Mitsubishi Electric ecodan ECOSLIM150L-PP-MEUK Installation Manual page 39

Table of Contents

Advertisement

Electrical Installation
23
A.
Earth terminal
B.
Terminal block
C.
Clamp
D.
Service panel
E.
Wire the cables so
that they do not contact the
centre of the service panel
Outdoor Model Number
Outdoor unit power supply
Outdoor unit Circuit Breaker Capacity
Wiring Wire
No. x size
(mm²)
Circuit
Rating
*1.
A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker
(NV). The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
*2.
Max. 120 m
*3.
The values given in the table above are not always measured against the ground value.
*
1
Outdoor unit power supply
including earth
Interface unit/flow temp.
*
2
controller– outdoor unit
Remote controller-Interface
unit/ Flow temp. controller
Outdoor unit L-N (single)
*
3
Outdoor unit L1-N, L2-N,
L3-N (3 phase)
Interface unit/Flow temp.
*
3
controller-outdoor unit
S2-S3
Remote controller-Interface *
3
unit/Flow temp.
controller
(continued)
PUHZ-
PUHZ-
W50VHA-BS
W85VHA(2)-BS
~/N (single),
~/N (single),
50Hz, 230V
50Hz, 230V
16 A
32 A
3 x Min. 2.5
3 x Min. 4
2 x 1.5
2 x 1.5
(polar)
(polar)
2 x 0.3
2 x 0.3
(non-polar)
(non-polar)
AC 230 V
AC 230 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V
Pre-Plumbed Slimline Cylinder Installation Manual
PUHZ-
PUHZ-
HW140VHA(2)-BS
HW140YHA(2)-BS
~/N (single),
3N (3 phase),
50Hz, 230V
50Hz, 415V
40 A
16 A
3 x Min. 6
5 x Min. 2.5
2 x 1.5
3 x 1.5
(polar)
(polar)
2 x 0.3
2 x 0.3
(non-polar)
(non-polar)
AC 230 V
AC 415 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V
39