t1 has elapsed, When t2 or t2MPh t1 and t2 and t2MPh with TRRET will has elapsed, TRBU will be stopped will be given if (reset) if FollowStart&M external START...
  • Page 199 1MRK 505 370-UUS Rev. K Section 7 Current protection 7.7.2 Identification SEMOD127866-2 v2 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Breaker failure protection, single phase CCSRBRF 50BF version I>BF SYMBOL-II V1 EN-US 7.7.3 Application SEMOD127974-4 v3 In the design of the fault clearance system the N-1 criterion is often used.
  • Page 200 Section 7 1MRK 505 370-UUS Rev. K Current protection when the CB position criterion is used, is either to shortly activate BLOCK input or setting CCSRBRF to blocked when the IED is in test mode. By setting the StartMode, it is possible to select how t1 and t2 timers are run and consequently how output commands are given from the function: •...
  • Page 201 1MRK 505 370-UUS Rev. K Section 7 Current protection TRRET PICKUP Current Check CB Position Check TRBU ANSI18001003-1-en.vsdx ANSI18001003 V1 EN-US Figure 106: Simplified overall logic for FollowStart PICKUP TRRET Current Check CB Position Check TRBU ANSI18001004-1-en.vsdx ANSI18001004 V1 EN-US Figure 107: Simplified overall logic for FollowStart&Mode RetripMode: This setting defines how the retrip function shall operate.
  • Page 202 Section 7 1MRK 505 370-UUS Rev. K Current protection based function will be enabled only if the current at the moment of starting is below this set level. The setting can be given within the range 5 – 200% of IBase. It is strongly recommended to set this level above IPPU set level.
  • Page 203 1MRK 505 370-UUS Rev. K Section 7 Current protection tCBAlarm: Time delay for alarm in case of indication of faulty circuit breaker. There is a binary input 52FAIL from the circuit breaker. This signal is activated when internal supervision in the circuit breaker detect that the circuit breaker is unable to clear fault.
  • Page 204 Section 7 1MRK 505 370-UUS Rev. K Current protection StartMode RetripMode t1 and t2 initiated When t1 has When t2 has elapsed, t1 and t2 will be with elapsed, TRRET TRBU will be given if stopped (reset) if will FollowStart&M external START never be given current is above set...
  • Page 205 1MRK 505 370-UUS Rev. K Section 7 Current protection StartMode RetripMode t1 and t2 initiated When t1 has When t2 has elapsed, t1 and t2 will be with elapsed, TRRET TRBU will be given if stopped (reset) if will FollowStart&M external START never be given be given if CBCLD...
  • Page 206 Section 7 1MRK 505 370-UUS Rev. K Current protection StartMode RetripMode t1 and t2 initiated When t1 has When t2 has elapsed, t1 and t2 will be with elapsed, TRRET TRBU will be given if stopped (reset) if will FollowStart external START never be given current is above set...
  • Page 207 1MRK 505 370-UUS Rev. K Section 7 Current protection Directional underpower protection GUPPDUP (37) SEMOD156693-1 v4 7.8.1 Identification SEMOD158941-2 v4 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Directional underpower protection GUPPDUP P < SYMBOL-LL V2 EN-US 7.8.2 Application SEMOD151283-4 v6...
  • Page 208 Section 7 1MRK 505 370-UUS Rev. K Current protection Power to the power plant auxiliaries may come from a station service transformer connected to the secondary side of the unit step-up transformer. Power may also come from a start-up service transformer connected to the external network.
  • Page 209 1MRK 505 370-UUS Rev. K Section 7 Current protection Mode: The voltage and current used for the power measurement. The setting possibilities are shown in table 36. Table 36: Complex power calculation Set value Mode Formula used for complex power calculation A, B, C ×...
  • Page 210 Section 7 1MRK 505 370-UUS Rev. K Current protection Power1(2) Angle1(2) Operate en06000441.vsd IEC06000441 V1 EN-US Figure 110: Underpower mode The setting Power1(2) gives the power component pick up value in the Angle1(2) direction. The setting is given in p.u. of the generator rated power, see equation 56. Minimum recommended setting is 0.2% of S when metering class CT inputs into the IED are used.
  • Page 211 1MRK 505 370-UUS Rev. K Section 7 Current protection Operate ° Angle1(2) = 0 Power1(2) en06000556.vsd IEC06000556 V1 EN-US Figure 111: For low forward power the set angle should be 0° in the underpower function TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pick up. Hysteresis1(2) is given in p.u.
  • Page 212 Section 7 1MRK 505 370-UUS Rev. K Current protection VMagComp5, VMagComp30, VMagComp100 IMagComp5, IMagComp30, IMagComp100 The angle compensation is given as difference between current and voltage angle errors. The values are given for operating points 5, 30 and 100% of rated current/voltage. The values should be available from instrument transformer test protocols.
  • Page 213 1MRK 505 370-UUS Rev. K Section 7 Current protection steam supply, the electric power consumption will be about 2% of rated power. Even if the turbine rotates in vacuum, it will soon become overheated and damaged. The turbine overheats within minutes if the turbine loses the vacuum.
  • Page 214 Section 7 1MRK 505 370-UUS Rev. K Current protection 7.9.3 Setting guidelines SEMOD172150-4 v7 GlobalBaseSel: Selects the global base value group used by the function to define IBase, VBase and SBase. Note that this function will only use IBase value. Operation: With the parameter Operation the function can be set Enabled/Disabled.
  • Page 215 1MRK 505 370-UUS Rev. K Section 7 Current protection Operate Power1(2) Angle1(2) en06000440.vsd IEC06000440 V1 EN-US Figure 113: Overpower mode The setting Power1(2) gives the power component pick up value in the Angle1(2) direction. The setting is given in p.u. of the generator rated power, see equation 69. Minimum recommended setting is 0.2% of S when metering class CT inputs into the IED are used.
  • Page 216 Section 7 1MRK 505 370-UUS Rev. K Current protection Angle1(2 ) = 180 Operate Power 1(2) IEC06000557-2-en.vsd IEC06000557 V2 EN-US Figure 114: For reverse power the set angle should be 180° in the overpower function TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pick up. Hysteresis1(2) is given in p.u.
  • Page 217 1MRK 505 370-UUS Rev. K Section 7 Current protection IMagComp5, IMagComp30, IMagComp100 VMagComp5, VMagComp30, VMagComp100 IAngComp5, IAngComp30, IAngComp100 The angle compensation is given as difference between current and voltage angle errors. The values are given for operating points 5, 30 and 100% of rated current/voltage. The values should be available from instrument transformer test protocols.
  • Page 218 Section 7 1MRK 505 370-UUS Rev. K Current protection Rack Capacitor Unit (Can) IEC09000753_1_en.vsd IEC09000753 V1 EN-US Figure 115: Replacement of a faulty capacitor unit within SCB There are four types of the capacitor unit fusing designs which are used for construction of SCBs: Externally fused where an individual fuse, externally mounted, protects each capacitor unit.
  • Page 219 1MRK 505 370-UUS Rev. K Section 7 Current protection Delta-connected banks (generally used only at distribution voltages) Single wye-connected banks Double wye-connected banks H-configuration, where each phase is connected in a bridge Additionally, the SCB star point, when available, can be either grounded , grounded via impedance or isolated from ground.
  • Page 220 Section 7 1MRK 505 370-UUS Rev. K Current protection • Voltage in excess of the nameplate rating at fundamental frequency, but not over 110% of rated RMS voltage • Harmonic voltages superimposed on the fundamental frequency • Reactive power manufacturing tolerance of up to 115% of rated reactive power Capacitor units rated above 600 V shall have an internal discharge device to reduce the residual voltage to 50 V or less in 5 or 10 minutes (depending on national standard).
  • Page 221 1MRK 505 370-UUS Rev. K Section 7 Current protection 400kV Preprocessing Capacitor bank Function Block protection function SMAI CBPGAPC 500/1 200MVAr 400kV IEC09000754-1-en.vsd IEC09000754 V1 EN-US Figure 116: Single line diagram for the application example From figure it is possible to calculate the following rated fundamental frequency current for this SCB: ×...
  • Page 222 Section 7 1MRK 505 370-UUS Rev. K Current protection IRecInhibit =10% (of IBase); Current level under which function will detect that SCB is disconnected from the power system tReconnInhibit =300s; Time period under which SCB shall discharge remaining residual voltage to less than 5%.
  • Page 223 1MRK 505 370-UUS Rev. K Section 7 Current protection 7.10.3.1 Restrike detection GUID-114747A5-0F7C-4F48-A32D-0C13BFF6ADCE v1 Opening of SCBs can be quite problematic for certain types of circuit breakers (CBs). Typically such problems are manifested as CB restrikes. In simple words this means that the CB is not breaking the current at the first zero crossing after separation of the CB contacts.
  • Page 225 1MRK 505 370-UUS Rev. K Section 8 Voltage protection Section 8 Voltage protection Two step undervoltage protection UV2PTUV (27) IP14544-1 v3 8.1.1 Identification M16876-1 v7 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Two step undervoltage protection UV2PTUV 3U<...
  • Page 226 Section 8 1MRK 505 370-UUS Rev. K Voltage protection 8.1.2.4 Voltage instability mitigation M13851-59 v3 This setting is very much dependent on the power system characteristics, and thorough studies have to be made to find the suitable levels. 8.1.2.5 Backup protection for power system faults M13851-62 v3 The setting must be below the lowest occurring "normal"...
  • Page 227 1MRK 505 370-UUS Rev. K Section 8 Voltage protection ResetTypeCrvn: This parameter for inverse time characteristic can be set to Instantaneous, Frozen time, Linearly decreased. The default setting is Instantaneous. tIResetn: Reset time for step n if inverse time delay is used, given in s. The default value is 25 ms. TDn: Time multiplier for inverse time characteristic.
  • Page 228 Section 8 1MRK 505 370-UUS Rev. K Voltage protection decreasing the voltage. The function has a high measuring accuracy and hysteresis setting to allow applications to control reactive load. OV2PTOV (59) is used to disconnect apparatuses, like electric motors, which will be damaged when subject to service under high voltage conditions.
  • Page 229 1MRK 505 370-UUS Rev. K Section 8 Voltage protection 8.2.3.3 Power supply quality M13852-16 v1 The setting has to be well above the highest occurring "normal" voltage and below the highest acceptable voltage, due to regulation, good practice or other agreements. 8.2.3.4 High impedance grounded systems M13852-19 v6...
  • Page 230 Section 8 1MRK 505 370-UUS Rev. K Voltage protection Pickupn: Set pickup overvoltage operation value for step n, given as % of VBase. The setting is highly dependent of the protection application. Here it is essential to consider the maximum voltage at non- faulted situations.
  • Page 231 1MRK 505 370-UUS Rev. K Section 8 Voltage protection Two step residual overvoltage protection ROV2PTOV (59N) IP14546-1 v4 8.3.1 Function revision history GUID-22110E0B-DEFB-461F-A437-4D221DB88799 v2 Document Product History revision revision 2.2.1 2.2.1 2.2.2 2.2.3 2.2.3 2.2.3 2.2.4 2.2.4 2.2.5 8.3.2 Identification SEMOD54295-2 v6 Function description IEC 61850...
  • Page 232 Section 8 1MRK 505 370-UUS Rev. K Voltage protection 8.3.4 Setting guidelines M13853-3 v8 All the voltage conditions in the system where ROV2PTOV (59N) performs its functions should be considered. The same also applies to the associated equipment, its voltage withstand capability and time characteristic.
  • Page 233 1MRK 505 370-UUS Rev. K Section 8 Voltage protection ANSI07000190-1-en.vsd ANSI07000190 V1 EN-US Figure 117: Ground fault in Non-effectively grounded systems 8.3.4.5 Direct grounded system GUID-EA622F55-7978-4D1C-9AF7-2BAB5628070A v8 In direct grounded systems, an ground fault on one phase is indicated by voltage collapse in that phase. The other healthy phase will still have normal phase-to-ground voltage.
  • Page 234 Section 8 1MRK 505 370-UUS Rev. K Voltage protection VBase (given in GlobalBaseSel) is used as voltage reference for the set pickup values. The voltage can be fed to the IED in different ways: The IED is fed from a normal voltage transformer group where the residual voltage is calculated internally from the phase-to-ground voltages within the protection.
  • Page 235 1MRK 505 370-UUS Rev. K Section 8 Voltage protection TDn: Time multiplier for inverse time characteristic. This parameter is used for co-ordination between different inverse time delayed undervoltage protections. ACrvn, BCrvn, CCrvn, DCrvn, PCrvn: Parameters for step n, to set to create programmable undervoltage inverse time characteristic.
  • Page 236 Section 8 1MRK 505 370-UUS Rev. K Voltage protection 8.4.3 Application SEMOD153893-5 v4 The Voltage differential protection VDCPTOV (60) functions can be used in some different applications. • Voltage unbalance protection for capacitor banks. The voltage on the bus is supervised with the voltage in the capacitor bank, phase- by phase.
  • Page 237 1MRK 505 370-UUS Rev. K Section 8 Voltage protection GlobalBaseSel: Selects the global base value group used by the function to define IBase, VBase and SBase. Note that this function will only use IBase value. BlkDiffAtVLow: The setting is to block the function when the voltages in the phases are low. RFLx: Is the setting of the voltage ratio compensation factor where possible differences between the voltages is compensated for.
  • Page 238 Section 8 1MRK 505 370-UUS Rev. K Voltage protection Loss of voltage check LOVPTUV (27) SEMOD171868-1 v2 8.5.1 Identification SEMOD171954-2 v2 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Loss of voltage check LOVPTUV 8.5.2 Application SEMOD171876-4 v3 The trip of the circuit breaker at a prolonged loss of voltage at all the three phases is normally used in automatic restoration systems to facilitate the system restoration after a major blackout.
  • Page 239 1MRK 505 370-UUS Rev. K Section 9 Frequency protection Section 9 Frequency protection Underfrequency protection SAPTUF (81) IP15746-1 v3 9.1.1 Identification M14865-1 v5 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Underfrequency protection SAPTUF f < SYMBOL-P V1 EN-US 9.1.2 Application...
  • Page 240 Section 9 1MRK 505 370-UUS Rev. K Frequency protection Some applications and related setting guidelines for the frequency level are given below: Equipment protection, such as for motors and generators The setting has to be well below the lowest occurring "normal" frequency and well above the lowest acceptable frequency for the equipment.
  • Page 241 1MRK 505 370-UUS Rev. K Section 9 Frequency protection There are two application areas for SAPTOF (81): to protect equipment against damage due to high frequency, such as generators, and motors to protect a power system, or a part of a power system, against breakdown, by shedding generation, in over production situations.
  • Page 242 Section 9 1MRK 505 370-UUS Rev. K Frequency protection 9.3.3 Setting guidelines M14971-3 v7 The parameters for Rate-of-change frequency protection SAPFRC (81) are set via the local HMI or or through the Protection and Control Manager (PCM600). All the frequency and voltage magnitude conditions in the system where SAPFRC (81) performs its functions should be considered.
  • Page 243 1MRK 505 370-UUS Rev. K Section 10 Multipurpose protection Section 10 Multipurpose protection 10.1 General current and voltage protection CVGAPC IP14552-1 v2 10.1.1 Function revision history GUID-74F9B9A9-91EB-45BA-A883-6BA325C8B272 v1 Document Product History revision revision 2.2.1 2.2.1 2.2.2 2.2.3 2.2.3 2.2.3 2.2.4 2.2.4 2.2.4 2.2.5...
  • Page 244 Section 10 1MRK 505 370-UUS Rev. K Multipurpose protection protections based on measurement of phase-to-ground, phase-to-phase, residual- or sequence- voltage components can be used to detect and operate for such incident. The IED can be provided with multiple General current and voltage protection (CVGAPC) protection modules.
  • Page 245 1MRK 505 370-UUS Rev. K Section 10 Multipurpose protection Table 38: Available selection for current quantity within CVGAPC function Set value for parameter Comment "CurrentInput” PhaseA CVGAPC function will measure the phase A current phasor PhaseB CVGAPC function will measure the phase B current phasor PhaseC CVGAPC function will measure the phase C current phasor PosSeq...
  • Page 246 Section 10 1MRK 505 370-UUS Rev. K Multipurpose protection Set value for parameter Comment "VoltageInput" -NegSeq CVGAPC function will measure internally calculated negative sequence voltage phasor. This voltage phasor will be intentionally rotated for 180° in order to enable easier settings for the directional feature when used. -3*ZeroSeq CVGAPC function will measure internally calculated zero sequence voltage phasor multiplied by factor 3.
  • Page 247 1MRK 505 370-UUS Rev. K Section 10 Multipurpose protection rated phase-to-ground voltage of the protected object in primary kV, when the measured Voltage Quantity is selected from 1 to 9, as shown in table 39. rated phase-to-phase voltage of the protected object in primary kV, when the measured Voltage Quantity is selected from 10 to 15, as shown in table 39.
  • Page 248 Section 10 1MRK 505 370-UUS Rev. K Multipurpose protection Higher quantities of machine current and voltage (3 to 4 per unit current and 50% to 70% rated voltage) can be expected if the generator is connected to a strong system. Lower current and voltage values (1 to 2 per unit current and 20% to 40% rated voltage) are representative of weaker systems.
  • Page 249 1MRK 505 370-UUS Rev. K Section 10 Multipurpose protection 10.1.4.1 Directional negative sequence overcurrent protection M13088-3 v6 Directional negative sequence overcurrent protection is typically used as sensitive ground-fault protection of power lines where incorrect zero sequence polarization may result from mutual induction between two or more parallel lines.
  • Page 250 Section 10 1MRK 505 370-UUS Rev. K Multipurpose protection • the set values for RCADir and ROADir settings will be as well applicable for OC2 stage • setting DirMode_OC2 shall be set to Reverse • setting parameter PickupCurr_OC2 shall be made more sensitive than pickup value of forward OC1 element (that is, typically 60% of OC1 set pickup level) in order to insure proper operation of the directional comparison scheme during current reversal situations •...
  • Page 251 1MRK 505 370-UUS Rev. K Section 10 Multipurpose protection × æ ö ç ÷ × è ø (Equation 81) EQUATION1741-ANSI V1 EN-US In order to achieve such protection functionality with one CVGAPC functions the following must be done: Connect three-phase generator currents to one CVGAPC instance (for example, CVGAPC:1) Set parameter CurrentInput to value NegSeq Set base current value to the rated generator current in primary amperes Enable one overcurrent step (for example, OC1)
  • Page 252 Section 10 1MRK 505 370-UUS Rev. K Multipurpose protection Furthermore the other built-in protection elements can be used for other protection and alarming purposes (for example, use OC2 for negative sequence overcurrent alarm and OV1 for negative sequence overvoltage alarm). 10.1.4.3 Generator stator overload protection in accordance with ANSI or IEEE standards...
  • Page 253 1MRK 505 370-UUS Rev. K Section 10 Multipurpose protection Connect three-phase generator currents to one CVGAPC instance (for example, CVGAPC:2) Set parameter CurrentInput to value PosSeq Set base current value to the rated generator current in primary amperes (the correct Global Base values group shall be selected by the parameter GlobalBaseSel) Enable one overcurrent step (for example OC1) Select parameter CurveType_OC1 to value Programmable æ...
  • Page 254 Section 10 1MRK 505 370-UUS Rev. K Multipurpose protection 10.1.4.4 Open phase protection for transformer, lines or generators and circuit breaker head flashover protection for generators M13088-142 v4 Example will be given how to use one CVGAPC function to provide open phase protection. This can be achieved by using one CVGAPC function by comparing the unbalance current with a pre-set level.
  • Page 255 1MRK 505 370-UUS Rev. K Section 10 Multipurpose protection Enable one overcurrent step (for example, OC1) Select CurveType_OC1 to value ANSI Very inv If required set minimum operating time for this curve by using parameter tMin_OC1 (default value 0.05s) Set PickupCurr_OC1 to value 185% 10.
  • Page 256 Section 10 1MRK 505 370-UUS Rev. K Multipurpose protection Q [pu] Operating region ILowSet P [pu] -rca -0.2 -0.4 ILowSet Operating Region -0.6 -0.8 en05000535_ansi.vsd ANSI05000535 V1 EN-US Figure 120: Loss of excitation 10.1.4.7 Undercurrent protection for capacitor bank GUID-1AAD3844-6FEE-4050-8260-27E7A30F6352 v1 Following example explains how an undercurrent protection within CVGAPC function can be used for the disconnection of shunt capacitor bank (SCB) in case of very low voltages at the busbar.
  • Page 257 1MRK 505 370-UUS Rev. K Section 11 Secondary system supervision Section 11 Secondary system supervision 11.1 Fuse failure supervision FUFSPVC IP14556-1 v3 11.1.1 Identification M14869-1 v4 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Fuse failure supervision FUFSPVC 11.1.2 Application...
  • Page 258 Section 11 1MRK 505 370-UUS Rev. K Secondary system supervision 11.1.3 Setting guidelines IP15000-1 v1 11.1.3.1 General M13683-3 v5 The negative and zero sequence voltages and currents always exist due to different non-symmetries in the primary system and differences in the current and voltage instrument transformers. The minimum value for the operation of the current and voltage measuring elements must always be set with a safety margin of 10 to 20%, depending on the system operating conditions.
  • Page 259 1MRK 505 370-UUS Rev. K Section 11 Secondary system supervision   VBase (Equation 87) EQUATION1757-ANSI V4 EN-US where: V2PU is the maximal negative sequence voltage during normal operation conditions, plus a margin of 10...20% VBase is the base voltage for the function according to the setting GlobalBaseSel The setting of the current limit 3I2PU is in percentage of parameter IBase.
  • Page 260 Section 11 1MRK 505 370-UUS Rev. K Secondary system supervision 11.1.3.5 Delta V and delta I GUID-02336F26-98C0-419D-8759-45F5F12580DE v7 Set the operation mode selector OpDVDI to Enabled if the delta function shall be in operation. The setting of DVPU should be set high (approximately 60% of VBase) and the current threshold DIPU low (approximately 10% of IBase) to avoid unwanted operation due to normal switching conditions in the network.
  • Page 261 1MRK 505 370-UUS Rev. K Section 11 Secondary system supervision 11.2.2 Application GUID-AD63BF6C-0351-4E48-9FB2-9AB5CF0C521E v2 Some protection functions operate on the basis of measured voltage at the relay point. Examples of such protection functions are distance protection function, undervoltage function and energisation-check function.
  • Page 262 Section 11 1MRK 505 370-UUS Rev. K Secondary system supervision GUID-0B298162-C939-47E4-A89B-7E6BD7BEBB2C v2 The voltage input type (phase-to-phase or phase-to-neutral) is selected using ConTypeMain and ConTypePilot parameters, for main and pilot fuse groups respectively. The connection type for the main and the pilot fuse groups must be consistent. The settings Vdif Main block, Vdif Pilot alarm and VSealIn are in percentage of the base voltage, VBase.
  • Page 263 1MRK 505 370-UUS Rev. K Section 11 Secondary system supervision • Instantaneous sample based delta detection • True RMS value based delta detection • DFT magnitude based delta detection • Vector shift protection The Delta detection mode is selected on the basis of application requirements. For example, Instantaneous sample based delta supervision is very fast;...
  • Page 264 Section 11 1MRK 505 370-UUS Rev. K Secondary system supervision DELVSPVC (78V) V3P* BFI_3P BLOCK PICKUP_A 78V Pickup PICKUP_B PICKUP_C STRISE STRISE_A STRISE_B STRISEL3 STLOW STLOW_A STLOW_B STLOWL3 DELMAG_A DELMAG_B DELMAGL3 ANSI18000903‐1‐en.vsdx ANSI18000903 V1 EN-US Figure 122: DELVSPVC connection diagram The vector shift detection guarantees fast and reliable detection of mains failure in almost all operational conditions when a distributed generation unit is running in parallel with the mains supply, but in certain cases this may fail.
  • Page 265 1MRK 505 370-UUS Rev. K Section 11 Secondary system supervision DeltaT: This setting defines the number of old cycles data to be used for delta calculation in RMS/DFT Mag and angle mode. Typical value is 2 cycles. This value is not used if OpMode is chosen as instantaneous 1 cycle or instantaneous 2 cycle.
  • Page 266 Section 11 1MRK 505 370-UUS Rev. K Secondary system supervision DelI>: This setting is used to detect the pickup value for instantaneous sample, RMS, DFT mag based delta detection. Set a typical value of 200% of IBase to use this function as fault detection. DeltaT: This setting defines the number of old cycles data to be used for delta calculation in RMS/DFT Mag mode.
  • Page 267 1MRK 505 370-UUS Rev. K Section 11 Secondary system supervision DelSt>: This setting is used to set the start value for delta detection. DeltaT: This setting defines the number of execution cycles of old data to be used for delta calculation. That is, if DeltaT setting is set as 6 for a 3 ms function, an 18 ms old value will be used to compare the change against.
  • Page 269 1MRK 505 370-UUS Rev. K Section 12 Control Section 12 Control 12.1 Synchronism check, energizing check, and synchronizing SESRSYN (25) IP14558-1 v4 12.1.1 Identification M14889-1 v4 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Synchrocheck, energizing check, and SESRSYN synchronizing sc/vc...
  • Page 270 Section 12 1MRK 505 370-UUS Rev. K Control sent in advance is using the measured SlipFrequency and the set tBreaker time. To prevent incorrect closing pulses, a maximum closing angle between bus and line is set with CloseAngleMax. Table below shows the maximum settable value for tBreaker when CloseAngleMax is set to 15 or 30 degrees, at different allowed slip frequencies for synchronizing.
  • Page 271 1MRK 505 370-UUS Rev. K Section 12 Control en04000179_ansi.vsd ANSI04000179 V1 EN-US Figure 123: Two interconnected power systems Figure shows two interconnected power systems. The cloud means that the interconnection can be further away, that is, a weak connection through other stations. The need for a check of synchronization increases if the meshed system decreases since the risk of the two networks being out of synchronization at manual or automatic closing is greater.
  • Page 272 Section 12 1MRK 505 370-UUS Rev. K Control SynchroCheck Bus voltage VHighBusSC > 50 – 120% of GblBaseSelBus Fuse fail VHighLineSC >50 – 120% of GblBaseSelLine Line Line Bus Voltage VDiffSC < 0.02 – 0.50 p.u. reference PhaseDiffM < 5 – 90 degrees voltage PhaseDiffA <...
  • Page 273 1MRK 505 370-UUS Rev. K Section 12 Control The energizing operation can operate in the dead line live bus (DLLB) direction, dead bus live line (DBLL) direction, or in both directions over the circuit breaker. Energizing from different directions can be different for automatic reclosing and manual closing of the circuit breaker.
  • Page 274 Section 12 1MRK 505 370-UUS Rev. K Control HMI, through selector switch function block, but alternatively there can for example, be a physical selector switch on the front of the panel which is connected to a binary to integer function block (B16I). If the PSTO input is used, connected to the Local-Remote switch on the local HMI, the choice can also be from the station HMI system, typically Hitachi Power grids Microscada through IEC 61850–8–1 communication.
  • Page 275 1MRK 505 370-UUS Rev. K Section 12 Control 12.1.3.1 Single circuit breaker with single busbar M12324-3 v12 SESRSYN (25) V3PB1* SYNOK Bus 1 V3PB2* AUTOSYOK V3PL1* AUTOENOK V3PL2* MANSYOK BLOCK MANENOK BLKSYNCH TSTSYNOK BLKSC TSTAUTSY BLKENERG TSTMANSY BUS1_OP TSTENOK BUS1_CL VSELFAIL Fuse BUS2_OP...
  • Page 276 Section 12 1MRK 505 370-UUS Rev. K Control 12.1.3.2 Single circuit breaker with double busbar, external voltage selection M12325-3 v8 SESRSYN (25) V3PB1* SYNOK V3PB2* AUTOSYOK V3PL1* AUTOENOK Bus 1 V3PL2* MANSYOK Bus 2 BLOCK MANENOK BLKSYNCH TSTSYNOK BLKSC TSTAUTSY BLKENERG TSTMANSY BUS1_OP...
  • Page 277 1MRK 505 370-UUS Rev. K Section 12 Control 12.1.3.3 Single circuit breaker with double busbar, internal voltage selection M12326-3 v7 SESRSYN (25) V3PB1* SYNOK V3PB2* AUTOSYOK V3PL1* AUTOENOK V3PL2* MANSYOK Bus 1 BLOCK MANENOK Bus 2 BLKSYNCH TSTSYNOK BLKSC TSTAUTSY BLKENERG TSTMANSY BUS1_OP...
  • Page 278 Section 12 1MRK 505 370-UUS Rev. K Control 12.1.3.4 Double circuit breaker M12329-3 v7 SESRSYN (25) V3PB1* SYNOK V3PB2* AUTOSYOK V3PL1* AUTOENOK V3PL2* MANSYOK BLOCK MANENOK BLKSYNCH TSTSYNOK BLKSC TSTAUTSY BLKENERG TSTMANSY BUS1_OP TSTENOK BUS1_CL VSELFAIL Fuse BUS2_OP B1SEL Voltage BUS2_CL B2SEL LINE1_OP...
  • Page 279 1MRK 505 370-UUS Rev. K Section 12 Control 12.1.3.5 Breaker-and-a-half M12330-3 v8 Figure describes a breaker-and-a-half arrangement with three SESRSYN functions in the same IED, each of them handling voltage selection for WA1_QA1, TIE_QA1 and WA2_QA1 breakers respectively. The voltage from busbar 1 VT is connected to V3PB1 on all three function blocks and the voltage from busbar 2 VT is connected to V3PB2 on all three function blocks.
  • Page 280 Section 12 1MRK 505 370-UUS Rev. K Control Bus 1 CB Bus 1 SESRSYN (25) Bus 2 V3PB1* SYNOK V3PB2* AUTOSYOK V3PL1* AUTOENOK V3PL2* MANSYOK BLOCK MANENOK BLKSYNCH TSTSYNOK BLKSC TSTAUTSY BLKENERG TSTMANSY Fuse BUS1_OP TSTENOK bus1 Voltage BUS1_CL VSELFAIL VREF1 BUS2_OP B1SEL...
  • Page 281 1MRK 505 370-UUS Rev. K Section 12 Control configurations must abide by the following rules: Normally apparatus position is connected with contacts showing both open (b-type) and closed positions (a-type). WA1_QA1: • BUS1_OP/CL = Position of TIE_QA1 breaker and belonging disconnectors •...
  • Page 282 Section 12 1MRK 505 370-UUS Rev. K Control found under Main menu/Settings /IED Settings/Control /Synchronizing(25,SC/VC)/SESRSYN(25,SC/ VC):X has been divided into four different setting groups: General, Synchronizing, Synchrocheck and Energizingcheck. General settings Operation: The operation mode can be set Enabled or Disabled. The setting Disabled disables the whole function.
  • Page 283 1MRK 505 370-UUS Rev. K Section 12 Control VDiffSynch Setting of the voltage difference between the line voltage and the bus voltage. The difference is set depending on the network configuration and expected voltages in the two networks running asynchronously. A normal setting is 0.10-0.15 p.u. FreqDiffMin The setting FreqDiffMin is the minimum frequency difference where the systems are defined to be asynchronous.
  • Page 284 Section 12 1MRK 505 370-UUS Rev. K Control The setting tMinSynch is set to limit the minimum time at which the synchronizing closing attempt is given. The synchronizing function will not give a closing command within this time, from when the synchronizing is started, even if a synchronizing condition is fulfilled.
  • Page 285 1MRK 505 370-UUS Rev. K Section 12 Control • Disabled, the energizing function is disabled. • DLLB, Dead Line Live Bus, the line voltage is below set value of VDeadLineEnerg and the bus voltage is above set value of VLIveBusEnerg. •...
  • Page 286 Section 12 1MRK 505 370-UUS Rev. K Control 12.2.1 Identification M14890-1 v7 Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Autorecloser for 1 phase, 2 phase and/or 3 SMBRREC phase 5(0 -->1) IEC15000204 V1 EN-US 12.2.2 Application M12391-3 v8 In certain countries it is standard practice to provide delayed restoration after busbar protection operation...
  • Page 287 1MRK 505 370-UUS Rev. K Section 12 Control Line protection Operate Operate time time Closed Circuit breaker Open Break time Closing time Break time Fault duration Fault duration AR open time for breaker Set AR open time Reset time Auto-reclosing function en04000146_ansi.vsd ANSI04000146 V1 EN-US...
  • Page 288 Section 12 1MRK 505 370-UUS Rev. K Control For the individual line breakers and auto reclosing equipment, the auto reclosing dead time expression is used. This is the dead time setting for the auto recloser. During simultaneous tripping and reclosing at the two line ends, auto reclosing dead time is approximately equal to the line dead time.
  • Page 289 1MRK 505 370-UUS Rev. K Section 12 Control When Single and/or three phase auto reclosing is considered, there are a number of cases where the tripping shall be three phase anyway. For example: • Evolving fault where the fault during the dead-time spreads to another phase. The other two phases must then be tripped and a three phase dead-time and auto reclose initiated •...
  • Page 290 Section 12 1MRK 505 370-UUS Rev. K Control • CBREADY, circuit breaker ready for a reclosing cycle, for example, charged operating gear. • CBCLOSED to ensure that the circuit breaker was closed when the line fault occurred and start was applied.
  • Page 291 1MRK 505 370-UUS Rev. K Section 12 Control 12.2.2.6 Long trip signal M12391-117 v4 In normal circumstances the auto recloser is started with a protection trip command which resets quickly due to fault clearing. The user can set a maximum start pulse duration tLongStartInh. This start pulse duration time is controlled by setting LongStartInhib.
  • Page 292 Section 12 1MRK 505 370-UUS Rev. K Control 12.2.2.10 ARMode = 1/2ph, 1-phase or 2-phase reclosing in the first shot M12391-136 v5 At single-pole or two-pole tripping, the operation is as in the example described above, program mode 1/2/3ph. If the first reclosing shot fails, a three-pole trip will be issued and three-pole auto reclosing can follow, if selected.
  • Page 293 1MRK 505 370-UUS Rev. K Section 12 Control MODEINT (integer) ARMode Type of fault 1st shot 2nd-5th shot 1ph + 1*2ph ....1/2ph + 1*3ph ..1ph + 1*2/3ph ..A start of a new auto reclosing cycle during the set “reset time” is blocked when the set number of reclosing shots have been reached.
  • Page 294 Section 12 1MRK 505 370-UUS Rev. K Control There is a counter for each type of auto reclosing command and one for the total number of auto reclosing commands. 12.2.2.17 Transient fault M12391-208 v4 After the breaker closing command the reclaim timer keeps running for the set tReclaim time. If no start (trip) occurs within this time, the auto recloser will reset.
  • Page 295 1MRK 505 370-UUS Rev. K Section 12 Control SMBRREC (79) BJ-TRIP INHIBIT ZCVPSOF-TRIP UNSUCCL SMBO ELECTRICAL RESET RELAY Lock-out CCRBRF (50BF) RXMD1 TRBU RESET MAIN ZAK CLOSE CLOSE COMMAND ANSI05000315_2_en.vsd ANSI05000315 V2 EN-US Figure 134: Lock-out arranged with an external lock-out relay SMBRREC (79) BJ-TRIP INHIBIT...
  • Page 296 Section 12 1MRK 505 370-UUS Rev. K Control 12.2.2.21 Automatic continuation of the auto reclosing sequence M12391-223 v5 The auto recloser can be programmed to proceed to the next auto reclosing shots (if multiple shots are selected) even if start signals are not received from protection functions, but the circuit breaker is still not closed.
  • Page 297 1MRK 505 370-UUS Rev. K Section 12 Control MODEINT The auto reclosing mode is selected with the ARMode setting. As an alternative to the setting, the mode can be selected by connecting an integer, for example from function block B16I, to the MODEINT input. The six possible modes are described in table 6 with their corresponding MODEINT integer value.
  • Page 298 Section 12 1MRK 505 370-UUS Rev. K Control connected to a permanently high source, TRUE. The signal is required for three-phase shots 1-5 to proceed (Note! Not the high-speed step). THOLHOLD Signal “Thermal overload protection holding back auto reclosing”. It can be connected to a thermal overload protection trip signal which resets only when the thermal content has fallen to an acceptable level, for example, 70%.
  • Page 299 1MRK 505 370-UUS Rev. K Section 12 Control • inProgress: auto recloser is started and dead time is in progress • reclaimTimeStarted: the circuit breaker closing command has started the reclaim timer • wait: an auto recloser, acting as slave, is waiting for a release from the master to proceed with its own reclosing sequence ACTIVE Indicates that the auto recloser is active, from start until end of reset time.
  • Page 300 Section 12 1MRK 505 370-UUS Rev. K Control SETON Indicates that auto recloser is switched on and operative. SUCCL If the circuit breaker closing command is given and the circuit breaker is closed within the set time interval tUnsucCl, the SUCCL output is activated after the set time interval tSuccessful. SYNCFAIL The SYNCFAIL output indicates that the auto recloser is inhibited because the synchrocheck or energizing check condition has not been fulfilled within the set time interval, tSync.
  • Page 301 1MRK 505 370-UUS Rev. K Section 12 Control SMBRREC (79) INPUT OUTPUT BLOCKED SETON BLKON INPROGR BLKOFF ACTIVE INHIBIT UNSUCCL SUCCL CBREADY PLCLOST CLOSECB PERMIT1P RESET TRIP-P3PTR PREP3P PROTECTION READY GROUND RELAYS xxxx-TRIP 1PT1 BLOCK 2PT1 3PT1 RI_HS 3PT2 SKIPHS 3PT3 ZCVPSOF-TRIP TRSOTF...
  • Page 302 Section 12 1MRK 505 370-UUS Rev. K Control The signals can be cross-connected to allow simple changing of the priority by just setting the High and the Low priorities without changing the configuration. The input 52a for each circuit breaker is important in multi-breaker arrangements to ensure that the circuit breaker was closed at the beginning of the cycle.
  • Page 303 1MRK 505 370-UUS Rev. K Section 12 Control The settings for the auto recloser are found under Main menu /Settings /IED Settings /Control / AutoRecloser(79,5(0->1)) /SMBRREC(79,5(0->)):X and have been divided into four different setting groups: General, CircuitBreaker, DeadTime and MasterSlave. General settings Operation: The operation of the auto recloser can be switched Enabled or Disabled.
  • Page 304 Section 12 1MRK 505 370-UUS Rev. K Control breaker will still be able to perform the C-O sequence. For the selection CO (circuit breaker ready for a Close – Open cycle) the condition is also checked after the set auto reclosing dead time. This selection has a value first of all at multi-shot auto reclosing to ensure that the circuit breaker is ready for a C-O sequence at shot two and further shots.
  • Page 305 1MRK 505 370-UUS Rev. K Section 12 Control DeadTime settings NoOfShots: In power transmission one shot is mostly used. In most cases one auto reclosing shot is sufficient as the majority of arcing faults will cease after the first auto reclosing shot. In power systems with many other types of faults caused by other phenomena, for example wind, a greater number of auto reclosing attempts (shots) can be motivated.
  • Page 306 Section 12 1MRK 505 370-UUS Rev. K Control 0.1sec because both master and slave should not send the circuit breaker closing command at the same time. 12.3 Apparatus control IP14560-1 v3 12.3.1 Function revision history GUID-CC62CA75-201A-4C5D-9FD4-89DBFD56F97C v2 12.3.2 Application M13443-4 v15 The apparatus control is a functionality for control and supervising of circuit breakers, disconnectors, and grounding switches within a bay.
  • Page 307 1MRK 505 370-UUS Rev. K Section 12 Control • Pole discrepancy supervision • Operation counter • Suppression of mid position The apparatus control function is realized by means of a number of function blocks designated: • Switch controller SCSWI • Circuit breaker SXCBR •...
  • Page 308 Section 12 1MRK 505 370-UUS Rev. K Control IEC 61850 QCBAY SCSWI SXCBR SXCBR SXCBR SCILO SXSWI SCSWI SCILO en05000116_ansi.vsd ANSI05000116 V1 EN-US Figure 140: Signal flow between apparatus control function blocks when all functions are situated within the IED Busbar protection REB670 Application manual ©...
  • Page 309 1MRK 505 370-UUS Rev. K Section 12 Control IEC 61850 on station bus Bay level IED QCBAY SCSWI SCILO GOOSEXLNRCV XLNPROXY SCSWI SCILO GOOSEXLNRCV XLNPROXY GOOSE over process bus Merging Unit XCBR -QB1 XCBR XCBR -QA1 XSWI -QB9 IEC16000070-1-EN.vsdx IEC16000070 V1 EN-US Figure 141: Signal flow between apparatus control functions with XCBR and XSWI located in a breaker IED Control operation can be performed from the local IED HMI.
  • Page 310 Section 12 1MRK 505 370-UUS Rev. K Control Accepted originator categories for PSTO If the requested command is accepted by the authority control, the value will change. Otherwise the attribute blocked-by-switching-hierarchy is set in the cause signal. If the PSTO value is changed during a command, then the command is aborted.
  • Page 311 1MRK 505 370-UUS Rev. K Section 12 Control QCBAY also provides blocking functions that can be distributed to different apparatuses within the bay. There are two different blocking alternatives: • Blocking of update of positions • Blocking of commands IEC13000016-2-en.vsd IEC13000016 V2 EN-US Figure 142: APC - Local remote function block 12.3.4...
  • Page 312 Section 12 1MRK 505 370-UUS Rev. K Control • Select and execute. • Select and until the reservation is granted. • Execute and the final end position of the apparatus. • Execute and valid close conditions from the synchronism check. At error the command sequence is cancelled.
  • Page 313 1MRK 505 370-UUS Rev. K Section 12 Control current status of the switch, such as blocking, selection, position, operating capability and operation counter. Since different switches are represented differently on IEC 61850, the data that is mandatory to model in IEC 61850 is mandatory inputs and the other useful data for the command and status following is optional.
  • Page 314 Section 12 1MRK 505 370-UUS Rev. K Control IEC16000072 V1 EN-US Figure 144: Configuration with XLNPROXY and GOOSEXLNRCV where only the mandatory data in the IEC 61850 modelling is used All the information from the XLNPROXY to the SCSWI about command following status, causes for failed command and selection status is transferred in the output XPOS.
  • Page 315 1MRK 505 370-UUS Rev. K Section 12 Control IEC61850 IEC61850 Cause Description Conditions Blocked-for-close-cmd The BLKCLS is active indicating that the switch is blocked for close commands. Blocked-by-process If the Blk input is connected and active indicating that the switch is dynamically blocked. Or if the OPCAP input is connected, it indicates that the operation capability of the switch is not enough to perform the command.
  • Page 316 Section 12 1MRK 505 370-UUS Rev. K Control SCSWI RES_GRT RES_RQ RESIN EXCH _IN QCRSV EXCH _ OUT RES_RQ1 From other . . . RES_RQ8 SCSWI in the bay RES_GRT1 To other RESIN SCSWI RES_GRT8 EXCH _IN in the EXCH _OUT RES_ DATA .
  • Page 317 1MRK 505 370-UUS Rev. K Section 12 Control SCSWI IntlReceive RESGRANT RES_EXT SELECTED SPGAPC IntlReceive Other SCWI in RESGRANT the bay . . . Station bus IEC05000178-3-en.vsd IEC05000178 V3 EN-US Figure 147: Application principle for an alternative reservation solution 12.3.8 Interaction between modules M16626-3 v11 A typical bay with apparatus control function consists of a combination of logical nodes or functions that...
  • Page 318 Section 12 1MRK 505 370-UUS Rev. K Control Synchronizing OK SMPPTRC SESRSYN (Trip logic) (Synchrocheck & Synchronizer) Trip QCBAY Operator place (Bay control) selection Open cmd Close cmd SCSWI SXCBR Res. req. (Switching control) (Circuit breaker) Res. granted QCRSV (Reservation) Res.
  • Page 319 1MRK 505 370-UUS Rev. K Section 12 Control SMPPTRC ZMQPDIS SECRSYN (Trip logic) (Synchrocheck) (Distance) Trip Synchrocheck QCBAY Operator place (Bay control) selection Open cmd Close cmd Res. req. SCSWI SXCBR (Switching control) Res. granted (Circuit breaker) QCRSV (Reservation) Res. req. Close CB SMBRREC (Auto-...
  • Page 320 Section 12 1MRK 505 370-UUS Rev. K Control GUID-A34013CF-497F-40B6-938A-965645FF5A8A V1 EN-US Figure 149: Example of how to allow the TRIP signal from SMPPTRC to override the blocked for open conditions 12.3.9 Setting guidelines M16669-3 v5 The setting parameters for the apparatus control function are set via the local HMI or PCM600. 12.3.9.1 Bay control (QCBAY) M16670-3 v7...
  • Page 321 1MRK 505 370-UUS Rev. K Section 12 Control The time parameter tResResponse is the allowed time from reservation request to the feedback reservation granted from all bays involved in the reservation function. When the time has expired, the control function is reset, and a cause-code is given. tSynchrocheck is the allowed time for the synchronism check function to fulfill the close conditions.
  • Page 322 Section 12 1MRK 505 370-UUS Rev. K Control 12.3.9.4 Proxy for signals from switching device via GOOSE XLNPROXY GUID-7C253FE7-6E02-4F94-96C7-81C9129D925D v1 The SwitchType setting controls the evaluation of the operating capability. If SwitchType is set to Circuit Breaker, the input OPCAP is interpreted as a breaker operating capability, otherwise it is interpreted as a switch operating capability.
  • Page 323 1MRK 505 370-UUS Rev. K Section 12 Control • To avoid the dangerous or damaging operation of switchgear • To enforce restrictions on the operation of the substation for other reasons for example, load configuration. Examples of the latter are to limit the number of parallel transformers to a maximum of two or to ensure that energizing is always from one side, for example, the high voltage side of a transformer.
  • Page 324 Section 12 1MRK 505 370-UUS Rev. K Control the configuration settings. The inputs for delivery specific conditions (Qx_EXy) are set to 1=TRUE if they are not used, except in the following cases: • 989_EX2 and 989_EX4 in modules BH_LINE_A and BH_LINE_B •...
  • Page 325 1MRK 505 370-UUS Rev. K Section 12 Control Signal 789OPTR 789 is open VP789TR The switch status for 789 is valid. EXDU_BPB No transmission error from the bay that contains the above information. For bay n, these conditions are valid: 789OPTR (bay 1) BB7_D_OP 789OPTR (bay 2)
  • Page 326 Section 12 1MRK 505 370-UUS Rev. K Control Signal BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2. BC_17_OP No bus-coupler connection between busbar WA1 and WA7. BC_17_CL A bus-coupler connection exists between busbar WA1and WA7. BC_27_OP No bus-coupler connection between busbar WA2 and WA7. BC_27_CL A bus-coupler connection exists between busbar WA2 and WA7.
  • Page 327 1MRK 505 370-UUS Rev. K Section 12 Control Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2. S1S2CLTR A bus-section coupler connection exists between bus-sections 1 and 2. VPS1S2TR The switch status of bus-section coupler BS is valid. EXDU_BS No transmission error from the bay that contains the above information.
  • Page 328 Section 12 1MRK 505 370-UUS Rev. K Control BC12CLTR (sect.1) BC_12_CL DCCLTR (A1A2) DCCLTR (B1B2) BC12CLTR (sect.2) VPBC12TR (sect.1) VP_BC_12 VPDCTR (A1A2) VPDCTR (B1B2) VPBC12TR (sect.2) BC17OPTR (sect.1) BC_17_OP DCOPTR (A1A2) BC17OPTR (sect.2) BC17CLTR (sect.1) BC_17_CL DCCLTR (A1A2) BC17CLTR (sect.2) VPBC17TR (sect.1) VP_BC_17 VPDCTR (A1A2)
  • Page 329 1MRK 505 370-UUS Rev. K Section 12 Control 12.4.2.4 Configuration setting M13560-108 v4 If there is no bypass busbar and therefore no 789 disconnector, then the interlocking for 789 is not used. The states for 789, 7189G, BB7_D, BC_17, BC_27 are set to open by setting the appropriate module inputs as follows.
  • Page 330 Section 12 1MRK 505 370-UUS Rev. K Control WA1 (A) WA2 (B) WA7 (C) 2089 189G 289G en04000514_ansi.vsd ANSI04000514 V1 EN-US Figure 154: Switchyard layout ABC_BC (3) 12.4.3.2 Configuration M13553-138 v4 The signals from the other bays connected to the bus-coupler module ABC_BC are described below. 12.4.3.3 Signals from all feeders M13553-6 v4...
  • Page 331 1MRK 505 370-UUS Rev. K Section 12 Control 1289OPTR (bay 1) BBTR_OP 1289OPTR (bay 2) ..1289OPTR (bay n-1) VP1289TR (bay 1) VP_BBTR VP1289TR (bay 2) ..VP1289TR (bay n-1) EXDU_12 (bay 1) EXDU_12 EXDU_12 (bay 2)
  • Page 332 Section 12 1MRK 505 370-UUS Rev. K Control Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2. VPS1S2TR The switch status of bus-section coupler BS is valid. EXDU_BS No transmission error from the bay that contains the above information. For a bus-coupler bay in section 1, these conditions are valid: BBTR_OP (sect.1) BBTR_OP...
  • Page 333 1MRK 505 370-UUS Rev. K Section 12 Control Signal BC_12_CL Another bus-coupler connection exists between busbar WA1 and WA2. VP_BC_12 The switch status of BC_12 is valid. EXDU_BC No transmission error from any bus-coupler bay (BC). These signals from each bus-coupler bay (ABC_BC), except the own bay, are needed: Signal BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1...
  • Page 334 Section 12 1MRK 505 370-UUS Rev. K Control For a bus-coupler bay in section 2, the same conditions as above are valid by changing section 1 to section 2 and vice versa. 12.4.3.5 Configuration setting M13553-107 v4 If there is no bypass busbar and therefore no 289 and 789 disconnectors, then the interlocking for 289 and 789 is not used.
  • Page 335 1MRK 505 370-UUS Rev. K Section 12 Control WA1 (A) WA2 (B) 189G AB_TRAFO 289G 389G 252 and 489G are not used in this interlocking 489G en04000515_ansi.vsd ANSI04000515 V1 EN-US Figure 160: Switchyard layout AB_TRAFO (3) M13566-4 v4 The signals from other bays connected to the module AB_TRAFO are described below. 12.4.4.2 Signals from bus-coupler M13566-6 v4...
  • Page 336 Section 12 1MRK 505 370-UUS Rev. K Control Signal BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2. VP_BC_12 The switch status of BC_12 is valid. EXDU_BC No transmission error from bus-coupler bay (BC). The logic is identical to the double busbar configuration “Signals from bus-coupler“. 12.4.4.3 Configuration setting M13566-22 v5...
  • Page 337 1MRK 505 370-UUS Rev. K Section 12 Control WA1 (A1) WA2 (A2) 289G 189G 489G 389G A1A2_BS en04000516_ansi.vsd ANSI04000516 V1 EN-US Figure 162: Switchyard layout A1A2_BS (3) M15111-4 v3 The signals from other bays connected to the module A1A2_BS are described below. 12.4.5.2 Signals from all feeders M15111-6 v4...
  • Page 338 Section 12 1MRK 505 370-UUS Rev. K Control Signal 1289OPTR 189 or 289 or both are open. VP1289TR The switch status of 189 and 289 are valid. EXDU_12 No transmission error from the bay that contains the above information. These signals from each bus-coupler bay (ABC_BC) are needed: Signal BC12OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 and...
  • Page 339 1MRK 505 370-UUS Rev. K Section 12 Control S1S2OPTR (B1B2) BC12OPTR (sect.1) 1289OPTR (bay 1/sect.2) . . . BBTR_OP . . . 1289OPTR (bay n/sect.2) S1S2OPTR (B1B2) BC12OPTR (sect.2) 1289OPTR (bay 1/sect.1) ..1289OPTR (bay n /sect.1) VPS1S2TR (B1B2) VPBC12TR (sect.1) VP1289TR (bay 1/sect.2)
  • Page 340 Section 12 1MRK 505 370-UUS Rev. K Control S1S2OPTR (A1A2) BC12OPTR (sect.1) 1289OPTR (bay 1/sect.2) . . . BBTR_OP . . . 1289OPTR (bay n/sect.2) S1S2OPTR (A1A2) BC12OPTR (sect.2) 1289OPTR (bay 1/sect.1) ..1289OPTR (bay n /sect.1) VPS1S2TR (A1A2) VPBC12TR (sect.1) VP1289TR (bay 1/sect.2)
  • Page 341 1MRK 505 370-UUS Rev. K Section 12 Control 12.4.6.1 Application M13544-3 v7 The interlocking for bus-section disconnector (A1A2_DC, 3) function is used for one bus-section disconnector between section 1 and 2 according to figure 166. A1A2_DC (3) function can be used for different busbars, which includes a bus-section disconnector.
  • Page 342 Section 12 1MRK 505 370-UUS Rev. K Control Signal 189OPTR 189 is open. 289OPTR 289 is open (AB_TRAFO, ABC_LINE). 22089OTR 289 and 2089 are open (ABC_BC). VP189TR The switch status of 189 is valid. VP289TR The switch status of 289 is valid. V22089TR The switch status of 289 and 2089 are valid.
  • Page 343 1MRK 505 370-UUS Rev. K Section 12 Control 189OPTR (bay 1/sect.A2) S2DC_OP ..189OPTR (bay n/sect.A2) DCOPTR (A2/A3) VP189TR (bay 1/sect.A2) VPS2_DC ..VP189TR (bay n/sect.A2) VPDCTR (A2/A3) EXDU_BB (bay 1/sect.A2) .
  • Page 344 Section 12 1MRK 505 370-UUS Rev. K Control 289OPTR (22089OTR)(bay 1/sect.B2) S2DC_OP ..289OPTR (22089OTR)(bay n/sect.B2) DCOPTR (B2/B3) VP289TR(V22089TR) (bay 1/sect.B2) VPS2_DC ..VP289TR(V22089TR) (bay n/sect.B2) VPDCTR (B2/B3) EXDU_BB (bay 1/sect.B2) .
  • Page 345 1MRK 505 370-UUS Rev. K Section 12 Control Signal S1DC_OP All disconnectors on bus-section 1 are open. S2DC_OP All disconnectors on bus-section 2 are open. VPS1_DC The switch status of all disconnectors on bus-section 1 is valid. VPS2_DC The switch status of all disconnectors on bus-section 2 is valid. EXDU_BB No transmission error from double-breaker bay (DB) that contains the above information.
  • Page 346 Section 12 1MRK 505 370-UUS Rev. K Control 189OPTR (bay 1/sect.A2) S2DC_OP ..189OPTR (bay n/sect.A2) VP189TR (bay 1/sect.A2) VPS2_DC ..VP189TR (bay n/sect.A2) EXDU_DB (bay 1/sect.A2) EXDU_BB .
  • Page 347 1MRK 505 370-UUS Rev. K Section 12 Control 12.4.6.4 Signals in breaker and a half arrangement M13542-127 v5 If the busbar is divided by bus-section disconnectors, the condition for the busbar disconnector bay no other disconnector connected to the bus-section must be made by a project-specific logic. The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC.
  • Page 348 Section 12 1MRK 505 370-UUS Rev. K Control 12.4.7.2 Signals in single breaker arrangement M15053-6 v5 The busbar grounding switch is only allowed to operate if all disconnectors of the bus-section are open. Section 1 Section 2 (WA1)A1 (WA2)B1 (WA7)C A1A2_DC(BS) B1B2_DC(BS) BB_ES...
  • Page 349 1MRK 505 370-UUS Rev. K Section 12 Control corresponding signals from busbar B are used. The same type of module (A1A2_BS) is used for different busbars, that is, for both bus-section circuit breakers A1A2_BS and B1B2_BS. Signal 189OPTR 189 is open. 289OPTR 289 is open.
  • Page 350 Section 12 1MRK 505 370-UUS Rev. K Control 189OPTR (bay 1/sect.A2) BB_DC_OP ..189OPTR (bay n/sect.A2) DCOPTR (A1/A2) VP189TR (bay 1/sect.A2) VP_BB_DC ..VP189TR (bay n/sect.A2) VPDCTR (A1/A2) EXDU_BB (bay 1/sect.A2) .
  • Page 351 1MRK 505 370-UUS Rev. K Section 12 Control 289OPTR(22089OTR) (bay 1/sect.B2) BB_DC_OP ..289OPTR(22089OTR) (bay n/sect.B2) DCOPTR (B1/B2) VP289TR(V22089TR) (bay 1/sect.B2) VP_BB_DC ..VP289TR(V22089TR) (bay n/sect.B2) VPDCTR (B1/B2) EXDU_BB (bay 1/sect.B2) .
  • Page 352 Section 12 1MRK 505 370-UUS Rev. K Control Section 1 Section 2 (WA1)A1 (WA2)B1 A1A2_DC(BS) B1B2_DC(BS) BB_ES BB_ES DB_BUS DB_BUS en04000511_ansi.vsd ANSI04000511 V1 EN-US Figure 185: Busbars divided by bus-section disconnectors (circuit breakers) To derive the signals: Signal BB_DC_OP All disconnectors of this part of the busbar are open. VP_BB_DC The switch status of all disconnectors on this part of the busbar are valid.
  • Page 353 1MRK 505 370-UUS Rev. K Section 12 Control Section 1 Section 2 (WA1)A1 (WA2)B1 A1A2_DC(BS) B1B2_DC(BS) BB_ES BB_ES BH_LINE BH_LINE en04000512_ansi.vsd ANSI04000512 V1 EN-US Figure 186: Busbars divided by bus-section disconnectors (circuit breakers) The project-specific logic are the same as for the logic for the double busbar configuration described in section “Signals in single breaker arrangement”.
  • Page 354 Section 12 1MRK 505 370-UUS Rev. K Control Three types of interlocking modules per double circuit breaker bay are defined. DB_BUS_A (3) handles the circuit breaker QA1 that is connected to busbar WA1 and the disconnectors and grounding switches of this section. DB_BUS_B (3) handles the circuit breaker QA2 that is connected to busbar WA2 and the disconnectors and grounding switches of this section.
  • Page 355 1MRK 505 370-UUS Rev. K Section 12 Control WA1 (A) WA2 (B) 189G 189G 289G 289G 389G 389G BH_LINE_B BH_LINE_A 6189 6289 289G 189G 989G 989G BH_CONN en04000513_ansi.vsd ANSI04000513 V1 EN-US Figure 188: Switchyard layout breaker-and-a-half M13570-7 v4 Three types of interlocking modules per diameter are defined. BH_LINE_A (3) and BH_LINE_B (3) are the connections from a line to a busbar.
  • Page 356 Section 12 1MRK 505 370-UUS Rev. K Control • VOLT_OFF = 1 • VOLT_ON = 0 12.5 Logic rotating switch for function selection and LHMI presentation SLGAPC SEMOD114936-1 v5 12.5.1 Identification SEMOD167845-2 v3 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number...
  • Page 357 1MRK 505 370-UUS Rev. K Section 12 Control StopAtExtremes: Sets the behavior of the switch at the end positions – if set to Disabled, when pressing UP while on first position, the switch will jump to the last position; when pressing DOWN at the last position, the switch will jump to the first position;...
  • Page 358 Section 12 1MRK 505 370-UUS Rev. K Control parameter. Also, being accessible on the single line diagram (SLD), this function block has two control modes (settable through CtlModel): Dir Norm and SBO Enh. 12.7 Generic communication function for Double Point indication DPGAPC SEMOD55384-1 v4 12.7.1...
  • Page 359 1MRK 505 370-UUS Rev. K Section 12 Control 12.7.3 Setting guidelines SEMOD55398-5 v5 The function does not have any parameters available in the local HMI or PCM600. 12.8 Single point generic control 8 signals SPC8GAPC SEMOD176448-1 v3 12.8.1 Identification SEMOD176456-2 v3 Function description IEC 61850 IEC 60617...
  • Page 360 Section 12 1MRK 505 370-UUS Rev. K Control 12.9.1 Identification GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number AutomationBits, command function for AUTOBITS DNP3 12.9.2 Application SEMOD158637-5 v4 Automation bits, command function for DNP3 (AUTOBITS) is used within PCM600 in order to get into the configuration the commands coming through the DNP3.0 protocol.
  • Page 361 1MRK 505 370-UUS Rev. K Section 12 Control sending a pulse to the binary outputs of the IED. Figure shows a close operation. An open breaker operation is performed in a similar way but without the synchro-check condition. This function is only used for SPA and LON communication. Single command function...
  • Page 362 Section 12 1MRK 505 370-UUS Rev. K Control Single command function Configuration logic circuits SINGLESMD Device 1 CMDOUTy OUTy User- defined conditions en04000208_ansi.vsd ANSI04000208 V2 EN-US Figure 192: Application example showing a logic diagram for control of external devices via configuration logic circuits 12.10.3 Setting guidelines...
  • Page 363 1MRK 505 370-UUS Rev. K Section 13 Logic Section 13 Logic 13.1 Trip matrix logic TMAGAPC IP15121-1 v4 13.1.1 Identification SEMOD167882-2 v3 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Trip matrix logic TMAGAPC 13.1.2 Application M15321-3 v14 The trip matrix logic (TMAGAPC) function is used to route trip signals and other logical output signals to different output contacts on the IED.
  • Page 364 Section 13 1MRK 505 370-UUS Rev. K Logic 13.2.2 Application GUID-70B268A9-B248-422D-9896-89FECFF80B75 v1 Group alarm logic function ALMCALH is used to route alarm signals to different LEDs and/or output contacts on the IED. ALMCALH output signal and the physical outputs allows the user to adapt the alarm signal to physical tripping outputs according to the specific application needs.
  • Page 365 1MRK 505 370-UUS Rev. K Section 13 Logic 13.4.1.2 Setting guidelines GUID-7E776D39-1A42-4F90-BF50-9B38F494A01E v2 Operation: Enabled or Disabled 13.5 Configurable logic blocks IP11009-1 v4 The configurable logic blocks are available in two categories: • Configurable logic blocks that do not propagate the time stamp and the quality of signals. They do not have the suffix QT at the end of their function block name, for example, SRMEMORY.
  • Page 366 Section 13 1MRK 505 370-UUS Rev. K Logic IEC09000695_2_en.vsd IEC09000695 V2 EN-US Figure 193: Example designation, serial execution number and cycle time for logic function IEC09000310-2-en.vsd IEC09000310 V2 EN-US Figure 194: Example designation, serial execution number and cycle time for logic function that also propagates timestamp and quality of input signals The execution of different function blocks within the same cycle is determined by the order of their serial execution numbers.
  • Page 367 1MRK 505 370-UUS Rev. K Section 13 Logic Example for use of GRP_OFF signal in FXDSIGN The Restricted earth fault function (REFPDIF) (87N) can be used both for auto-transformers and normal transformers. When used for auto-transformers, information from both windings parts, together with the neutral point current, needs to be available to the function.
  • Page 368 Section 13 1MRK 505 370-UUS Rev. K Logic 13.7 Boolean 16 to Integer conversion B16I SEMOD175715-1 v1 13.7.1 Identification SEMOD175721-2 v2 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Boolean 16 to integer conversion B16I 13.7.2 Application SEMOD175832-4 v4 Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary (logical) signals...
  • Page 369 1MRK 505 370-UUS Rev. K Section 13 Logic Name of input Type Default Description Value when Value when activated deactivated IN14 BOOLEAN Input 14 8192 IN15 BOOLEAN Input 15 16384 IN16 BOOLEAN Input 16 32768 The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are active that is=1;...
  • Page 370 Section 13 1MRK 505 370-UUS Rev. K Logic Name of input Type Default Description Value when Value when activated deactivated BOOLEAN Input 6 BOOLEAN Input 7 BOOLEAN Input 8 BOOLEAN Input 9 IN10 BOOLEAN Input 10 IN11 BOOLEAN Input 11 1024 IN12 BOOLEAN...
  • Page 371 1MRK 505 370-UUS Rev. K Section 13 Logic Name of input Type Default Description Value when Value when activated deactivated BOOLEAN Input 1 BOOLEAN Input 2 BOOLEAN Input 3 BOOLEAN Input 4 BOOLEAN Input 5 BOOLEAN Input 6 BOOLEAN Input 7 BOOLEAN Input 8 BOOLEAN...
  • Page 372 Section 13 1MRK 505 370-UUS Rev. K Logic More specifically, it transfers an integer input ZONCONI to a combination of activated binary outputs ZONEx (1≤x≤6) and CZ, so that:       ZONCONI CZ ZONEx  (Equation 94) IECEQUATION16077 V1 EN-US where 0≤ZONCONI≤127.
  • Page 373 1MRK 505 370-UUS Rev. K Section 13 Logic 13.11 Integer to Boolean 16 conversion with logic node representation ITBGAPC SEMOD158419-1 v3 13.11.1 Identification SEMOD167944-2 v4 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Integer to boolean 16 conversion with ITBGAPC logic node representation 13.11.2...
  • Page 374 Section 13 1MRK 505 370-UUS Rev. K Logic Name of OUTx Type Description Value when activated Value when deactivated OUT14 BOOLEAN Output 14 8192 OUT15 BOOLEAN Output 15 16384 OUT16 BOOLEAN Output 16 32768 The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16) are active equals 65535.
  • Page 375 1MRK 505 370-UUS Rev. K Section 13 Logic 13.13 Comparator for integer inputs - INTCOMP 13.13.1 Identification GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Comparison of integer values INTCOMP Int<=> 13.13.2 Application GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1 The function gives the possibility to monitor the level of integer values in the system relative to each other or to a fixed value.
  • Page 376 Section 13 1MRK 505 370-UUS Rev. K Logic Set the RefSource = Set Value SetValue shall be set between -2000000000 to 2000000000 Similarly for signed comparison between input and setting Set the EnaAbs = Signed Set the RefSource = Set Value SetValue shall be set between -2000000000 to 2000000000 13.14 Comparator for real inputs - REALCOMP...
  • Page 377 1MRK 505 370-UUS Rev. K Section 13 Logic • Absolute: Comparison is performed with absolute values of input and reference. • Signed: Comparison is performed with signed values of input and reference. RefSource: This setting is used to select the reference source between input and setting for comparison. •...
  • Page 378 Section 13 1MRK 505 370-UUS Rev. K Logic RefSource = Input REF EqualBandHigh = 5.0 % of reference value EqualBandLow = 5.0 % of reference value. Busbar protection REB670 Application manual © 2017 - 2021 Hitachi Power Grids. All rights reserved...
  • Page 379 1MRK 505 370-UUS Rev. K Section 14 Monitoring Section 14 Monitoring 14.1 Measurement GUID-9D2D47A0-FE62-4FE3-82EE-034BED82682A v1 14.1.1 Function revision history GUID-D462FD8B-5BC4-40A4-93C7-6CCC4F77FBC3 v1 14.1.2 Function revision history GUID-8EAA18E2-28AF-498A-889A-24AB7518ADDA v1 Document Product History revision revision 2.2.1 2.2.1 2.2.2 2.2.3 2.2.3 2.2.3 2.2.4 2.2.4 2.2.4 2.2.5 14.1.3...
  • Page 380 Section 14 1MRK 505 370-UUS Rev. K Monitoring Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Current sequence component CMSQI measurement I1, I2, I0 SYMBOL-VV V1 EN-US Voltage sequence component VMSQI measurement U1, U2, U0 SYMBOL-TT V1 EN-US Phase-neutral voltage measurement VNMMXU SYMBOL-UU V1 EN-US...
  • Page 381 1MRK 505 370-UUS Rev. K Section 14 Monitoring • I: phase currents (magnitude and angle) (CMMXU) • V: voltages (phase-to-ground and phase-to-phase voltage, magnitude and angle) (VMMXU, VNMMXU) The CVMMXN function calculates three-phase power quantities by using fundamental frequency phasors (DFT values) of the measured current and voltage signals.
  • Page 382 Section 14 1MRK 505 370-UUS Rev. K Monitoring • When system voltage falls below UGenZeroDB, values for S, P, Q, PF, ILAG, ILEAD, U and F are forced to zero. • When system current falls below IGenZeroDB, values for S, P, Q, PF, ILAG, ILEAD, U and F are forced to zero.
  • Page 383 1MRK 505 370-UUS Rev. K Section 14 Monitoring The following general settings can be set for the Phase-phase voltage measurement (VMMXU). VMagCompY: Amplitude compensation to calibrate voltage measurements at Y% of Vn, where Y is equal to 5, 30 or 100. VAngCompY: Angle compensation to calibrate angle measurements at Y% of Vn, where Y is equal to 5, 30 or 100.
  • Page 384 Section 14 1MRK 505 370-UUS Rev. K Monitoring first phase will be used as reference channel and compared with the curve for calculation of factors. The factors will then be used for all related channels. Magnitude % of In compensation IMagComp5 Measured current...
  • Page 385 1MRK 505 370-UUS Rev. K Section 14 Monitoring 380kV Busbar 800/5 A 380kV 120V 380kV OHL ANSI09000039-1-en.vsd ANSI09000039 V1 EN-US Figure 199: Single line diagram for 380kV OHL application In order to monitor, supervise and calibrate the active and reactive power as indicated in figure it is necessary to do the following: Set correctly CT and VT data and phase angle reference channel PhaseAngleRef using PCM600 for...
  • Page 386 Section 14 1MRK 505 370-UUS Rev. K Monitoring Setting Short Description Selected Comments value VBase (set in Base setting for voltage level in 400.00 Set rated OHL phase-to-phase voltage Global base) IBase (set in Base setting for current level in 1000 Set rated primary CT current used for OHL Global base)
  • Page 387 1MRK 505 370-UUS Rev. K Section 14 Monitoring Setting Short Description Selected Comments value IAngComp5 Angle calibration for current at 0.00 5% of In IAngComp30 Angle pre-calibration for current 0.00 at 30% of In IAngComp100 Angle pre-calibration for current 0.00 at 100% of In Measurement function application for a power transformer SEMOD54481-61 v9...
  • Page 388 Section 14 1MRK 505 370-UUS Rev. K Monitoring Table 52: General settings parameters for the Measurement function Setting Short description Selected Comment value Operation Operation Disabled/Enabled Enabled Function must be Enabled PowAmpFact Magnitude factor to scale power 1.000 Typically no scaling is required calculations PowAngComp Angle compensation for phase...
  • Page 389 1MRK 505 370-UUS Rev. K Section 14 Monitoring 230kV Busbar 300/5 100 MVA 15/0.12kV AB , 100 MVA 15.65kV 4000/5 ANSI09000041-1-en.vsd ANSI09000041 V1 EN-US Figure 201: Single line diagram for generator application In order to measure the active and reactive power as indicated in figure 201, it is necessary to do the following: Set correctly all CT and VT data and phase angle reference channel PhaseAngleRef using PCM600 for analog input channels...
  • Page 390 Section 14 1MRK 505 370-UUS Rev. K Monitoring Setting Short description Selected Comment value Low pass filter coefficient for 0.00 Typically no additional filtering is required power measurement, V and I VGenZeroDb Zero point clamping in % of Set minimum voltage level to 25% Vbase IGenZeroDb Zero point clamping in % of...
  • Page 391 1MRK 505 370-UUS Rev. K Section 14 Monitoring 14.2.4 Setting guidelines GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v4 The parameters for Gas medium supervision SSIMG can be set via local HMI or Protection and Control Manager PCM600. Operation: This is used to disable/enable the operation of gas medium supervision, that is, Off/On. PresAlmLimit: This is used to set the limit for a pressure alarm condition in the circuit breaker.
  • Page 392 Section 14 1MRK 505 370-UUS Rev. K Monitoring 14.3.2 Identification GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v4 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Insulation liquid monitoring function SSIML 14.3.3 Application GUID-140AA10C-4E93-4C23-AD57-895FADB0DB29 v8 Liquid medium supervision (SSIML ,71) is used for monitoring the oil insulated device condition. For example, transformers, shunt reactors, and so on.
  • Page 393 1MRK 505 370-UUS Rev. K Section 14 Monitoring Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Breaker monitoring SSCBR 14.4.2 Application GUID-45572680-3A39-4B3C-8639-4E4C5A95AA26 v10 The circuit breaker maintenance is usually based on regular time intervals or the number of operations performed.
  • Page 394 Section 14 1MRK 505 370-UUS Rev. K Monitoring 100000 50000 20000 10000 5000 2000 1000 Interrupted current (kA) IEC12000623_1_en.vsd IEC12000623 V1 EN-US Figure 202: An example for estimating the remaining life of a circuit breaker Calculation for estimating the remaining life The graph shows that there are 10000 possible operations at the rated operating current and 900 operations at 10 kA and 50 operations at rated fault current.
  • Page 395 1MRK 505 370-UUS Rev. K Section 14 Monitoring Accumulated energy Monitoring the contact erosion and interrupter wear has a direct influence on the required maintenance frequency. Therefore, it is necessary to accurately estimate the erosion of the contacts and condition of interrupters using cumulative summation of I .
  • Page 396 Section 14 1MRK 505 370-UUS Rev. K Monitoring 14.4.3.1 Setting procedure on the IED GUID-4E895FEA-74BF-4B11-A239-0574F8FF5188 v5 The parameters for breaker monitoring (SSCBR) can be set via the local HMI or Protection and Control Manager (PCM600). Common base IED values for primary current (IBase), primary voltage (VBase) and primary power (SBase) are set in Global base values for settings function GBASVAL.
  • Page 397 1MRK 505 370-UUS Rev. K Section 14 Monitoring OperTimeDelay: Time delay between change of status of trip output and start of main contact separation. 14.5 Event function EVENT IP14590-1 v2 14.5.1 Identification SEMOD167950-2 v2 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification...
  • Page 398 Section 14 1MRK 505 370-UUS Rev. K Monitoring M12811-34 v1 It is important to set the time interval for cyclic events in an optimized way to minimize the load on the station bus. 14.6 Disturbance report DRPRDRE IP14584-1 v2 14.6.1 Function revision history GUID-85FF8EB6-0D47-4776-8E1A-2F8F978B5F00 v2 Document...
  • Page 399 1MRK 505 370-UUS Rev. K Section 14 Monitoring Disturbance report DRPRDRE, always included in the IED, acquires sampled data of all selected analog and binary signals connected to the function blocks that is, • Maximum 30 external analog signals, • 10 internal derived analog signals, and •...
  • Page 400 Section 14 1MRK 505 370-UUS Rev. K Monitoring AxRADR Disturbance Report DRPRDRE Analog signals Trip value rec BxRBDR Disturbance recorder Binary signals Sequential of events Event recorder Indications ANSI09000337-2-en.vsd ANSI09000337 V2 EN-US Figure 203: Disturbance report functions and related function blocks For Disturbance report function there are a number of settings which also influences the sub-functions.
  • Page 401 1MRK 505 370-UUS Rev. K Section 14 Monitoring Operation M12179-82 v8 The operation of Disturbance report function DRPRDRE has to be set Enabled or Disabled. If Disabled is selected, note that no disturbance report is registered, and none sub-function will operate (the only general parameter that influences Sequential of events (SOE)).
  • Page 402 Section 14 1MRK 505 370-UUS Rev. K Monitoring In order to capture the new disturbance it is possible to allow retriggering (PostRetrig = Enabled) during the post-fault time. In this case a new, complete recording will pickup and, during a period, run in parallel with the initial recording.
  • Page 403 1MRK 505 370-UUS Rev. K Section 14 Monitoring OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relative nominal value for analog input M in percent of nominal value. 14.6.4.4 Sub-function parameters M12179-389 v3 All functions are in operation as long as Disturbance report is in operation. Indications M12179-448 v4 IndicationMaN: Indication mask for binary input N.
  • Page 404 Section 14 1MRK 505 370-UUS Rev. K Monitoring • Binary signals: Use only relevant signals to start the recording that is, protection trip, carrier receive and/or pickup signals. • Analog signals: The level triggering should be used with great care, since unfortunate settings will cause enormously number of recordings.
  • Page 405 1MRK 505 370-UUS Rev. K Section 14 Monitoring 14.8 Limit counter L4UFCNT GUID-22E141DB-38B3-462C-B031-73F7466DD135 v1 14.8.1 Identification GUID-F3FB7B33-B189-4819-A1F0-8AC7762E9B7E v3 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Limit counter L4UFCNT 14.8.2 Application GUID-41B13135-5069-4A5A-86CE-B7DBE9CFEF38 v2 Limit counter (L4UFCNT) is intended for applications where positive and/or negative sides on a binary signal need to be counted.
  • Page 406 Section 14 1MRK 505 370-UUS Rev. K Monitoring 14.9.3 Setting guidelines GUID-D3BED56A-BA80-486F-B2A8-E47F7AC63468 v1 The settings tAlarm and tWarning are user settable limits defined in hours. The achievable resolution of the settings is 0.1 hours (6 minutes). tAlarm and tWarning are independent settings, that is, there is no check if tAlarm > tWarning.
  • Page 407 1MRK 505 370-UUS Rev. K Section 14 Monitoring Moreover, in four-wire distribution systems (three-phase and neutral), the currents in the three phases will return via the neutral conductor, a 120 degree phase shift between corresponding phase currents that causes the currents to cancel out in the neutral, under balanced loading conditions. When nonlinear loads are present, any ‘Triplen’...
  • Page 408 Section 14 1MRK 505 370-UUS Rev. K Monitoring WrnLimitTHD: It defines the warning limit for the calculated total harmonic distortion. tDelayAlmTHD: It defines the alarm time limit for the calculated total harmonic distortion which is applied after the warning signal pickup and depends on its sustainability. This intimates the operator to take corrective operations immediately, otherwise the system will go under thermal stress.
  • Page 409 1MRK 505 370-UUS Rev. K Section 14 Monitoring 14.11 Voltage harmonic monitoring VHMMHAI(VTHD) GUID-B2F24353-AAEA-4520-BB1C-5FD5FFCFC67B v1 14.11.1 Function revision history GUID-E828F930-88FF-4D5B-8304-2BD3B89919B8 v1 Document Product History revision revision 2.2.3 2.2.3 2.2.3 2.2.4 2.2.4 2.2.4 2.2.5 Updated monitoring till 9 order voltage harmonics. Refer to document revision J for monitoring till 5 order voltage harmonics.
  • Page 410 Section 14 1MRK 505 370-UUS Rev. K Monitoring 14.11.4 Setting guidelines GUID-57719753-00C3-43F6-97B5-AA3B22618A3F v2 The recommended limits for total harmonic distortion and individual harmonic distortion are available in the IEEE 519-2014 standard. The limits are based on measurements which are done at the point of common coupling.
  • Page 411 1MRK 505 370-UUS Rev. K Section 14 Monitoring WrnLimit5thHD: It defines the warning limit for the calculated fifth harmonic distortion. According to standard IEEE 519-2014, harmonic voltage distortions on power system 161 kV and above is limited to 1.0% for each individual harmonic. tDelayAlm5thHD: It defines the alarm time limit for the calculated fifth harmonic distortion which is applied after the warning signal pickup and depends on its sustainability.
  • Page 412 Section 14 1MRK 505 370-UUS Rev. K Monitoring 14.12.2 Identification GUID-A5B9E605-328B-4168-BEE3-7BF30BC7E701 v1 Function description IEC 61850 identification IEC 60617 identification ANSI/IEEE C37.2 device number Fault current and voltage FLTMMXU monitoring function 14.12.3 Application GUID-2638C099-B885-4168-B4AC-CC837BCBF96E v1 Fault current and voltage monitoring function (FLTMMXU) is used for monitoring the fault data on occurrence of a fault event.
  • Page 413 1MRK 505 370-UUS Rev. K Section 14 Monitoring Instantaneous samples Peak value(SMAI o/p) RMS value(SMAI o/p) PreTrig PostTrig TRIGFLTUI Time duration for maximum peak and RMS current calculation IL1MAXPK IL1MAX FLTIL1MAG IL2MAXPK IL2MAX FLTIL2MAG IL3MAXPK IL3MAX FLTIL3MAG IEC21000227 V1 EN-US Figure 205: Maximum peak and RMS current calculation Busbar protection REB670 Application manual...
  • Page 414 Section 14 1MRK 505 370-UUS Rev. K Monitoring 14.12.4 Setting guidelines GUID-0A8DF112-1058-4B1C-BEB2-AAD055D99646 v1 The setting parameters for fault current and voltage reporting function FLTMMXU can be set via Protection and Control Manager PCM600. Operation: This is used to disable/enable the operation of fault current and voltage reporting function, that is, Off/On.
  • Page 415 1MRK 505 370-UUS Rev. K Section 14 Monitoring IEC21000229 V1 EN-US Figure 206: Current and voltage signals in the considered system The general setting parameters for FLTMMXU, OC4PTOC and SMPPTRC functions can be set as mentioned in Table Table 56 Table 57 respectively and the connection diagram is shown in Figure...
  • Page 416 Section 14 1MRK 505 370-UUS Rev. K Monitoring IEC21000230 V2 EN-US Figure 207: Connection diagram of OC4PTOC, SMPPTRC and FLTMMXU function Table 55: General setting parameters for the FLTMMXU function Setting Default value Operation PreTrig PostTrig Table 56: General setting parameters for the OC4PTOC function Name Description Value...
  • Page 417 1MRK 505 370-UUS Rev. K Section 14 Monitoring From the positive edge of the binary input TRIGFLTUI, the fault data will be stored for 5 cycles (0.083 s prior to TRIGFLTUI active, based on the setting PreTrig) prior to positive edge and 5 cycles (0.083 s post to TRIGFLTUI active, based on the setting PostTrig) post positive edge as shown in Figure 206 and is...
  • Page 419 1MRK 505 370-UUS Rev. K Section 15 Metering Section 15 Metering 15.1 Pulse-counter logic PCFCNT IP14600-1 v3 15.1.1 Identification M14879-1 v4 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Pulse-counter logic PCFCNT S00947 V1 EN-US 15.1.2 Application M13395-3 v6 Pulse-counter logic (PCFCNT) function counts externally generated binary pulses, for instance pulses...
  • Page 420 Section 15 1MRK 505 370-UUS Rev. K Metering The setting is common for all input channels on BIM, that is, if limit changes are made for inputs not connected to the pulse counter, the setting also influences the inputs on the same board used for pulse counting.
  • Page 421 1MRK 505 370-UUS Rev. K Section 15 Metering Alternatively, the energy values can be presented with use of the pulse counters function (PCGGIO). The output energy values are scaled with the pulse output setting values EAFAccPlsQty, EARAccPlsQty, ERFAccPlsQty and ERVAccPlsQty of the energy metering function and then the pulse counter can be set-up to present the correct values by scaling in this function.
  • Page 423 1MRK 505 370-UUS Rev. K Section 16 Ethernet-based communication Section 16 Ethernet-based communication 16.1 Access point 16.1.1 Application GUID-2942DF07-9BC1-4F49-9611-A5691D2C925C v1 The access points are used to connect the IED to the communication buses (like the station bus) that use communication protocols. The access point can be used for single and redundant data communication. The access points are also used for communication with the merging units and for time synchronization using Precision Time Protocol (PTP).
  • Page 424 Section 16 1MRK 505 370-UUS Rev. K Ethernet-based communication for the specific access point. For information on how to activate the individual communication protocols, see the communication protocol chapters. To increase security it is recommended to uncheck protocols that are not used on the access point.
  • Page 425 1MRK 505 370-UUS Rev. K Section 16 Ethernet-based communication Device 2 Device 1 PhyPortA PhyPortB PhyPortA PhyPortB Switch A Switch B PhyPortA PhyPortB PhyPortA PhyPortB Device 4 Device 3 IEC09000758-4-en.vsd IEC09000758 V4 EN-US Figure 210: Parallel Redundancy Protocol (PRP) Device 1 Device 2 PhyPortA PhyPortB...
  • Page 426 Section 16 1MRK 505 370-UUS Rev. K Ethernet-based communication 16.2.3 Setting guidelines GUID-887B0AE2-0F2E-414D-96FD-7EC935C5D2D8 v1 Redundant communication is configured with the Ethernet configuration tool in PCM600. Redundancy: redundant communication is activated when the parameter is set to PRP-0, PRP-1 or HSR. The settings for the next access point will be hidden and PhyPortB will show the second port information.
  • Page 427 1MRK 505 370-UUS Rev. K Section 16 Ethernet-based communication IEC17000044-1-en.vsdx IEC17000044 V1 EN-US Figure 213: Merging unit 16.3.2 Setting guidelines GUID-3449AB24-8C9D-4D9A-BD46-5DDF59A0F8E3 v1 For information on the merging unit setting guidelines, see section IEC/UCA 61850-9-2LE communication protocol. 16.4 Routes 16.4.1 Application GUID-19616AC4-0FFD-4FF4-9198-5E33938E5ABD v1 Setting up a route enables communication to a device that is located in another subnetwork.
  • Page 429 1MRK 505 370-UUS Rev. K Section 17 Station communication Section 17 Station communication 17.1 Communication protocols M14815-3 v15 Each IED is provided with several communication interfaces enabling it to connect to one or many substation level systems or equipment, either on the Substation Automation (SA) bus or Substation Monitoring (SM) bus.
  • Page 430 Section 17 1MRK 505 370-UUS Rev. K Station communication Engineering Station HSI Workstation Gateway Base System Printer KIOSK 3 KIOSK 1 KIOSK 2 IEC09000135_en.v IEC09000135 V1 EN-US Figure 214: SA system with IEC 61850–8–1 M16925-3 v4 Figure215 shows the GOOSE peer-to-peer communication. Station HSI MicroSCADA Gateway...
  • Page 431 1MRK 505 370-UUS Rev. K Section 17 Station communication 17.2.2 Setting guidelines SEMOD55317-5 v7 There are two settings related to the IEC 61850–8–1 protocol: Operation: User can set IEC 61850 communication to Enabled or Disabled. GOOSEPortEd1: Selection of the Ethernet link where GOOSE traffic shall be sent and received. This is only valid for Edition 1 and can be ignored if Edition 2 is used.
  • Page 432 Section 17 1MRK 505 370-UUS Rev. K Station communication 17.2.3.2 Receiving data GUID-CAE4B020-7131-49BF-BA29-3EEE0EFEA2B8 v2 The GOOSE data must be received at function blocks. There are different GOOSE receiving function blocks depending on the type of the received data. Refer to the Engineering manual for more information about how to configure GOOSE.
  • Page 433 1MRK 505 370-UUS Rev. K Section 17 Station communication Factors influencing the accuracy of the sampled values from the merging unit are, for example, anti aliasing filters, frequency range, step response, truncating, A/D conversion inaccuracy, time tagging accuracy etc. In principle, the accuracy of the current and voltage transformers, together with the merging unit, will have the same quality as the direct input of currents and voltages.
  • Page 434 Section 17 1MRK 505 370-UUS Rev. K Station communication Station Wide Station Wide SCADA System GPS Clock IEC61850-8-1 Splitter Electrical-to- Optical Converter IEC61850-8-1 110 V Other 1PPS Relays IEC61850-9-2LE Ethernet Switch IEC61850-9-2LE 1PPS Merging Unit Combi Sensor Conventional VT en08000069-3.vsd IEC08000069 V2 EN-US Figure 218: Example of a station configuration with the IED receiving analog values from both classical measuring transformers and merging units.
  • Page 435 1MRK 505 370-UUS Rev. K Section 17 Station communication SMAI function delivers a magnitude of zero with good quality for all the channels. Thus, this has no effect on a busbar protection, nor protections in an 1 1/2 circuit breaker configuration. SMAI function blocks exist in different cycle times, and all the SMAI blocks that receive SV streams from the merging units must have the block input signal configured in the same way to get the correct behavior.
  • Page 436 Section 17 1MRK 505 370-UUS Rev. K Station communication GUID-5AC45CBE-8933-4467-B7C0-275468556211 V1 EN-US Figure 220: SMAI configurations for single bay applications up to 12 bays Busbar protection REB670 Application manual © 2017 - 2021 Hitachi Power Grids. All rights reserved...
  • Page 437 1MRK 505 370-UUS Rev. K Section 17 Station communication GUID-235F41C6-FD66-4CB0-A062-09B65482805D V1 EN-US Figure 221: SMAI configurations for single bay applications larger than 12 bays For single-phase busbar applications, we support upto 12 bays, to cover upto 24 bays. Each SMAI handles current from 3 bays, but a SMAI only has one common block input. Therefore, 3 feeders must be out of service, before maintenance process starts on the faulty merging unit.
  • Page 438 Section 17 1MRK 505 370-UUS Rev. K Station communication 17.3.3 Bay out of service for maintenance GUID-4E073C5A-F0E3-4FCA-A0D8-B6972C395A4A v1 When a bay need maintenance and has energized merging unit connected, it is always a risk to get unplanned interruptions in the auxiliary power supply which may lead to unwanted blocking of protections.
  • Page 439 1MRK 505 370-UUS Rev. K Section 17 Station communication Function description IEC 61850 identification Busbar differential protection, zone 1 BZNPDIF_Zx, (1≤x≤6) Capacitor bank protection CBPGAPC Breaker failure protection CCRBRF Breaker failure protection, single phase version CCSRBRF General currrent and voltage protection CVGAPC Current delta supervision DELISPVC...
  • Page 440 Section 17 1MRK 505 370-UUS Rev. K Station communication be synchronized with the merging unit. However, the global/complete time might not be correct. Disturbance recordings then appear incorrect since analog data is timestamped by MU, and binary events use the internal IED time. It is thus recommended to use time synchronization also when analog data emanate from only one MU.
  • Page 441 1MRK 505 370-UUS Rev. K Section 17 Station communication Settings on the local HMI under Main menu/Configuration /Communication/Ethernet configuration / Access point/AP_X : • Operation: On • PTP: On Two status monitoring signals can be: • SYNCH signal on the MUx function block indicates that protection functions are blocked due to loss of internal time synchronization to the IED •...
  • Page 442 Section 17 1MRK 505 370-UUS Rev. K Station communication • SYNCH signal on the MUx function block indicates that protection functions are blocked due to loss of internal time synchronization to the IED. • MUSYNCH signal on the MUx function block monitors the synchronization flag smpSynch in the datastream and IED hardware time synchronization.
  • Page 443 1MRK 505 370-UUS Rev. K Section 17 Station communication IEC/UCA 61850-9-2LE Data IEC10000075=2=en=Original.vsd IEC10000075 V2 EN-US Figure 225: Setting example without time synchronization It is also possible to use IEC/UCA 61850-9-2LE communication without time synchronization. Settings on the local HMI under Main menu/Configuration /Time/Synchronization / TIMESYNCHGEN:1/IEC61850-9-2 : •...
  • Page 444 Section 17 1MRK 505 370-UUS Rev. K Station communication 17.4 LON communication protocol IP14420-1 v1 17.4.1 Application IP14863-1 v1 M14804-3 v6 Control Center Station HSI MicroSCADA Gateway Star coupler RER 111 IEC05000663-1-en.vsd IEC05000663 V2 EN-US Figure 226: Example of LON communication structure for a substation automation system An optical network can be used within the substation automation system.
  • Page 445 1MRK 505 370-UUS Rev. K Section 17 Station communication Hardware and software modules M14804-35 v5 The hardware needed for applying LON communication depends on the application, but one very central unit needed is the LON Star Coupler and optical fibers connecting the star coupler to the IEDs. To interface the IEDs from the MicroSCADA with Classic Monitor, application library LIB520 is required.
  • Page 446 Section 17 1MRK 505 370-UUS Rev. K Station communication 17.4.2.3 Setting guidelines SEMOD119915-1 v1 Settings M14789-4 v3 The parameters for the multiple command function are set via PCM600. The Mode setting sets the outputs to either a Steady or Pulsed mode. 17.5 SPA communication protocol IP14614-1 v1...
  • Page 447 1MRK 505 370-UUS Rev. K Section 17 Station communication can be applied on each fiber optic loop. A program is required in the master computer for interpretation of the SPA-bus codes and for translation of the data that should be sent to the IED. For the specification of the SPA protocol V2.5, refer to SPA-bus Communication Protocol V2.5.
  • Page 448 Section 17 1MRK 505 370-UUS Rev. K Station communication 17.6 IEC 60870-5-103 communication protocol IP14615-1 v2 17.6.1 Application IP14864-1 v1 M17109-3 v7 TCP/IP Control Station Center Gateway Star coupler ANSI05000660-4-en.vsd ANSI05000660 V4 EN-US Figure 228: Example of IEC 60870-5-103 communication structure for a substation automation system IEC 60870-5-103 communication protocol is mainly used when a protection IED communicates with a third party control or monitoring system.
  • Page 449 1MRK 505 370-UUS Rev. K Section 17 Station communication General M17109-43 v2 The protocol implementation consists of the following functions: • Event handling • Report of analog service values (measurands) • Fault location • Command handling • Autorecloser ON/OFF • Teleprotection ON/OFF •...
  • Page 450 Section 17 1MRK 505 370-UUS Rev. K Station communication Function blocks with user defined input signals in monitor direction, I103UserDef. These function blocks include the FUNCTION TYPE parameter for each block in the private range, and the INFORMATION NUMBER parameter for each input signal. •...
  • Page 451 1MRK 505 370-UUS Rev. K Section 17 Station communication and the information number for each signal. For more information on the description of the Disturbance report in the Technical reference manual. The analog channels, that are reported, are those connected to the disturbance function blocks A1RADR to A4RADR. The eight first ones belong to the public range and the remaining ones to the private range.
  • Page 452 Section 17 1MRK 505 370-UUS Rev. K Station communication GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN-US Figure 229: Settings for IEC 60870-5-103 communication The general settings for IEC 60870-5-103 communication are the following: • SlaveAddress and BaudRate: Settings for slave number and communication speed (baud rate). The slave number can be set to any value between 1 and 254.
  • Page 453 1MRK 505 370-UUS Rev. K Section 17 Station communication recorder for each input. The user must set these parameters to whatever he connects to the corresponding input. Refer to description of Main Function type set on the local HMI. Recorded analog channels are sent with ASDU26 and ASDU31. One information element in these ASDUs is called ACC, and it indicates the actual channel to be processed.
  • Page 454 Section 17 1MRK 505 370-UUS Rev. K Station communication DRA#-Input IEC103 meaning Private range Private range Private range Private range Private range Private range Private range Private range Private range 17.6.3 Function and information types M17109-145 v7 Product type IEC103mainFunType value Comment: REL 128 Compatible range REC 242 Private range, use default RED 192 Compatible range...
  • Page 455 1MRK 505 370-UUS Rev. K Section 17 Station communication 17.7 DNP3 Communication protocol 17.7.1 Application GUID-EF1F0C38-9FF6-4683-8B10-AAA372D42185 v1 For more information on the application and setting guidelines for the DNP3 communication protocol refer to the DNP3 Communication protocol manual. Busbar protection REB670 Application manual ©...
  • Page 457 1MRK 505 370-UUS Rev. K Section 18 Remote communication Section 18 Remote communication 18.1 Binary signal transfer IP12423-1 v2 18.1.1 Identification M14849-1 v4 Function description IEC 61850 identification IEC 60617 ANSI/IEEE C37.2 identification device number Binary signal transfer, BinSignRec1_1 receive BinSignRec1_2 BSR2M_305 BSR2M_312...
  • Page 458 Section 18 1MRK 505 370-UUS Rev. K Remote communication Important to know when connecting LDCM to SMAI function block with 3 or 8 ms cycle time. Doing so will affect all protections for the connected cycle time. LDCM 64kbit will increase trip time about 5 - 15 ms during normal conditions. LDCM 2Mbit will increase trip time about 2-3 ms during normal conditions.
  • Page 459 1MRK 505 370-UUS Rev. K Section 18 Remote communication en06000519-2.vsd IEC06000519 V2 EN-US Figure 231: Direct fiber optical connection between two IEDs with LDCM The LDCM can also be used together with an external optical to galvanic G.703 converter or with an alternative external optical to galvanic X.21 as shown in figure 232.
  • Page 460 Section 18 1MRK 505 370-UUS Rev. K Remote communication possible to use LDCM communication modules to effectively share the binary Ios between three units, as shown in figure 233233. <= 192 Binary Signals => Wire status of REB 670, B31 disconnectors Phase L1 from Bays 01-08...
  • Page 461 1MRK 505 370-UUS Rev. K Section 18 Remote communication OutOfService is selected, the IED should have active communication to the remote end during the whole maintenance process, that is, no restart or removal of the fiber can be done. This setting does not apply to two-end communication. Blocked IED does not use data from the LDCM OutOfService...
  • Page 462 Section 18 1MRK 505 370-UUS Rev. K Remote communication Short-range LDCM: Use LowPower for fibers 0 – 1 km and HighPower for fibers greater than 1 km. Medium-range LDCM: Typical distance 80 km for HighPower. Long-range LDCM: Typical distance 120 km for HighPower. An optical budget calculation should be made for the actual case.
  • Page 463 1MRK 505 370-UUS Rev. K Section 18 Remote communication Table 63: Example of calculating the optical budget (maximum distance) Type of LDCM Short range (SR) Short range (SR) Medium range (MR) Long range (LR) Type of fibre Multi-mode fiber glass Multi-mode fiber glass Single-mode fiber Single-mode fiber...
  • Page 464 Section 18 1MRK 505 370-UUS Rev. K Remote communication • one of the two possible local currents is transmitted • sum of the two local currents is transmitted • channel is used as a redundant backup channel breaker-and-a-half arrangement has two local currents, and the Current Transformer (CT) grounding for those can differ.
  • Page 465 1MRK 505 370-UUS Rev. K Section 19 Security Section 19 Security 19.1 Authority status ATHSTAT SEMOD158575-1 v2 19.1.1 Application SEMOD158527-5 v3 Authority status (ATHSTAT) function is an indication function block, which informs about two events related to the IED and the user authorization: •...
  • Page 466 Section 19 1MRK 505 370-UUS Rev. K Security The information can, in addition to be viewed on the built in HMI, also be retrieved with the aid of a PC with PCM600 installed and by using the Event Monitoring Tool. The PC can either be connected to the front port, or to the port at the back of the IED.
  • Page 467 1MRK 505 370-UUS Rev. K Section 19 Security 19.4 Denial of service SCHLCCH/RCHLCCH 19.4.1 Application GUID-64F4D905-9F73-4073-B8F6-8D373155316A v5 The denial of service functionality is designed to limit the CPU load that can be produced by Ethernet network traffic on the IED. The communication facilities must not be allowed to compromise the primary functionality of the device.
  • Page 469 1MRK 505 370-UUS Rev. K Section 20 Basic IED functions Section 20 Basic IED functions 20.1 IED identifiers TERMINALID IP15060-1 v2 20.1.1 Application M15324-3 v7 IED identifiers (TERMINALID) function allows the user to identify the individual IED in the system, not only in the substation, but in a whole region or a country.
  • Page 470 Section 20 1MRK 505 370-UUS Rev. K Basic IED functions • Describes the type of the IED. Example: REL670 • ProductDef • Describes the release number from the production. Example: 2.1.0 • FirmwareVer • Describes the firmware version. • The firmware version can be checked from Main menu/Diagnostics/IED status/Product identifiers •...
  • Page 471 1MRK 505 370-UUS Rev. K Section 20 Basic IED functions 20.3.3 Setting guidelines SEMOD113223-4 v1 There are no settable parameters for the measured value expander block function. 20.4 Parameter setting groups IP1745-1 v1 20.4.1 Application M12007-6 v10 Six sets of settings are available to optimize IED operation for different power system conditions. By creating and switching between fine tuned setting sets, either from the local HMI or configurable binary inputs, results in a highly adaptable IED that can cope with a variety of power system scenarios.
  • Page 472 Section 20 1MRK 505 370-UUS Rev. K Basic IED functions 20.5.2 Application M15288-3 v6 The rated system frequency and phase rotation direction are set under Main menu /Configuration / Power system / Primary Values in the local HMI and PCM600 parameter setting tree. 20.5.3 Setting guidelines M15292-3 v2...
  • Page 473 1MRK 505 370-UUS Rev. K Section 20 Basic IED functions 20.7.1 Identification GUID-0D5405BE-E669-44C8-A208-3A4C86D39115 v3 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Global base values GBASVAL 20.7.2 Application GUID-D58ECA9A-9771-443D-BF84-8EF582A346BF v4 Global base values function (GBASVAL) is used to provide global values, common for all applicable functions within the IED.
  • Page 474 Section 20 1MRK 505 370-UUS Rev. K Basic IED functions 20.9 Signal matrix for binary outputs SMBO SEMOD55215-1 v2 20.9.1 Application SEMOD55213-5 v4 The Signal matrix for binary outputs function SMBO is used within the Application Configuration tool in direct relation with the Signal Matrix tool. SMBO represents the way binary outputs are sent from one IED configuration.
  • Page 475 1MRK 505 370-UUS Rev. K Section 20 Basic IED functions 20.11.2 Frequency values GUID-B494B93C-B5AA-4FD6-8080-8611C34C2AD8 v5 The SMAI function includes a functionality based on the level of positive sequence voltage, MinValFreqMeas, to validate if the frequency measurement is valid or not. If the positive sequence voltage is lower than MinValFreqMeas, the function freezes the frequency output value for 500 ms and after that the frequency output is set to the nominal value.
  • Page 476 Section 20 1MRK 505 370-UUS Rev. K Basic IED functions However, this configuration, combined with unbalanced three-phase input, results in incorrect calculated phase-earth values. This in turn may result in maloperation of functions connected to SMAIs configured in this way, if the function uses phase-earth based values.
  • Page 477 1MRK 505 370-UUS Rev. K Section 20 Basic IED functions Even if the user sets the AnalogInputType of a SMAI block to “Current”, the MinValFreqMeas is still visible. However, using the current channel values as base for frequency measurement is not recommendable for a number of reasons, not last among them being the low level of currents that one can have in normal operating conditions.
  • Page 478 Section 20 1MRK 505 370-UUS Rev. K Basic IED functions Task time group 1 SMAI instance 3 phase group SMAI1:1 SMAI2:2 DFTRefGrp7 SMAI3:3 SMAI4:4 SMAI5:5 SMAI6:6 SMAI7:7 SMAI8:8 SMAI9:9 SMAI10:10 SMAI11:11 SMAI12:12 Task time group 2 DFTRefGrp4 SMAI instance 3 phase group SMAI1:13 SMAI2:14 SMAI3:15...
  • Page 479 1MRK 505 370-UUS Rev. K Section 20 Basic IED functions The examples shows a situation with adaptive frequency tracking with one reference selected for all instances. In practice each instance can be adapted to the needs of the actual application. The adaptive frequency tracking is needed in IEDs that belong to the protection system of synchronous machines and that are active during run-up and shout-down of the machine.
  • Page 480 Section 20 1MRK 505 370-UUS Rev. K Basic IED functions SMAI1:13 – SMAI12:24: DFTReference = ExternalDFTRef to use DFTSPFC input of SMAI1:13 as reference (SMAI7:7) For task time group 3 this gives the following settings: SMAI1:25 – SMAI12:36: DFTReference = ExternalDFTRef to use DFTSPFC input as reference (SMAI7:7) For task time group 4 this gives the following settings: SMAI1:37 –...
  • Page 481 1MRK 505 370-UUS Rev. K Section 20 Basic IED functions For task time group 2 this gives the following settings: SMAI1:13: DFTRefExtOut = DFTRefGrp4 to route SMAI4:16 reference to the SPFCOUT output, DFTReference = DFTRefGrp4 for SMAI1:13 to use SMAI4:16 as reference (see Figure 238) SMAI2:14 – SMAI12:24: DFTReference = DFTRefGrp4 to use SMAI4:16 as reference.
  • Page 482 Section 20 1MRK 505 370-UUS Rev. K Basic IED functions SMAI1:1 – SMAI12:12: DFTReference = ExternalDFTRef to use DFTSPFC input as reference (SMAI6:42) For task time group 2 this gives the following settings: SMAI1:13 – SMAI12:24: DFTReference = ExternalDFTRef to use DFTSPFC input as reference (SMAI6:42) For task time group 3 this gives the following settings: SMAI1:25 –...
  • Page 483 1MRK 505 370-UUS Rev. K Section 20 Basic IED functions The DataObject Mod of the Root LD.LNN0 can be set on the LHMI under Main menu/Test/Function test modes/Communication/Station communication /IEC61850 LD0 LLN0/LD0LLN0:1 to On, Off, TestBlocked,Test or Blocked. When the setting of the DataObject Mod is changed at this level, all Logical Nodes inside the logical device update their own behavior according to IEC61850-7-4.
  • Page 484 Section 20 1MRK 505 370-UUS Rev. K Basic IED functions Forcing of binary input and output signals is only possible when the IED is in IED test mode. 20.13 Time synchronization TIMESYNCHGEN IP1750-1 v2 20.13.1 Application M11345-3 v13 Use time synchronization to achieve a common time base for the IEDs in a protection and control system.
  • Page 485 1MRK 505 370-UUS Rev. K Section 20 Basic IED functions IEEE 1588 (PTP) PTP according to IEEE 1588-2008 and specifically its profile IEC/IEEE 61850-9-3 for power utility automation is a synchronization method that can be used to maintain a common time within a station. This time can be synchronized to the global time using, for instance, a GPS receiver.
  • Page 486 Section 20 1MRK 505 370-UUS Rev. K Basic IED functions The function input to be used for minute-pulse synchronization is called BININPUT. For a description of the BININPUT settings, see the Technical Manual. The system time can be set manually, either via the local HMI or via any of the communication ports. The time synchronization fine tunes the clock (seconds and milliseconds).
  • Page 487 1MRK 505 370-UUS Rev. K Section 20 Basic IED functions Setting example Station bus Process bus SAM600-TS SAM600-CT SAM600-VT IEC16000167-1-en.vsdx IEC16000167 V1 EN-US Figure 241: Example system Figure describes an example system. The REC and REL are both using the 9-2 stream from the SAM600, and gets its synch from the GPS.
  • Page 488 Section 20 1MRK 505 370-UUS Rev. K Basic IED functions If PTP is not used, use the same synchronization method for the HwSyncSrc as the merging unit provides. For instance, if the merging unit provides PPS as synchronization, use PPS as HwSyncSrc. If either PMU or LDCM in GPS-mode is used, that is, the hardware and software clocks are connected to each other, HwSyncSrc is not used and other means to synchronize the merging unit to the IED is required.
  • Page 489 1MRK 505 370-UUS Rev. K Section 21 Requirements Section 21 Requirements 21.1 Current transformer requirements IP15171-1 v2 M11609-3 v2 The performance of a protection function will depend on the quality of the measured current signal. Saturation of the current transformers (CTs) will cause distortion of the current signals and can result in a failure to operate or cause unwanted operations of some functions.
  • Page 490 Section 21 1MRK 505 370-UUS Rev. K Requirements • Very High Remanence type CT • High Remanence type CT • Low Remanence type CT • Non Remanence type CT The Very High Remanence (VHR) type is a CT with closed iron core (for example. protection classes TPX, P, PX according to IEC, class C, K according to ANSI/IEEE) and with an iron core material (new material, typically new alloy based magnetic materials) that gives a remanent flux higher than 80 % of the saturation flux.
  • Page 491 1MRK 505 370-UUS Rev. K Section 21 Requirements Depending on the protection function phase-to-ground, phase-to-phase and three-phase faults have been tested for different relevant fault positions for example, close in forward and reverse faults, zone 1 reach faults, internal and external faults. The dependability and security of the protection was verified by checking for example, time delays, unwanted operations, directionality, overreach and stability.
  • Page 492 Section 21 1MRK 505 370-UUS Rev. K Requirements 21.1.5 General current transformer requirements M11615-3 v3 The current transformer ratio is mainly selected based on power system data for example, maximum load and/or maximum fault current. It should be verified that the current to the protection is higher than the minimum operating value for all faults that are to be detected with the selected CT ratio.
  • Page 493 1MRK 505 370-UUS Rev. K Section 21 Requirements Maximum primary fundamental frequency fault current on the busbar (A) fmax The rated primary CT current (A) The rated secondary CT current (A) The nominal current of the protection IED (A) The secondary resistance of the CT (W) The resistance of the secondary wire and additional load (W).
  • Page 494 Section 21 1MRK 505 370-UUS Rev. K Requirements 21.1.6.3 Non-directional instantaneous and definitive time, phase and residual overcurrent protection M11622-3 v5 The CTs must have a rated equivalent limiting secondary e.m.f. E that is larger than or equal to the required rated equivalent limiting secondary e.m.f.
  • Page 495 1MRK 505 370-UUS Rev. K Section 21 Requirements The secondary resistance of the CT (W) The resistance of the secondary cable and additional load (W). The loop resistance containing the phase and neutral wires, must be used for faults in solidly grounded systems.
  • Page 496 Section 21 1MRK 505 370-UUS Rev. K Requirements Therefore, the CTs according to class PX, PXR, X and TPS must have a rated knee point e.m.f. E knee that fulfills the following: × × TD S TD S Calculated (Equation 103) EQUATION1893.ANSI V1 EN-US 21.1.7.3 Current transformers according to ANSI/IEEE...
  • Page 497 1MRK 505 370-UUS Rev. K Section 21 Requirements Magnetic or capacitive voltage transformers can be used. The capacitive voltage transformers (CCVTs) should fulfill the requirements according to the IEC 61869-5 standard regarding ferro-resonance and transients. The ferro-resonance requirements of the CCVTs are specified in chapter 6.502 of the standard.
  • Page 498 Section 21 1MRK 505 370-UUS Rev. K Requirements Synchronization in SDH systems with G.703 E1 or IEEE C37.94 The G.703 E1, 2 Mbit shall be set according to ITU-T G.803, G.810-13 • One master clock for the actual network • The actual port Synchronized to the SDH system clock at 2048 kbit •...
  • Page 499 1MRK 505 370-UUS Rev. K Section 21 Requirements Note that the IEC/UCA 61850-9-2LE standard does not specify the quality of the sampled values, only the transportation. Thus, the accuracy of the current and voltage inputs to the merging unit and the inaccuracy added by the merging unit must be coordinated with the requirement for actual type of protection function.
  • Page 501 1MRK 505 370-UUS Rev. K Section 22 Glossary Section 22 Glossary M14893-1 v20 Alternating current Actual channel Application configuration tool within PCM600 A/D converter Analog-to-digital converter ADBS Amplitude deadband supervision Analog digital conversion module, with time synchronization Analog input ANSI American National Standards Institute Access Point Autoreclosing...
  • Page 502 Section 22 1MRK 505 370-UUS Rev. K Glossary CAN carrier module CCVT Capacitive Coupled Voltage Transformer Class C Protection Current Transformer class as per IEEE/ ANSI CMPPS Combined megapulses per second Communication Management tool in PCM600 CO cycle Close-open cycle Codirectional Way of transmitting G.703 over a balanced line.
  • Page 503 1MRK 505 370-UUS Rev. K Section 22 Glossary Digital signal processor Direct transfer trip scheme Ethernet configuration tool EHV network Extra high voltage network Electronic Industries Association Electromagnetic compatibility Electromotive force Electromagnetic interference EnFP End fault protection Enhanced performance architecture Electrostatic discharge F-SMA Type of optical fiber connector...
  • Page 504 Section 22 1MRK 505 370-UUS Rev. K Glossary High-availability Seamless Redundancy High-voltage HVDC High-voltage direct current IDBS Integrating deadband supervision International Electrical Committee IEC 60044-6 IEC Standard, Instrument transformers – Part 6: Requirements for protective current transformers for transient performance IEC 60870-5-103 Communication standard for protection equipment.
  • Page 505 1MRK 505 370-UUS Rev. K Section 22 Glossary International Telecommunications Union Local area network LIB 520 High-voltage software module Liquid crystal display LDAPS Lightweight Directory Access Protocol LDCM Line data communication module Local detection device Light-emitting diode LON network tool Local operating network Miniature circuit breaker Mezzanine carrier module...
  • Page 506 Section 22 1MRK 505 370-UUS Rev. K Glossary Process bus Bus or LAN used at the process level, that is, in near proximity to the measured and/or controlled components Parallel redundancy protocol Power supply module Parameter setting tool within PCM600 Precision time protocol PT ratio Potential transformer or voltage transformer ratio...
  • Page 507 1MRK 505 370-UUS Rev. K Section 22 Glossary Switch for CB ready condition Switch or push button to trip Starpoint Neutral/Wye point of transformer or generator Static VAr compensation Trip coil Trip circuit supervision Transmission control protocol. The most common transport layer protocol used on Ethernet and the Internet.
  • Page 508 Section 22 1MRK 505 370-UUS Rev. K Glossary Three times zero-sequence current.Often referred to as the residual or the ground-fault current Three times the zero sequence voltage. Often referred to as the residual voltage or the neutral point voltage Busbar protection REB670 Application manual ©...
  • Page 510 ABB Power Grids Sweden AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 10 738 00 00 Scan this QR code to visit our website https://hitachiabb-powergrids.com/protection-control © 2017 - 2021 Hitachi Power Grids. All rights reserved...

This manual is also suitable for:

Relion reb670

Table of Contents