Beko BEKOMAT 12 Original Installation And Operation Manual page 35

Table of Contents

Advertisement

Original installation and operation manual
Illustration
t = 30 ms
n = 20
t = 30 ms
t = 30 ms
t = 40 ms (BM12)
t = 140 ms (BM13)
t = 500 ms
For further information about fault indications during operation see "15. Troubleshooting / FAQ" on Page 55.
n = 2
t = 500 ms
n = ∞
t = 30 ms
t = 970 ms
Fail-Safe
t = 500 ms
n = ∞
BEKOMAT
Description / explanation
Positive power-on self-test (repeat 2x)
The red Alarm LED is off
The green Valve LED lights up during the solenoid
valve cycles
The green Power LED is on
The solenoid valve cycles
0 goes into normal operation
Negative power-on self-test (repeat 20x)
The red Alarm LED is on
The green Valve LED lights up during the solenoid
valve cycles
The green Power LED is on
The solenoid valve cycles
0 Goes to fail-safe operation (continuous loop)
The solenoid valve cycles once per second
Ready for operation (normal operating mode)
The red Alarm LED is off
The green Valve LED is off
The green Power LED is on
Discharge procedure
(TEST button pressed briefly)
The red Alarm LED is off
The green Valve LED lights up during the discharge
procedure
The green Power LED is on
Pre-alarm (
TEST button pressed >1 min and <5 min
The red Alarm LED flashes
The green Valve LED is on
The green Power LED is on
Alarm
(TEST button pressed >5 min)
The red Alarm LED is on
The green Valve LED is off
The green Power LED is on
Alarm mode (problem with condensate discharge)
The red Alarm LED flashes
The green Power LED lights up
The green Valve LED lights up during the solenoid
valve cycles
The solenoid valve sets a cycle every 4 minutes
0 Passes to normal mode with free condensate discharge
12, 12 CO, 12 CO PN63
®
)
35 | 64

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bekomat 12 coBm12Bm12coBm12copn63Bekomat 12 co pn63

Table of Contents